Safety Precautions

e) If a vacuum is not possible, make a 

manifold so that refrigerant can be 
removed from various parts of the system.

f)  Make sure that cylinder is situated on the 

scales before recovery takes place.

g) Start the recovery machine and operate in 

accordance with instructions.

h) Do not over 

fi

 ll cylinders. (No more than 

80 % volume liquid charge).

i)  Do not exceed the maximum working 

pressure of the cylinder, even temporarily.

j)  When the cylinders have been 

fi

 lled 

correctly and the process completed, make 
sure that the cylinders and the equipment 
are removed from site promptly and all 
isolation valves on the equipment are 
closed off.

k) Recovered refrigerant shall not be charged 

into another refrigerating system unless it 
has been cleaned and checked.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
or discharging the refrigerant. To avoid 

fi

 re or 

explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

11. Labelling

• Equipment shall be labelled stating that it 

has been de-commissioned and emptied of 
refrigerant.

• The label shall be dated and signed.
• Ensure that there are labels on the equipment 

stating the equipment contains 

fl

 ammable 

refrigerant.

12. Recovery

• When removing refrigerant from a system, 

either for servicing or decommissioning, 
it is recommended good practice that all 
refrigerants are removed safely.

• When transferring refrigerant into cylinders, 

ensure that only appropriate refrigerant 
recovery cylinders are employed.

• Ensure that the correct number of cylinders 

for holding the total system charge are 
available.

• All cylinders to be used are designated for 

the recovered refrigerant and labelled for 
that refrigerant (i.e. special cylinders for the 
recovery of refrigerant).

• Cylinders shall be complete with pressure 

relief valve and associated shut-off valves in 
good working order.

• Recovery cylinders are evacuated and, if 

possible, cooled before recovery occurs.

• The recovery equipment shall be in good 

working order with a set of instructions 
concerning the equipment that is at hand and 
shall be suitable for the recovery of 

fl

 ammable 

refrigerants.

• In addition, a set of calibrated weighing scales 

shall be available and in good working order.

• Hoses shall be complete with leak-free 

disconnect couplings and in good condition.

• Before using the recovery machine, check 

that it is in satisfactory working order, has 
been properly maintained and that any 
associated electrical components are sealed 
to prevent ignition in the event of a refrigerant 
release. Consult manufacturer if in doubt.

• The recovered refrigerant shall be returned to 

the refrigerant supplier in the correct recovery 
cylinder, and the relevant Waste Transfer 
Note arranged.

• Do not mix refrigerants in recovery units and 

especially not in cylinders.

• If compressors or compressor oils are to 

be removed, ensure that they have been 
evacuated to an acceptable level to make 
certain that 

fl

 ammable refrigerant does not 

remain within the lubricant.

• The evacuation process shall be carried 

out prior to returning the compressor to the 
suppliers.

• Only electric heating to the compressor body 

shall be employed to accelerate this process.

• When oil is drained from a system, it shall be 

carried out safely.

English

Summary of Contents for CS-XU10XKH

Page 1: ...oughly and keep them for future reference Before installation the installer should Read the Installation Instructions then request the customer keep them for future reference Remove the remote control...

Page 2: ...the remote control receiver on the indoor unit Quick Guide Inserting the batteries 1 2 3 1 Pull out the back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 P...

Page 3: ...purposes only and may differ from the actual unit They are subject to change without notice B Basic operation Thank you for purchasing Panasonic Air Conditioner 1 Press to start stop the operation POW...

Page 4: ...supervised to ensure that they do not play with the appliance Please consult an authorised dealer or specialist to clean the internal parts repair install remove disassemble and reinstall the unit Im...

Page 5: ...not wash the indoor unit with water benzine thinner or scouring powder to avoid damage or corrosion at the unit Do not use for preservation of precise equipment food animals plants artwork or other o...

Page 6: ...l the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of...

Page 7: ...he precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised a...

Page 8: ...ernally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the...

Page 9: ...the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also t...

Page 10: ...minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging...

Page 11: ...employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refri...

Page 12: ...manually This operation can be activated even when the unit is OFF Note that the flap and fan speed will operate according to the remote control setting If a power failure occurs during this operatio...

Page 13: ...s to turn on the unit in iAUTO X mode How to Use To reach the desired temperature quickly For Wireless LAN Module operation setup please refer to Setup Instructions Manual To connect to a network This...

Page 14: ...ive setting or then press The nearest timer setting is displayed and will activate in sequence The timer operation follows the clock setting on the remote control and will repeat daily when timer has...

Page 15: ...ailure the operation will restart automatically with the last operation mode and airflow direction This control is not applicable when TIMER is set nanoe X filter deactivation Depending on the unit s...

Page 16: ...cleaned periodically by an authorised dealer Outdoor unit Clean the debris that surround the unit Clear any blockage from the drain pipe Front panel Wash gently and dry How to remove front panel AUTO...

Page 17: ...heat sun light UV light or environmental factors After extended use dust may cover the front panel grilles and the wall surrounding the unit The dust accumulation is due to the air purification effec...

Page 18: ...refer The remote control is missing or a malfunction has occurred above After 15 minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents C...

Page 19: ...r abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdoor mis...

Page 20: ...1 2 3 1 2 AAA R03 3 8 m A B A 1 CLOCK 12 am pm 24 CLOCK 5 2 20...

Page 21: ...B 2 DRY iAUTO X COOL 1 POWER ON 3 TEMP UP TEMP DOWN 16 0 C 30 0 C 60 F 86 F C F 10 22 33 34 36 37 38 39 40 41 45 47 AAA R03 2 2 Panasonic Burmese 21...

Page 22: ...22...

Page 23: ...ELCB RCD ELCB Burmese 23...

Page 24: ...Ni Cd nanoeTM G 24...

Page 25: ...R32 Amin m Amin m R32 R410A R22 R22 R22 R32 R32 R410A R32 R410A Flare Nut R32 R410A R22 R32 R410A 1 2 inch R32 R410A Burmese 25...

Page 26: ...AHU 5 1 04MPa 4 15MPa 0 25 26...

Page 27: ...1 Amin m 12 2 2 1 2 2 2 2 2 8 2 m 2 m Burmese 27...

Page 28: ...2 3 2 4 CO2 2 5 2 6 2 7 28...

Page 29: ...2 8 capacitors discharged 3 Burmese 29...

Page 30: ...4 5 6 7 5 1 04MPa 4 15MPa 0 25 LFL 25 8 30...

Page 31: ...8 OFN OFN OFN OFN 9 OFN 7 Burmese 31...

Page 32: ...10 Recover Machine Recover Machine 80 11 32...

Page 33: ...12 Burmese 33...

Page 34: ...To adjust airflow direction LAN ON OFF FAN SPEED FAN AUTO iAUTO X AUTO iAUTO X QUIET FAN SPEED QUIET nanoeTM X nanoeTM G nanoeTM TECHNOLOGY nanoeTM TECHNOLOGY OFF 34...

Page 35: ...LAN 0 5 1 2 3 4 5 6 7 8 9 OFF 0 0h iAUTO X 2 C 4 F AUTO 4 iAUTO X iAUTO X 23 C 60 iAUTO X iAUTO X iAUTO X 2 C 4 F 4 Burmese 35...

Page 36: ...2 3 1 2 1 TIMER ON TIMER OFF 22 00 OFF 2 3 36...

Page 37: ...iAUTO X COOL DRY COOL 26 0 C 28 0 C 79 F 82 F COOL DRY iAUTO X COOL DRY iAUTO X TIMER nanoe X nanoeTM X nanoeTM X COOL DRY 2 5 nanoeTM TECHNOLOGY 2 Burmese 37...

Page 38: ...C F DBT WBT DBT WBT COOL 32 89 6 23 73 4 46 114 8 26 78 8 16 60 8 11 51 8 16 60 8 11 51 8 DBT WBT 38...

Page 39: ...H 99 pH 7 40 C 104 F AUTO OFF ON 2 A B 1 B A AUTO OFF ON 2 1 3 4 AUTO OFF ON nanoeTM G Burmese 39...

Page 40: ...nanoeTM G 2 2 40...

Page 41: ...POWER TIMER ON 15 TIMER ON UV Burmese 41...

Page 42: ...COOL nanoeTM TECHNOLOGY nanoeTM TECHNOLOGY ON nanoeTM G nanoeTM TECHNOLOGY nanoeTM X nanoeTM TECHNOLOGY OFF LAN ON LAN 42...

Page 43: ...AUTO OFF ON 1 2 iAUTO X AUTO OFF ON 3 COOL 1 AUTO OFF ON 4 AUTO OFF ON 5 COOL AUTO OFF ON 15 8 C 14 4 F nanoeTM TECHNOLOGY 2 3 Burmese 43...

Page 44: ...H 00 H 11 H 12 H 14 H 15 H 16 current transformer CT H 17 H 19 H 21 Float Switch H 23 1 H 24 2 H 25 H 26 Negative H 27 H 28 1 H 30 Discharge Pipe H 31 H 32 2 H 33 H 34 H 35 H 36 Gas Pipe H 37 Liquid P...

Page 45: ...52 Limit Switch H 58 H 59 H 64 H 67 nanoe H 70 H 71 H 72 H 85 LAN H 97 H 98 H 99 F 11 4 way F 16 F 17 F 18 Dry Circuit F 87 PCB F 90 Power Factor F 91 F 93 F 94 F 95 Cooling Side F 96 F 97 F 98 F 99 D...

Page 46: ...tion with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flammable refrigerant If t...

Page 47: ...47 Pb...

Page 48: ...Printed in Malaysia Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2021 ACXF55 29860 SZ0221 0...

Reviews: