12.12.2.1 Demo Mode
The air conditioner starts the operation in the Demo mode as described below when 2 minutes have elapsed after the
protection control was started subsequent to the confirmation of communication error.
(At this time, a strong warning sound is emitted for 3 minutes if the test run memory is “incomplete”.)
Condition to stop the mode
The operation is stopped by turning off the air conditioner on the remote control or pressing the EMERGENCY
OPERATON switch during the Demo mode.
(“TIMER” LED flashes.)
Zone B
Airflow Unit Operation Mode (Normal Operation)
Transition time to Demo
Mode
180sec from
the demo starts
360 sec from
the demo starts
540 sec from
the demo starts
640 sec from
the demo starts
[POWER] LED
ON
OFF
[NANOE-G] LED
Follow the remote control settings
OFF
[+8/10°C HEAT] LED
Follow the remote control settings
OFF
[ECONAVI] LED
Follow the remote control settings
OFF
[TIMER] LED
Auto Demo mode is set during the model selection: Follow the remote control settings.
When in Product Demo mode: Always OFF (Timer is cancelled due to H11)
Front panel STM
Open
Stop position
Vertical louver STM
Ceiling airflow
Heating 5
Swing
Stop position
Horizontal louver STM
Area OFF or Auto Demo is set: Swing from the front side
Others: Area control under Heating, Range B, Airflow stable
Reset
Fan motor
Fan speed is set to Auto on the remote control: OFF
Fan speed is set to Manual on the remote control: Remote controller
setting tap
Stop position
Human activity sensor
Area ON: Repeat the scan detection and fixed detection.
Area OFF: Standby position (Default position)
Standby position
(Default position)
Sunlight sensor
LED brightness changes (Bright-Dim) when ECONAVI is ON. Confirmed time is for Demo only.
NANOE output
OFF
12.12.2.2 Infrared Sensor Abnormality
Abnormality detection:
Connector disconnection / Wire cut abnormality
o
Sensor judge Hi level continuously for 25 seconds
Circuit
abnormality
o
65 seconds after power ON, if infrared sensor judge Lo level continuously for 25 seconds
Error Code judgment
When abnormality happened, internal counter increase by 1 time.
Infrared sensor power OFF, retry after 5 seconds.
When the infrared sensor maintains normal condition for 120 seconds, the counter reset or AC reset.
When abnormality counter reached 4 times, H59 occurred – No TIMER indicator blinking.
When error code happened, the unit is able to operate without ECONAVI / AUTO COMFORT.
12.12.2.3 Infrared Sensor Check Mode
1 Conditions to start the mode
The infrared sensor check mode starts when all of the following conditions are met:
o
The infrared sensor error is not being detected.
o
Not in Demo mode.
o
Human activity sensor is not selected.
o
An error of Error Level 20 or higher is not present.
o
The signal for infrared sensor check is received. (Long-press the “AUTO COMFORT” button on the
remote control for 10 seconds)
2 Conditions to end the mode
The infrared sensor check mode ends when any of the following conditions is met:
o
A signal other than the signal for infrared sensor check is received; or the EMERGENCY button is
pressed
→
The signal received is followed.
o
5 minutes have elapsed since the signal for infrared sensor check was received
→
The mode is stopped.
o
The infrared sensor error is confirmed
→
The mode is stopped.
o
An error of Error Level 20 or higher has occurred
→
Follow the processing of each error.
Summary of Contents for CS-VE9NKE
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit and Remote Control...
Page 14: ...14 5 2 Outdoor Unit...
Page 15: ...15 6 Refrigeration Cycle Diagram...
Page 16: ...16 7 Block Diagram...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit...
Page 18: ...18 8 2 Outdoor Unit...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Page 20: ...20 9 2 Outdoor Unit...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Page 22: ...22 10 1 2 Printed Circuit Board...
Page 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board...
Page 27: ...27...
Page 68: ...68 15 4 Self diagnosis Method 15 4 1 H11 Indoor Outdoor Communication Error Troubleshooting...
Page 69: ...69 15 4 2 H14 Indoor Unit Intake Air Temperature Sensor Error Troubleshooting...
Page 71: ...71 15 4 8 H53 Heat Storage Tank Temperature Sensor Error Troubleshooting...
Page 72: ...72 15 4 9 H16 Outdoor Unit CT Disconnection Error Troubleshooting...
Page 73: ...73 15 4 10 H19 Indoor Unit Fan Motor Lock Error Troubleshooting...
Page 75: ...75 15 4 12 H38 Brand not Corresponding Troubleshooting...
Page 76: ...76 15 4 13 H50 Ventilation Fan Motor Error Troubleshooting...
Page 77: ...77 15 4 14 H51 Filter Cleaning Nozzle Lock Error Troubleshooting...
Page 78: ...78 15 4 15 H59 Infrared Sensor Error Troubleshooting...
Page 79: ...79 15 4 16 H67 NANOE Error Troubleshooting...
Page 80: ...80 15 4 17 H70 Sunlight Sensor Error Troubleshooting...
Page 81: ...81 15 4 18 H96 2 and 3 Way Valve Opening Failure Check Troubleshooting...
Page 82: ...82 15 4 19 H97 Outdoor Unit Fan Motor Lock Error Troubleshooting...
Page 83: ...83 15 4 20 H98 Indoor Unit Overpressure Protection Troubleshooting...
Page 85: ...85 15 4 22 F11 Cooling Heating Switching Error Troubleshooting...
Page 86: ...86 15 4 23 F16 Cooling Dry Switching Error Troubleshooting...
Page 87: ...87 15 4 24 F19 Heat Storage Cycle Error Troubleshooting...
Page 88: ...88 15 4 25 F90 PFC Protection Troubleshooting...
Page 89: ...89 15 4 26 F91 Refrigeration Cycle Error Troubleshooting...
Page 90: ...90 15 4 27 F93 Compressor Rotation Error Troubleshooting...
Page 91: ...91 15 4 28 F95 Overpressure Protection in Case of Cooling Error Troubleshooting...
Page 92: ...92 15 4 29 F96 Transistor Module Over temperature Protection Troubleshooting...
Page 93: ...93 15 4 30 F97 Compressor Over temperature Protection Troubleshooting...
Page 94: ...94 15 4 31 F98 Total Current Protection Control Troubleshooting...
Page 95: ...95 15 4 32 F99 DC Peak Operation Error Troubleshooting...
Page 127: ...127 Heating Characteristic Condition Room temperature 20 C DBT Piping length 5m Fh 37Hz...
Page 131: ...131 Heating Characteristic Condition Room temperature 20 C DBT Piping length 5m Fh 49Hz...
Page 134: ...134 18 Exploded View and Replacement Parts List 18 1 Indoor Unit...