background image

1. Safety Precautions 

 

Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. 

 

Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and 
main circuit for the model installed. 

 

The caution items stated here must be followed because these important contents are related to safety. The meaning of each 
indication used is as below. Incorrect installation or servicing due to ignoring of the instruction will cause harm or damage, 
and the seriousness is classified by the following indications. 

 

  

WARNING

 

This indication shows the possibility of causing death or serious injury. 

  

CAUTION

 

This indication shows the possibility of causing injury or damage to properties. 

 

 

The items to be followed are classified by the symbols: 

 

 

This symbol denotes item that is PROHIBITED from doing. 

 

 

Carry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation, care and 
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference. 

 

  

WARNING

 

1. 

Do not modify the machine, part, material during repairing service. 

2. 

If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit. 

3. 

Do not wrench the fasten terminal. Pull it out or insert it straightly. 

4. 

Engage authorized dealer or specialist for installation and servicing. If installation of servicing done by the user is defective, it will cause 
water leakage, electrical shock or fire. 

5. 

Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire. 

6. 

Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage, 
fire or electrical shock. 

7. 

Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly 
done, the set will drop and cause injury. 

8. 

For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single 
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire. 

9. 

This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD).      
Otherwise, it may cause electrical shock and fire in case equipment breakdown or insulation breakdown.

 

10. 

Do not use joint cable for indoor/outdoor connection cable. Use the specified indoor/outdoor connection cable, refer to installation 
instruction CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor/outdoor connection. Clamp the cable so that no 
external force will be acted on the terminal. If connecting or fixing is not perfect, it will cause heat up or fire at the connection. 

11. 

Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will 
cause heat-up or fire at the connection point of terminal, fire or electrical shock. 

12. 

When install or relocate air conditioner, do not let any substance other than the specified refrigerant, eg. air etc. mix into refrigeration cycle 
(piping). (Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.). 

13. 

Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit at veranda of high rise building, child may climb up 
to outdoor unit and cross over the handrail and causing accident. 

14. 

This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and 
telephone. Otherwise, it may cause electrical shock in case equipment breakdown or insulation breakdown. 

 

15.  Keep away from small children, the thin film may cling to nose and mouth and prevent breathing. 

 

16. 

Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with 
other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire. 

 

17. 

Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may 
break and cause refrigerant gas leakage. 

18. 

For R410A models, when connecting the piping, do not use any existing (R22) pipes and flares nuts. Using such same may cause 
abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. In case of using existing 
(R22) pipes during installation of R410A models, must carry out pump down properly to collect back the refrigerant and oil before 
installation new unit. 
Thickness of copper pipes used with R410A must be more than 0.6mm. Never use copper pipes thinner than 0.6mm. 
It is desirable that the amount of residual oil is less than 40 mg/10m.

 

 

 

Summary of Contents for CS-S9NKUW-1

Page 1: ...bite be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit WARNING This service information is designed for experienced repair technicians only and is not de...

Page 2: ...f Dry Mode 49 11 7 Powerful Mode Operation 50 11 8 Timer Control 50 11 9 Random Auto Restart Control 50 11 10 Indication Panel 51 12 Protection Control 52 12 1 Restart Control Time Delay Safety Contro...

Page 3: ...alled with Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire in case equipment breakdown or insulation breakdown 10 Do not use joint ca...

Page 4: ...cause refrigerant gas leakage 4 Do not touch outdoor unit air inlet and aluminium fin It may cause injury 5 Select an installation location which is easy for maintenance 6 Pb free solder has a higher...

Page 5: ...rent A Max Input Power W 4 1 900 5 4 1 22k Starting Current A 3 7 5 1 Min Circuit Ampacity 15 0 15 0 Max Overcurrent Protection 15 0 15 0 Type Hermetic Motor Rotary Hermetic Motor Rotary Motor Type Br...

Page 6: ...16 7 5 8 16 7 5 8 Drain Hose Length mm inch 650 25 5 8 650 25 5 8 Fin Material Aluminium Pre Coat Aluminium Pre Coat Fin Type Slit Fin Slit Fin Row x Stage x FPI 2 x 15 x 19 2 x 15 x 21 Indoor Heat E...

Page 7: ...Input Power W 9 0 1 99k 10 8 2 48k Starting Current A 8 3 11 2 Min Circuit Ampacity 15 0 20 0 Max Overcurrent Protection 20 0 25 0 Type Hermetic Motor Scroll Hermetic Motor Scroll Motor Type Brushless...

Page 8: ...nch 16 7 5 8 16 7 5 8 Drain Hose Length mm inch 650 25 5 8 650 25 5 8 Fin Material Aluminium Pre Coat Aluminium Pre Coat Fin Type Slit Fin Slit Fin Row x Stage x FPI 2 x 15 x 21 2 x 15 x 21 Indoor Hea...

Page 9: ...9 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...

Page 10: ...10 4 Dimensions 4 1 Indoor Unit 4 1 1 CS S9NKUW 1 CS S12NKUW 1...

Page 11: ...11 4 1 2 CS S18NKU 1 CS S22NKU 1...

Page 12: ...12 4 2 Outdoor Unit 4 2 1 CU S9NKU 1 CU S12NKU 1 4 2 2 CU S18NKU 1 CU S22NKU 1...

Page 13: ...13 5 Refrigeration Cycle Diagram 5 1 CS S9NKUW 1 CU S9NKU 1 CS S12NKUW 1 CU S12NKU 1...

Page 14: ...14 5 2 CS S18NKU 1 CU S18NKU 1 CS S22NKU 1 CU S22NKU 1...

Page 15: ...15 6 Block Diagram 6 1 CS S9NKUW 1 CU S9NKU 1 CS S12NKUW 1 CU S12NKU 1...

Page 16: ...16 6 2 CS S18NKU 1 CU S18NKU 1 CS S22NKU 1 CU S22NKU 1...

Page 17: ...17 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS S9NKUW 1 CS S12NKUW 1...

Page 18: ...18 7 1 2 CS S18NKU 1 CS S22NKU 1...

Page 19: ...19 7 2 Outdoor Unit 7 2 1 CU S9NKU 1 CU S12NKU 1...

Page 20: ...20 7 2 2 CU S18NKU 1...

Page 21: ...21 7 2 3 CU S22NKU 1...

Page 22: ...22 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS S9NKUW 1 CS S12NKUW 1...

Page 23: ...23 8 1 2 CS S18NKU 1 CS S22NKU 1...

Page 24: ...24 8 2 Outdoor Unit 8 2 1 CU S9NKU 1 CU S12NKU 1...

Page 25: ...25 8 2 2 CU S18NKU 1...

Page 26: ...26 8 2 3 CU S22NKU 1...

Page 27: ...27 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board...

Page 28: ...28 9 1 2 Power Printed Circuit Board 9 1 3 Indicator Printed Circuit Board...

Page 29: ...29 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9NKU 1 CU S12NKU 1...

Page 30: ...30 9 2 1 2 CU S18NKU 1 CU S22NKU 1...

Reviews: