5. Charging hose
•
•
•
•
The pressure resistance of the charging hose has been
raised to match the higher pressure of R410A. The hose
material has also been changed to suit HFC use, and
the size of the fitting has been changed to match the
manifold ports.
6. Vacuum pump adaptor
•
•
•
•
When using a vacuum pump for R410A, it is necessary
to install an electromagnetic valve to prevent the
vacuum pump oil from flowing back into the charging
hose. The vacuum pump adaptor is installed for that
purpose. If the vacuum pump oil (mineral oil) becomes
mixed with R410A, it will damage the unit.
7. Electric gas leak detector for HFC refrigerant
•
•
•
•
The leak detector and halide torch that were used with
CFC and HCFC cannot be used with R410A (because
there is no chlorine in the refrigerant).
•
•
•
•
The present R134a leak detector can be used, but the
detection sensitivity will be lower (setting the sensitivity
for R134a at 1, the level for R410A will drop to 0.6).
•
•
•
•
For detecting small amounts of gas leakage, use the
electric gas leak detector for HFC refrigerant. (Detection
sensitivity with R410A is about 23 g/year).
Fig. 4 Manifold gauge charging hose
Fig. 5 Vacuum pump adaptor
Fig. 6 Electric gas leak detector for HFC refrigerant
Table 8 Difference between R410A and conventional charging hoses
Conventional hoses
R410A hoses
Pressure
resistance
Working pressure
3.4 MPa (35 kgf/cm
3
)
5.1 MPa (52 kgf/cm
3
)
Bursting pressure
17.2 MPa (175 kgf/cm
3
)
27.4 MPa (280 kgf/cm
3
)
Material
NBR rubber
HNBR rubber Nylon coating inside
44
CS-PW18CKE CU-PW18CKE
Summary of Contents for CS-PW18CKE
Page 8: ...4 Dimensions 8 CS PW18CKE CU PW18CKE ...
Page 9: ...9 CS PW18CKE CU PW18CKE ...
Page 10: ...5 Refrigeration Cycle Diagram 10 CS PW18CKE CU PW18CKE ...
Page 11: ...6 Block Diagram 11 CS PW18CKE CU PW18CKE ...
Page 12: ...7 Wiring Diagram CS PW18CKE CU PW18CKE 12 ...
Page 15: ...Cooling Operation Time Diagram 15 CS PW18CKE CU PW18CKE ...
Page 17: ...Soft Dry Operation Time Diagram 17 CS PW18CKE CU PW18CKE ...
Page 21: ...a Normal Deicing Time Diagram b Overload Deicing Time Diagram 21 CS PW18CKE CU PW18CKE ...
Page 58: ...14 Technical Data 58 CS PW18CKE CU PW18CKE ...
Page 60: ...60 CS PW18CKE CU PW18CKE ...
Page 68: ...SCHEMATIC DIAGRAM 4 4 68 CS PW18CKE CU PW18CKE ...
Page 70: ...19 1 REMOTE CONTROL 70 CS PW18CKE CU PW18CKE ...
Page 71: ...19 2 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD TOP VIEW 71 CS PW18CKE CU PW18CKE ...
Page 72: ...19 3 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD BOTTOM VIEW 72 CS PW18CKE CU PW18CKE ...