background image

Panasonic Appliances Air-Conditioning Malaysia Sdn. Bhd. & Panasonic Appliances Air-Conditioning R & D Malaysia Sdn. Bhd.

1

2

3

4

5

6

7

8

A

B

C

D

E

F

A

B

C

D

E

F

A3

UNIT : mm

NAME

OPERATING INSTRUCTIONS ( 5 / 11 )

CODE NO.

ACXF55-18700

6

 Safety precautions

WARNING

This appliance is 

¿

 lled with R32 

(mild 

À

 ammable refrigerant). 

If the refrigerant is leaked and exposed to 
an external ignition source, there is a risk 
of 

¿

 re.

Indoor unit and outdoor unit

The appliance shall be installed, and/or 
operated in a room with 

À

 oor area larger 

than Amin (m²) and keep away from ignition 
sources, such as heat/sparks/open 

À

 ame or 

hazardous areas such as gas appliances, gas 
cooking, reticulated gas supply systems or 
electric cooking appliances, etc.(Refer to Table 
A of Installation instructions table for Amin (m²))
Be aware that refrigerant may not contain an 
odour, highly recommended to ensure suitable 

À

 ammable refrigerant gas detectors are 

present, operating and able to warn of a leak.
Keep any required ventilation openings clear of 
obstruction.
Do not pierce or burn as the appliance is 
pressurized. Do not expose the appliance to 
heat, 

À

 ame, sparks, or other sources of ignition. 

Else it may explode and cause injury or death.

Precaution for using R32 refrigerant

The basic installation work procedures are the same as 
conventional refrigerant (R410A, R22) models.

Since the working pressure is higher than that 
of refrigerant R22 models, some of the piping 
and installation and service tools are special. 
Especially, when replacing a refrigerant R22 
model with a new refrigerant R32 model, 
always replace the conventional piping and 

À

 are nuts with the R32 and R410A piping and 

À

 are nuts on the outdoor unit side. 

For R32 and R410A, the same 

À

 are nut on the 

outdoor unit side and pipe can be used.
The mixing of different refrigerants within 
a system is prohibited. Models that use 
refrigerant R32 and R410A have a different 
charging port thread diameter to prevent 
erroneous charging with refrigerant R22 and 
for safety. 
Therefore, check beforehand. [The charging port 
thread diameter for R32 and R410A is 1/2 inch.]

 

Must always ensure that foreign matter (oil, 
water, etc.) does not enter the piping. Also, 
when storing the piping, securely seal the 
opening by pinching, taping, etc. (Handling of 
R32 is similar to R410A.)
• Operation, maintenance, repairing and 

refrigerant recovery should be carried 
out by trained and certi

¿

 ed personnel in 

the use of 

À

 ammable refrigerants and as 

recommended by the manufacturer. Any 
personnel conducting an operation, servicing 
or maintenance on a system or associated 
parts of the equipment should be trained and 
certi

¿

 ed.

• Any part of refrigerating circuit (evaporators, 

air coolers, AHU, condensers or liquid 
receivers) or piping should not be located in 
the proximity of heat sources, open 

À

 ames, 

operating gas appliance or an operating 
electric heater.

• The user/owner or their authorised 

representative shall regularly check the 
alarms, mechanical ventilation and detectors, 
at least once a year, where as required by 
national regulations, to ensure their correct 
functioning.

• A logbook shall be maintained. The results 

of these checks shall be recorded in the 
logbook.

• In case of ventilations in occupied spaces 

shall be checked to con

¿

 rm no obstruction.

• Before a new refrigerating system is put 

into service, the person responsible for 
placing the system in operation should 
ensure that trained and certi

¿

 ed operating 

personnel are instructed on the basis of the 
instruction manual about the construction, 
supervision, operation and maintenance of 
the refrigerating system, as well as the safety 
measures to be observed, and the properties 
and handling of the refrigerant used.

• The general requirement of trained and 

certi

¿

 ed personnel are indicated as below:

a) Knowledge of legislation, regulations 

and standards relating to 

À

 ammable 

refrigerants; and,

b) Detailed knowledge of and skills in 

handling 

À

 ammable refrigerants, personal 

protective equipment, refrigerant leakage 
prevention, handling of cylinders, charging, 
leak detection, recovery and disposal; and,

c) Able to understand and to apply in practice 

the requirements in the national legislation, 
regulations and Standards; and,

d) Continuously undergo regular and further 

training to maintain this expertise.

 

7

English

S

afety precautions

1. Installation (Space)

• Product with 

À

 ammable refrigerants, shall not 

be installed in an unventilated space, if that 
space is smaller than Amin (m²).

• In case of 

¿

 eld charge, the effect on 

refrigerant charge caused by the different pipe 
length has to be quanti

¿

 ed, measured and 

labelled.

• Must ensure the installation of pipe-work shall 

be kept to a minimum. Avoid use dented pipe 
and do not allow acute bending.

• Must ensure that pipe-work shall be protected 

from physical damage.

• Must comply with national gas regulations, 

state municipal rules and legislation. Notify 
relevant authorities in accordance with all 
applicable regulations.

• Must ensure mechanical connections be 

accessible for maintenance purposes.

• In cases that require mechanical ventilation, 

ventilation openings shall be kept clear of 
obstruction.

• When disposal of the product, do follow to the 

precautions in #12 and comply with national 
regulations.
Always contact to local municipal of

¿

 ces for 

proper handling.

2. Servicing
2-1. Service personnel

• The system is inspected, regularly supervised 

and maintained by a trained and certi

¿

 ed 

service personnel who is employed by the 
person user or party responsible.

• Ensure the actual refrigerant charge size is in 

accordance with the room size within which 
the refrigerant containing parts are installed.

• Ensure refrigerant charge not to leak.
• Any quali

¿

 ed person who is involved with 

working on or breaking into a refrigerant 
circuit should hold a current valid certi

¿

 cate 

from an industry-accredited assessment 
authority, which authorizes their competence 
to handle refrigerants safely in accordance 
with an industry recognised assessment 
speci

¿

 cation.

• Servicing shall only be performed 

as recommended by the equipment 
manufacturer. Maintenance and repair 
requiring the assistance of other skilled 
personnel shall be carried out under the 
supervision of the person competent in the 
use of 

À

 ammable refrigerants.

• Servicing shall be performed only as 

recommended by the manufacturer.

 

2-2. Work

• Prior to beginning work on systems containing 

À

 ammable refrigerants, safety checks are 

necessary to ensure that the risk of ignition 

is minimised. For repair to the refrigerating 

system, the precautions in #2-2 to #2-8 must be 

followed before conducting work on the system.

• Work shall be undertaken under a controlled 

procedure so as to minimize the risk of a 

À

 ammable gas or vapour being present while 

the work is being performed.

• All maintenance staff and others working in the 

local area shall be instructed and supervised 

on the nature of work being carried out.

• Avoid working in con

¿

 ned spaces. Always 

ensure away from source, at least 2 meter of 

safety distance, or zoning of free space area 

of at least 2 meter in radius.

• Wear appropriate protective equipment, including 

respiratory protection, as conditions warrant.

• Ensure that the conditions within the area 

have been made safe by limit of use of any 

À

 ammable material. Keep all sources of 

ignition and hot metal surfaces away.

2-3. Checking for presence of refrigerant

• The area shall be checked with an 

appropriate refrigerant detector prior to and 

during work, to ensure the technician is aware 

of potentially 

À

 ammable atmospheres.

• Ensure that the leak detection equipment 

being used is suitable for use with 

À

 ammable 

refrigerants, i.e. non sparking, adequately 

sealed or intrinsically safe.

• In case of leakage/spillage happened, 

immediately ventilate area and stay upwind 

and away from spill/release.

• In case of leakage/spillage happened, do 

notify persons down wind of the leaking/

spill, isolate immediate hazard area and keep 

unauthorized personnel out.

2-4. Presence of 

¿

 re extinguisher

• If any hot work is to be conducted on the 

refrigeration equipment or any associated 

parts, appropriate 

¿

 re extinguishing 

equipment shall be available at hand.

• Have a dry powder or CO² 

¿

 re extinguisher 

adjacent to the charging area.

Summary of Contents for CS-U12UKY

Page 1: ...ist refer to technical manual DSA R009 This part should practice first in first out FIFO management SAFETY PART C EN Sym Date Revision Signed Checked AA NOV 22 17 New release Scale Written Checked Checked Approved Authorized NAME OPERATING INSTRUCTIONS 1 11 CODE NO ChiewSF Baizura WeeFL J Terauchi NOV 22 17 NOV 22 17 NOV 22 17 NOV 22 17 ACXF55 18700 Finish Staple Binding 210 148 Front Page Brand N...

Page 2: ...ct Please see the Panasonic website for further information on collection centers etc http www panasonic com in corporate sustainability panasonic india i recycle program html WARNING This symbol shows that this equipment uses a Àammable refrigerant If the refrigerant is leaked together with an external ignition source there is a possibility of ignition This symbol shows that the Operation Instruc...

Page 3: ...sor Area Search Activity Detection Absence Detection AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON FAN SPEED MODE SLEEP QUIET AIR SWING TEMP OFF ON AIR CONDITIONER ON OFF TIMER CANCEL FAN SPEED SLEEP QUIET AIR SWING A B 3 English Table of contents Safety precautions 4 11 How to use 12 13 To learn more 14 15 Cleaning instructions 16 Troubleshooting 17 19 Information Back Cover B Basic operation 1 ...

Page 4: ...r Ż Complete wire without joining Ż Ż Approved connecting means for example approved socket and plug Complete wire without joining Power Supply OR Indoor Unit Outdoor Unit If the supply cord is damaged it must be replaced by the manufacturer service agent or similarly quali ed persons in order to avoid a hazard It is strongly recommended to be installed with Earth Leakage Circuit Breaker ELCB or R...

Page 5: ...n handling of cylinders charging leak detection recovery and disposal and c Able to understand and to apply in practice the requirements in the national legislation regulations and Standards and d Continuously undergo regular and further training to maintain this expertise 7 English Safety precautions 1 Installation Space Product with Àammable refrigerants shall not be installed in an unventilated...

Page 6: ...damage to cables excessive number of connections terminals not made to original speci cation damage to seals incorrect tting of glands etc Ensure that apparatus is mounted securely Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of Àammable atmospheres Replacement parts shall be in accordance with the manufacturer s spec...

Page 7: ...the system when charging is complete if not already Extreme care shall be taken not to over ll the refrigeration system Prior to recharging the system it shall be pressure tested with OFN refer to 7 The system shall be leak tested on completion of charging but prior to commissioning A follow up leak test shall be carried out prior to leaving the site Electrostatic charge may accumulate and create ...

Page 8: ... or OFF timer Example OFF at 22 00 Each time pressed OFF Cancel 2 Set the time 3 Con rm SET To cancel ON or OFF timer press ON or OFF to select respective or then press CANCEL If timer is cancelled manually or due to power failure you can restore the timer again by pressing ON or OFF to select respective or then press SET The nearest timer setting will be displayed and will activate in sequence Ti...

Page 9: ...G deactivates viruses bacteria on the lter for 2 hours with fan stopped and Àap closed Do not turn off the power supply during this operation After power failure this operation will not resume Operating conditions Use this air conditioner in the temperature range indicated in the table Temperature C F Indoor Outdoor DBT WBT DBT WBT COOL Max 32 89 6 23 73 4 46 114 8 26 78 8 Min 16 60 8 11 51 8 16 6...

Page 10: ... is set the unit may start earlier up to 15 minutes before the actual set time in order to achieve the desired temperature on time TIMER indicator is always on The timer setting repeats daily once set Operation is delayed a few minutes after restarting The delay is a protection to the unit s compressor Indoor fan stops occasionally during automatic fan speed setting This helps to remove the surrou...

Page 11: ...ity H 26 Minus ION abnormality H 27 Outdoor air temperature sensor abnormality H 28 Outdoor heat exchanger temperature sensor 1 abnormality H 30 Outdoor discharge pipe temperature sensor abnormality H 31 Abnormal swimming pool sensor H 32 Outdoor heat exchanger temperature sensor 2 abnormality H 33 Indoor outdoor misconnection abnormality H 34 Outdoor heat sink temperature sensor abnormality H 35 ...

Reviews: