Panasonic CU-2Z35TBE Service Manual Download Page 8

   

CAUTION

 

2. 

2-9. Checks to the refrigeration equipment 

 

Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. 

 

At all times the manufacturer’s maintenance and service guidelines shall be followed. 

 

If in doubt consult the manufacturer’s technical department for assistance. 

 

The following checks shall be applied to installations using flammable refrigerants. 
-       The actual refrigerant charge is in accordance with the room size within which the refrigerant containing parts are installed. 
-       The ventilation machinery and outlets are operating adequately and are not obstructed. 
-       If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant. 
-       Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected. 
-       Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which  
        may corrode refrigerant containing components, unless the components are constructed of materials which are inherently  
        resistant to being corroded or are properly protected against being so corroded. 

2-10. Checks to electrical devices 

 

Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. 

 

Initial safety checks shall include but not limit to:- 
-       That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking. 
-       That there is no live electrical components and wiring are exposed while charging, recovering or purging the system. 
-       That there is continuity of earth bonding. 

 

At all times the manufacturer’s maintenance and service guidelines shall be followed. 

 

If in doubt consult the manufacturer’s technical department for assistance. 

 

If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt 
with. 

 

If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. 

 

The owner of the equipment must be informed or reported so all parties are advised thereinafter.

3. 

Repairs to sealed components 

 

During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to 
any removal of sealed covers, etc. 

 

If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak 
detection shall be located at the most critical point to warn of a potentially hazardous situation. 

 

Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in 
such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals 
not made to original specification, damage to seals, incorrect fitting of glands, etc. 

 

Ensure that apparatus is mounted securely. 

 

Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of 
flammable atmospheres. 

 

Replacement parts shall be in accordance with the manufacturer’s specifications. 

 

NOTE: 

The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. 
Intrinsically safe components do not have to be isolated prior to working on them. 

4. 

Repair to intrinsically safe components 

 

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible 
voltage and current permitted for the equipment in use. 

 

Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. 

 

The test apparatus shall be at the correct rating. 

 

Replace components only with parts specified by the manufacturer. Unspecified parts by manufacturer may result ignition of 
refrigerant in the atmosphere from a leak. 

5. 

Cabling 

 

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse 
environmental effects. 

 

The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.

6. 

Detection of flammable refrigerants 

 

Under no circumstances shall potential sources of ignition be used in the searching or detection of refrigerant leaks. 

 

A halide torch (or any other detector using a naked flame) shall not be used. 

 

The following leak detection methods are deemed acceptable for all refrigerant systems. 
-       No leaks shall be detected when using detection equipment with a sensitivity of 5 grams per year of refrigerant or better under  
        a pressure of at least 0,25 times the maximum allowable pressure (>1.04MPa, max 4.15MPa) for example, a universal sniffer. 
-       Electronic leak detectors may be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need  
        re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) 
-       Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. 
-       Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant  
        employed and the appropriate percentage of gas (25 % maximum) is confirmed. 
-       Leak detection fluids are also suitable for use with most refrigerants, for example, bubble method and fluorescent method  
        agents. The use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode  
        the copper pipe-work. 
-       If a leak is suspected, all naked flames shall be removed/extinguished. 
-       If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated  
        (by means of shut off valves) in a part of the system remote from the leak. The precautions in #7 must be followed to remove  
        the refrigerant. 

 
 
 
 
 
 

Summary of Contents for CU-2Z35TBE

Page 1: ...serviced or repaired only by experienced professional technicians Any attempt to service or repair the products dealt with in this service information by anyone else could result in serious injury or death There are special components used in this equipment which are important for safety These parts are marked by in the Schematic Diagrams Circuit Board Diagrams Exploded Views and Replacement Parts...

Page 2: ...efrigerant 6 3 Specifications 11 4 Exploded View and Replacement Parts List 13 4 1 CU 2Z35TBE CU 2Z41TBE CU 2Z50TBE 13 4 2 CU 3Z52TBE CU 3Z68TBE CU 4Z68TBE 16 4 3 CU 4Z80TBE CU 5Z90TBE 20 Specifications designs and contents in this Service Manual are subject to change without notice ...

Page 3: ... into the unit high speed rotating fan may cause injury 6 Do not sit or step on the unit you may fall down accidentally 7 Keep plastic bag packaging material away from small children it may cling to nose and mouth and prevent breathing 8 When installing or relocating air conditioner do not let any substance other than the specified refrigerant eg air etc mix into refrigeration cycle piping Mixing ...

Page 4: ...on will cause suck in of air abnormal high pressure in refrigeration cycle and result in explosion injury etc 21 During pump down operation stop the compressor before removing the refrigeration piping Removal of refrigeration piping while compressor is operating and valves are opened will cause suck in of air abnormal high pressure in refrigeration cycle and result in explosion injury etc 22 Tight...

Page 5: ...e solder has a higher melting point than standard solder typically the melting point is 50 F 70 F 30 C 40 C higher Please use a high temperature solder iron In case of the soldering iron with temperature control please set it to 700 20 F 370 10 C Pb free solder will tend to splash when heated too high about 1100 F 600 C 11 Power supply connection to the room air conditioner Use power supply cord 3...

Page 6: ...arly check the alarms mechanical ventilation and detectors at least once a year where as required by national regulations to ensure their correct functioning 8 A logbook shall be maintained The results of these checks shall be recorded in the logbook 9 In case of ventilations in occupied spaces shall be checked to confirm no obstruction 10 Before a new refrigerating system is put into service the ...

Page 7: ...m 2 3 Work procedure Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapour being present while the work is being performed 2 4 General work area All maintenance staff and others working in the local area shall be instructed and supervised on the nature of work being carried out Avoid working in confined spaces Always ensure away from source a...

Page 8: ...nals not made to original specification damage to seals incorrect fitting of glands etc Ensure that apparatus is mounted securely Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres Replacement parts shall be in accordance with the manufacturer s specifications NOTE The use of silicon sealant may inh...

Page 9: ...eate a hazardous condition when charging and discharging the refrigerant To avoid fire or explosion dissipate static electricity during transfer by grounding and bonding containers and equipment before charging discharging 9 Decommissioning Before carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its details It is recommended good pra...

Page 10: ...frigerants In addition a set of calibrated weighing scales shall be available and in good working order Hoses shall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in satisfactory working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigera...

Page 11: ...30 Additional gas amount over chargeless length g m 15 15 15 20 20 Note Available Remarks for CU 2Z35TBE CU 2Z41TBE CU 2Z50TBE 1 At least two indoor units must be connected 2 The total nominal cooling capacity of indoor unit that will be connected to outdoor unit must be within connectable capacity range of indoor unit as shown in the table above Example The indoor units combination below is possi...

Page 12: ...18 3kW Pipe length 1 room maximum pipe length m 25 25 25 Allowable elevation m 15 15 15 Total allowable pipe length m 60 70 80 Total pipe length for maximum chargeless length m 30 45 45 Additional gas amount over chargeless length g m 20 20 20 Note Available Remarks for CU 4Z68TBE CU 4Z80TBE CU 5Z90TBE 1 At least two indoor units must be connected 2 The total nominal cooling capacity of indoor uni...

Page 13: ...9 77 72 50 80 64 65 66 67 68 69 70 40 36 47 3 56 75 4 5 32 34 52 31 13 2 55 19 26 21 78 20 27 14 29 35 48 8 46 73 73 41 6 8 7 18 10 11 12 76 9 54 1 24 25 74 43 44 22 18 57 49 37 38 51 45 53 33 82 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 14: ...B111080 24 V COIL COMPLETE CN EV1 WHITE 1 CWA43C2579 Ο 25 V COIL COMPLETE CN EV2 YELLOW 1 CWA43C2580 Ο 26 V COIL COMPLETE 4 WAY VALVE 1 CWA43C2585 Ο 27 SOUND PROOF BOARD 1 CWH151364 29 SENSOR COMPLETE AIR TEMP SENSOR CN TH1 1 CWA50C3078 Ο 31 SENSOR COMPLETE GAS PIPE TEMP CN TH4 1 CWA50C3070 Ο 32 SENSOR COMPLETE DEFROST SENSOR CN TH2 1 CWA50C3069 Ο 33 HOLDER SENSOR 6 CWH32143 34 SENSOR COMPLETE TAN...

Page 15: ...INSTRUCTION 1 ACXF60 06580 66 INSTALLATION INSTRUCTION 1 ACXF60 06590 67 INSTALLATION INSTRUCTION 1 ACXF60 06600 68 INSTALLATION INSTRUCTION 1 ACXF60 06610 69 INSTALLATION INSTRUCTION 1 ACXF60 06620 70 INSTALLATION INSTRUCTION 1 ACXF60 06630 71 INSTALLATION INSTRUCTION 1 ACXF60 06640 72 INSTALLATION INSTRUCTION 1 ACXF60 06650 73 DISCHARGE MUFFLER 2 ACXB12 00610 74 DISCHARGE MUFFLER 1 ACXB12 01180 ...

Page 16: ... 50 89 5 4 8 9 6 7 3 4 2 29 28 31 44 60 59 24 25 24 57 38 32 40 41 39 15 36 37 35 34 23 26 79 22 21 33 82 56 76 19 20 17 18 27 16 77 53 30 80 81 74 13 12 11 1 47 10 14 75 83 54 91 78 79 CU 4Z68TBE only 84 85 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 17: ...2 Ο 19 HOLDER COUPLING 1 CWH351258 20 STRAINER 1 CWB11061 21 STRAINER 3 4 CWB111024 22 EXPANSION VALVE 3 4 CWB051029 Ο 23 4 WAYS VALVE WITH SCREW 1 CWB001026JX Ο 24 DISCHARGE MUFFLER 2 ACXB12 00650 25 HEATING PRESSURE SWITCH 1 CWA101013 26 FLARE NUT 1 4 3 4 CWT251030 27 FLARE NUT 3 8 3 4 CWT251031 28 SOUND PROOF MATERIAL 1 CWG302246 29 SOUND PROOR MATERIAL 1 CWG302520 30 SOUND PROOR MATERIAL 1 CWG...

Page 18: ...0300J 61 INSTALLATION INSTRUCTION 1 ACXF60 06660 62 INSTALLATION INSTRUCTION 1 ACXF60 06670 63 INSTALLATION INSTRUCTION 1 ACXF60 06680 64 INSTALLATION INSTRUCTION 1 ACXF60 06690 65 INSTALLATION INSTRUCTION 1 ACXF60 06700 66 INSTALLATION INSTRUCTION 1 ACXF60 06710 67 INSTALLATION INSTRUCTION 1 ACXF60 06720 68 INSTALLATION INSTRUCTION 1 ACXF60 06730 69 INSTALLATION INSTRUCTION 1 ACXF60 06740 70 INST...

Page 19: ...87 BASE BOARD COMPLETE 1 CWG62C1081 88 SHOCK ABSORBER 1 CWG712879 89 SHOCK ABSORBER 1 CWG712880 90 C C CASE 1 ACXG50 52321 91 MODEL LABEL 2 ACXF82 22640 ACXF82 22660 ACXF82 22670 Note All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock ...

Page 20: ...8 74 1 16 10 13 12 60 14 59 58 21 17 18 22 78 6 2 55 47 3 7 4 9 54 58 61 I I 66 I I 67 I I 68 I I 69 I I 80 I I 81 I I 62 I I 63 I I 64 I I 65 I I 56 57 82 83 86 85 84 92 90 88 89 91 90 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 21: ...22 EXPANSION VALVE 4 CWB051029 Ο 23 4 WAYS VALVE WITH SCREW 1 CWB001026JX Ο 24 DISCHARGE MUFFLER 2 ACXB12 00650 25 HEATING PRESSURE SWITCH 1 CWA101013 Ο 26 FLARE NUT 1 4 4 CWT251030 27 FLARE NUT 3 8 4 CWT251031 28 SOUND PROOF MATERIAL 1 CWG302804 31 SOUND PROOF MATERIAL 1 CWG302801 32 SENSOR COMPLETE DISCHARGE TEMP SENSOR CN DIS 1 CWA50C3091 Ο 33 V COIL CO 4 WAY VALVE CN HOT 1 CWA43C2586 Ο 34 V CO...

Page 22: ...COVER 1 CWH7080300J 61 INSTALLATION INSTRUCTION 1 ACXF60 16610 62 INSTALLATION INSTRUCTION 1 ACXF60 16620 63 INSTALLATION INSTRUCTION 1 ACXF60 16630 64 INSTALLATION INSTRUCTION 1 ACXF60 16640 65 INSTALLATION INSTRUCTION 1 ACXF60 16650 66 INSTALLATION INSTRUCTION 1 ACXF60 16660 67 INSTALLATION INSTRUCTION 1 ACXF60 16670 68 INSTALLATION INSTRUCTION 1 ACXF60 16680 69 INSTALLATION INSTRUCTION 1 ACXF60...

Page 23: ...TBE REMARK 90 SHOCK ABSORBER 2 CWG713581 91 SHOCK ABSORBER 1 CWG713582 92 C C CASE 1 ACXG50 52041 93 MODEL LABEL 2 ACXF82 44380 Note All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock ...

Page 24: ... EXPANSION VALVE 5 CWB051029 Ο 23 4 WAYS VALVE WITH SCREW 1 CWB001026JX Ο 24 DISCHARGE MUFFLER 2 ACXB12 00650 25 HEATING PRESSURE SWITCH 1 CWA101013 Ο 26 FLARE NUT 1 4 5 CWT251030 27 FLARE NUT 3 8 5 CWT251031 28 SOUND PROOF MATERIAL 1 CWG302804 31 SOUND PROOF MATERIAL 1 CWG302801 32 SENSOR COMPLETE DISCHARGE TEMP SENSOR CN DIS 1 CWA50C3091 Ο 33 V COIL CO 4 WAY VALVE CN HOT 1 CWA43C2586 Ο 34 V COIL...

Page 25: ...171039A 60 NUT TERMINAL COVER 1 CWH7080300J 61 INSTALLATION INSTRUCTION 1 ACXF60 16610 62 INSTALLATION INSTRUCTION 1 ACXF60 16620 63 INSTALLATION INSTRUCTION 1 ACXF60 16630 64 INSTALLATION INSTRUCTION 1 ACXF60 16640 65 INSTALLATION INSTRUCTION 1 ACXF60 16650 66 INSTALLATION INSTRUCTION 1 ACXF60 16660 67 INSTALLATION INSTRUCTION 1 ACXF60 16670 68 INSTALLATION INSTRUCTION 1 ACXF60 16680 69 INSTALLAT...

Page 26: ...K ABSORBER 2 CWG713581 91 SHOCK ABSORBER 1 CWG713582 92 C C CASE 1 ACXG50 52041 93 MODEL LABEL 2 ACXF82 44390 Note All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock PAPAMY Printed in Malaysia SY0321 0 ...

Reviews: