Safety Precautions

3. Repairs to sealed components

• During repairs to sealed components, all 

electrical supplies shall be disconnected from 
the equipment being worked upon prior to any 
removal of sealed covers, etc.

• If it is absolutely necessary to have an 

electrical supply to equipment during 
servicing, then a permanently operating 
form of leak detection shall be located at the 
most critical point to warn of a potentially 
hazardous situation.

• Particular attention shall be paid to the 

following to ensure that by working on 
electrical components, the casing is not 
altered in such a way that the level of 
protection is affected. This shall include 
damage to cables, excessive number of 
connections, terminals not made to original 
speci

fi

 cation, damage to seals, incorrect 

fi

 tting 

of glands, etc.

• Ensure that apparatus is mounted securely.
• Ensure that seals or sealing materials have 

not degraded such that they no longer serve 
the purpose of preventing the ingress of 

fl

 ammable atmospheres.

• Replacement parts shall be in accordance 

with the manufacturer’s speci

fi

 cations.

NOTE: The use of silicon sealant may inhibit 
the effectiveness of some types of leak 
detection equipment.
Intrinsically safe components do not have to be 
isolated prior to working on them.

4. Repair to intrinsically safe components

• Do not apply any permanent inductive or 

capacitance loads to the circuit without 
ensuring that this will not exceed the 
permissible voltage and current permitted for 
the equipment in use.

• Intrinsically safe components are the only 

types that can be worked on while live in the 
presence of a 

fl

 ammable atmosphere.

• The test apparatus shall be at the correct 

rating.

• Replace components only with parts speci

fi

 ed 

by the manufacturer. Unspeci

fi

 ed parts by 

manufacturer may result ignition of refrigerant 
in the atmosphere from a leak.

5. Cabling

• Check that cabling will not be subject 

to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse 
environmental effects.

• The check shall also take into account the 

effects of aging or continual vibration from 
sources such as compressors or fans.

6. Detection of 

fl

 ammable refrigerants

• Under no circumstances shall potential 

sources of ignition be used in the searching or 
detection of refrigerant leaks.

• A halide torch (or any other detector using a 

naked 

fl

 ame) shall not be used.

7. The following leak detection methods 

are deemed acceptable for all refrigerant 
systems

• No leaks shall be detected when using 

detection equipment with a sensitivity of 
5 grams per year of refrigerant or better 
under a pressure of at least 0.25 times the 
maximum allowable pressure (>1.04 MPa, 
max 4.15 MPa), for example, a universal 
sniffer.

• Electronic leak detectors may be used 

to detect 

fl

 ammable refrigerants, but the 

sensitivity may not be adequate, or may need 
re-calibration.
(Detection equipment shall be calibrated in a 
refrigerant-free area.)

• Ensure that the detector is not a potential 

source of ignition and is suitable for the 
refrigerant used.

• Leak detection equipment shall be set at a 

percentage of the LFL of the refrigerant and 
shall be calibrated to the refrigerant employed 
and the appropriate percentage of gas (25 % 
maximum) is con

fi

 rmed.

• Leak detection 

fl

uids are also suitable for use 

with most refrigerants, for example, bubble 
method and 

fl

uorescent method agents. The 

use of detergents containing chlorine shall 
be avoided as the chlorine may react with the 
refrigerant and corrode the copper pipe-work.

• If a leak is suspected, all naked 

fl

 ames shall 

be removed/extinguished.

• If a leakage of refrigerant is found which 

requires brazing, all of the refrigerant shall 
be recovered from the system, or isolated 
(by means of shut off valves) in a part of the 
system remote from the leak. The precautions 
in #8 must be followed to remove the 
refrigerant.

English

Summary of Contents for CS-XU10XKH

Page 1: ...oughly and keep them for future reference Before installation the installer should Read the Installation Instructions then request the customer keep them for future reference Remove the remote control...

Page 2: ...the remote control receiver on the indoor unit Quick Guide Inserting the batteries 1 2 3 1 Pull out the back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 P...

Page 3: ...purposes only and may differ from the actual unit They are subject to change without notice B Basic operation Thank you for purchasing Panasonic Air Conditioner 1 Press to start stop the operation POW...

Page 4: ...supervised to ensure that they do not play with the appliance Please consult an authorised dealer or specialist to clean the internal parts repair install remove disassemble and reinstall the unit Im...

Page 5: ...not wash the indoor unit with water benzine thinner or scouring powder to avoid damage or corrosion at the unit Do not use for preservation of precise equipment food animals plants artwork or other o...

Page 6: ...l the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of...

Page 7: ...he precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised a...

Page 8: ...ernally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the...

Page 9: ...the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also t...

Page 10: ...minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging...

Page 11: ...employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refri...

Page 12: ...manually This operation can be activated even when the unit is OFF Note that the flap and fan speed will operate according to the remote control setting If a power failure occurs during this operatio...

Page 13: ...s to turn on the unit in iAUTO X mode How to Use To reach the desired temperature quickly For Wireless LAN Module operation setup please refer to Setup Instructions Manual To connect to a network This...

Page 14: ...ive setting or then press The nearest timer setting is displayed and will activate in sequence The timer operation follows the clock setting on the remote control and will repeat daily when timer has...

Page 15: ...ailure the operation will restart automatically with the last operation mode and airflow direction This control is not applicable when TIMER is set nanoe X filter deactivation Depending on the unit s...

Page 16: ...cleaned periodically by an authorised dealer Outdoor unit Clean the debris that surround the unit Clear any blockage from the drain pipe Front panel Wash gently and dry How to remove front panel AUTO...

Page 17: ...heat sun light UV light or environmental factors After extended use dust may cover the front panel grilles and the wall surrounding the unit The dust accumulation is due to the air purification effec...

Page 18: ...refer The remote control is missing or a malfunction has occurred above After 15 minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents C...

Page 19: ...r abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdoor mis...

Page 20: ...1 2 3 1 2 AAA R03 3 8 m A B A 1 CLOCK 12 am pm 24 CLOCK 5 2 20...

Page 21: ...B 2 DRY iAUTO X COOL 1 POWER ON 3 TEMP UP TEMP DOWN 16 0 C 30 0 C 60 F 86 F C F 10 22 33 34 36 37 38 39 40 41 45 47 AAA R03 2 2 Panasonic Burmese 21...

Page 22: ...22...

Page 23: ...ELCB RCD ELCB Burmese 23...

Page 24: ...Ni Cd nanoeTM G 24...

Page 25: ...R32 Amin m Amin m R32 R410A R22 R22 R22 R32 R32 R410A R32 R410A Flare Nut R32 R410A R22 R32 R410A 1 2 inch R32 R410A Burmese 25...

Page 26: ...AHU 5 1 04MPa 4 15MPa 0 25 26...

Page 27: ...1 Amin m 12 2 2 1 2 2 2 2 2 8 2 m 2 m Burmese 27...

Page 28: ...2 3 2 4 CO2 2 5 2 6 2 7 28...

Page 29: ...2 8 capacitors discharged 3 Burmese 29...

Page 30: ...4 5 6 7 5 1 04MPa 4 15MPa 0 25 LFL 25 8 30...

Page 31: ...8 OFN OFN OFN OFN 9 OFN 7 Burmese 31...

Page 32: ...10 Recover Machine Recover Machine 80 11 32...

Page 33: ...12 Burmese 33...

Page 34: ...To adjust airflow direction LAN ON OFF FAN SPEED FAN AUTO iAUTO X AUTO iAUTO X QUIET FAN SPEED QUIET nanoeTM X nanoeTM G nanoeTM TECHNOLOGY nanoeTM TECHNOLOGY OFF 34...

Page 35: ...LAN 0 5 1 2 3 4 5 6 7 8 9 OFF 0 0h iAUTO X 2 C 4 F AUTO 4 iAUTO X iAUTO X 23 C 60 iAUTO X iAUTO X iAUTO X 2 C 4 F 4 Burmese 35...

Page 36: ...2 3 1 2 1 TIMER ON TIMER OFF 22 00 OFF 2 3 36...

Page 37: ...iAUTO X COOL DRY COOL 26 0 C 28 0 C 79 F 82 F COOL DRY iAUTO X COOL DRY iAUTO X TIMER nanoe X nanoeTM X nanoeTM X COOL DRY 2 5 nanoeTM TECHNOLOGY 2 Burmese 37...

Page 38: ...C F DBT WBT DBT WBT COOL 32 89 6 23 73 4 46 114 8 26 78 8 16 60 8 11 51 8 16 60 8 11 51 8 DBT WBT 38...

Page 39: ...H 99 pH 7 40 C 104 F AUTO OFF ON 2 A B 1 B A AUTO OFF ON 2 1 3 4 AUTO OFF ON nanoeTM G Burmese 39...

Page 40: ...nanoeTM G 2 2 40...

Page 41: ...POWER TIMER ON 15 TIMER ON UV Burmese 41...

Page 42: ...COOL nanoeTM TECHNOLOGY nanoeTM TECHNOLOGY ON nanoeTM G nanoeTM TECHNOLOGY nanoeTM X nanoeTM TECHNOLOGY OFF LAN ON LAN 42...

Page 43: ...AUTO OFF ON 1 2 iAUTO X AUTO OFF ON 3 COOL 1 AUTO OFF ON 4 AUTO OFF ON 5 COOL AUTO OFF ON 15 8 C 14 4 F nanoeTM TECHNOLOGY 2 3 Burmese 43...

Page 44: ...H 00 H 11 H 12 H 14 H 15 H 16 current transformer CT H 17 H 19 H 21 Float Switch H 23 1 H 24 2 H 25 H 26 Negative H 27 H 28 1 H 30 Discharge Pipe H 31 H 32 2 H 33 H 34 H 35 H 36 Gas Pipe H 37 Liquid P...

Page 45: ...52 Limit Switch H 58 H 59 H 64 H 67 nanoe H 70 H 71 H 72 H 85 LAN H 97 H 98 H 99 F 11 4 way F 16 F 17 F 18 Dry Circuit F 87 PCB F 90 Power Factor F 91 F 93 F 94 F 95 Cooling Side F 96 F 97 F 98 F 99 D...

Page 46: ...tion with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flammable refrigerant If t...

Page 47: ...47 Pb...

Page 48: ...Printed in Malaysia Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2021 ACXF55 29860 SZ0221 0...

Reviews: