61
•
How to pull the piping and drain hose out, in case of the
embedded piping.
•
In case of left piping how to insert the
connection cable and drain hose.
Rear view for left piping installation
Drain cap
Drain hose
Adjust the piping slightly
downwards.
Drain hose
Connection cable
PVC tube
for drain
hose
Indoor unit
Piping
Cable
Apply putty or
caulking material
to seal the wall
opening.
Connection cable
Piping
More than
470 mm
PVC tube (VP-65) for piping
and connection cable
PVC tube for drain hose (VP-30)
PVC tube for drain
hose (VP-20)
More than 700 mm
Drain hose
from main unit
Cable
45°
Drain
hose
Piping
Sleeve for piping hole
Drain hose
Piping
Connection cable
More than 950 mm
(For the right piping, follow the same procedure)
Replace the drain hose
(3/4 ~ 1.75HP) or
more than 1150 mm
(2.0 ~ 3.0HP)
More than 950 mm
(3/4 ~ 1.75HP) or more
than 1150 mm (2.0 ~ 3.0HP)
72 mm (3/4 ~ 1.75HP) or
82 mm (2.0 ~ 3.0HP)
12.2.4 Connect the Cable to the Indoor Unit
1 The inside and outside connection cable can be connected without removing the front grille.
2
Connection cable
between indoor unit and outdoor unit shall be approved polychloroprene sheathed
4 x 1.5 mm
2
flexible cord, type designation 60245 IEC 57 or heavier cord. Do not use joint connection cable.
Replace the wire if the existing wire (from concealed wiring, or otherwise) is too short. Allowable connection
cable length of each indoor unit shall be 30 m or less.
3 Bind all the indoor and outdoor connection cable with tape and route the connection cable via the
escapement.