33
13.1.6 Low pressure Prevention control (Gas Leakage Detection)
1. When the conditions listed in the table occur, the compressor stops and restarts after three minutes.
2. If this continuously occurs for twice within 20 minutes, all indoor and outdoor relays will be cut off.
3. This control is not applicable for deice operation.
13.1.7 Low Operation Frequency Protection Control
If one of the following conditions exists, the compressor will run with the frequency of 40 Hz
13.1.8 Compressor Tank Temperature Rise Protection Control
a. Control start conditions
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
• During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4
к
.
Indoor temperature and outdoor temperature is 30±5
к
.
Remote Control setting 16
к
and Hi Fan Speed.
• During Heating operations:
Indoor piping temperature - indoor suction is under 5
к
.
Indoor temperature and outdoor temperature is 20 ± 2
к
.
Remote control setting 30
к
and Hi Fan Speed.
b. Control contents
• Compressor stops (and restart after 3 minutes)
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated
13.2 Protection Control For Cooling and Soft Dry Operation
13.2.1 Outdoor Air Temperature Control
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
• This control will begin 1 minute after the compressor starts.
• Compressor frequency will adjust base on outdoor air temperature.
RE9HKE
RE12HK
Model
Summary of Contents for CS-RE9HKE
Page 11: ...11 5 Dimensions 5 1 Indoor Unit...
Page 12: ...12 5 2 Outdoor Unit Unit mm...
Page 13: ...13 6 Refrigeration Cycle Diagram...
Page 14: ...14 7 Block Diagram...
Page 16: ...16 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board TOP VIEW...
Page 17: ...17 BOTTOM VIEW...
Page 18: ...18 9 1 2 Indicator TOP VIEW BOTTOM VIEW...
Page 21: ...21 10 2 3 Indoor Unit Installation...
Page 38: ...38 14 2 3 Error Codes Table...
Page 40: ...40...
Page 41: ...41...
Page 42: ...42 16 Exploded View and Replacement Pars List 16 1 Indoor Unit 35 36 38 37...
Page 44: ...44 16 2 Outdoor Unit...