Quiet Operation Control
(For Cooling Mode or cooling region of Soft Dry Mode)
•
Purpose of this operation is to provide quite cooling operation compare to normal operation.
•
When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates, the sound level will be automatically decreased
2 dB (Lo), decreased 3 dB (Hi, Me), against the present sound level operation.
•
Quiet setting of fan speed rpm refer to Indoor Fan Speed Control.
•
Dew formation become severe at Quiet Lo cool, therefore Quiet Lo cool is operated only 1h 30 min (1h QLo, 30 min QLo + 50).
After that, it goes back to Lo cool (However Quiet LED remains on).
•
Manual Airflow Direction:-
−
RPM control during Lo cool
−
RPM control during Hi & Me cool
•
Auto Airflow Direction:-
•
Quiet Mode Operation will stop if:-
−
Quiet mode button is pressed again.
−
Stopped by ON/OFF switch.
−
Timer OFF activates.
−
Powerful mode button is pressed.
−
When change mode to Air Circulation mode.
20
CS-W7CKP CU-W7CKP5 / CS-W9CKP CU-W9CKP5 / CS-W12CKP CU-W12CKP5