![Panasonic CS-RE12NKX Service Manual Download Page 39](http://html.mh-extra.com/html/panasonic/cs-re12nkx/cs-re12nkx_service-manual_1507991039.webp)
39
Indoor piping temperature - indoor suction is under 5
℃
.
Indoor temperature and outdoor temperature is 20 ± 2
℃
.
Remote control setting 30
℃
and Hi Fan Speed.
b. Control contents
• Compressor stops (and restart after 3 minutes)
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated
13.2 Protection Control For Cooling and Soft Dry Operation
13.2.1 Outdoor Air Temperature Control
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
• This control will begin 1 minute after the compressor starts.
• Compressor frequency will adjust base on outdoor air temperature.
RE9NKX RE12NKX RE15NKX
13.2.2 Freeze Prevention Control
1 .Frequency of the compressor
For prevention of freezing of the indoor evaporator, the frequency of the compressor will be changed according to
the indoor piping temperature.
2 .Indoor Fan Control
Indoor fan speed changes according to the indoor piping temperature.
13.2.3 Dew Prevention Control
• To prevent dew formation at indoor unit discharge area.
• This control starts if all conditions continue for 20 minutes:
- Operated with Cooling or Soft Dry Mode.
- Outdoor air temperature is less than 34
℃
.
• This control stopped if anyone of the following conditions is achieved:
- Outdoor air temperature is over 34
℃
.
- Intake air temperature is less than 24
℃
.
- Operation without Cooling or Soft Dry Mode.
Outdoor air temp.(
℃
)
Outdoor air temp.(
℃
)
Outdoor air temp.(
℃
)
Summary of Contents for CS-RE12NKX
Page 11: ...11 5 Dimensions 5 1 Indoor Unit Unit mm ...
Page 12: ...12 5 2 Outdoor Unit CU RE9NKX Unit mm CU RE12NKX CU RE15NKX ...
Page 13: ...13 6 Refrigeration Cycle Diagram CS CU RE9NKX CS CU RE12NKX CU CU RE15NKX COOLING HEATING ...
Page 14: ...14 7 Block Diagram CS CU RE9NKX CS CU RE12NKX ...
Page 15: ...15 CS CU RE15NKX ...
Page 16: ...16 8 Wiring Diagram CS CU RE9NKX ...
Page 17: ...17 CS CU RE12NKX ...
Page 18: ...18 CS CU RE15NKX ...
Page 20: ...20 9 1 2 Indicator receiver TOP VIEW BOTTOM VIEW ...
Page 21: ...21 9 2 Outdoor Unit 9 2 1 CU RE9NKX TOP VIEW BOTTOM VIEW ...
Page 22: ...22 CU RE12NKX TOP VIEW BUTTOM VIEW ...
Page 23: ...23 CU RE15NKX TOP VIEW BUTTOM VIEW ...
Page 26: ...26 10 2 3 Indoor Unit Installation ...
Page 50: ...50 16 2 Outdoor Unit CU RE9NKX ...
Page 52: ...52 CU RE12NKX CU RE15NKX ...