8.2.2.4. Anti-Dew Formation Control
Anti-Dew control is perform if the following conditions is fulfilled during cooling/dry operation.
a. Control Start Condition
1) Indoor Intake Air Temperature
24°C & above
2) Outdoor Air Temperature
Refer below
3) Remote Control Setting Temperature
16°C & above, below 30°C
4) Fan tab
Refer below
Control start after 1) ~ 4) continued for more than 1 minutes.
b. Control Contents
*
If the outdoor temperature
30°C
Me & above (include auto air flow)
XE9CK
XE12CK
0 min
T
30 min
47
67
30 min
T
90 min
39
52
90 min
T
420 min
39
52
Below Me
XE9CK
XE12CK
0 min
T
30 min
33
44
30 min
T
90 min
26
36
90 min
T
420 min
26
36
*
If the outdoor temperature
30°C
Me & above (include auto air flow)
XE9CK
XE12CK
0 min
T
30 min
47
67
30 min
T
90 min
39
52
90 min
T
420 min
39
52
Below Me
XE9CK
XE12CK
0 min
T
30 min
33
44
30 min
T
90 min
26
36
90 min
T
420 min
26
36
c. Cancellation Condition
•
•
•
•
Perform cancellation within 420 minutes after start and return to initial control.
•
•
•
•
When changing the remote control setting temperature or air flow setting during the Anti-Dew control operation.
•
•
•
•
If the above starting condition is not fulfilled.
34
CS-XE9CKE CU-XE9CKE / CS-XE12CKE CU-XE12CKE
Summary of Contents for CS-XE12CKE
Page 10: ...4 Dimensions 10 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE ...
Page 11: ...11 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE ...
Page 12: ...5 Refrigeration Cycle Diagram 12 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE ...
Page 13: ...6 Block Diagram 13 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE ...
Page 14: ...7 Wiring Diagram 14 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE ...
Page 91: ...13 Technical Data 91 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE ...
Page 92: ...92 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE ...
Page 104: ...104 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE ...
Page 105: ...How to use electronic circuit diagram 105 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE ...
Page 106: ...18 1 REMOTE CONTROL 106 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE ...