Time Delay Safety Control
Anti-Freezing Control
Compressor Reverse Rotation Protection Control
Anti-Dew Formation Control
Automatic Fan Speed Mode
8.3. Soft Dry Mode Operation
•
•
•
•
The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
•
•
•
•
During Soft Dry operation, the Indoor Fan will operate at Lo- speed.
•
•
•
•
Once room temperature reaches below Soft Dry OFF temperature. Indoor Fan, Compressor and Outdoor Fan stop for 6
minutes.
•
•
•
•
Once the compressor stops, it will not start for 3 minutes during Cooling operation.
•
•
•
•
Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor
stops.)
•
•
•
•
Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting
is valid during compressor stops.)
•
•
•
•
Same as Anti-Dew Formation Control for Cooling Mode operation.
When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.
•
•
•
•
Fan speed off and on at Lo- speed.
•
•
•
•
Deodorizing Control.
16
CS-PW18CKE CU-PW18CKE
Summary of Contents for CS-PW18CKE
Page 8: ...4 Dimensions 8 CS PW18CKE CU PW18CKE ...
Page 9: ...9 CS PW18CKE CU PW18CKE ...
Page 10: ...5 Refrigeration Cycle Diagram 10 CS PW18CKE CU PW18CKE ...
Page 11: ...6 Block Diagram 11 CS PW18CKE CU PW18CKE ...
Page 12: ...7 Wiring Diagram CS PW18CKE CU PW18CKE 12 ...
Page 15: ...Cooling Operation Time Diagram 15 CS PW18CKE CU PW18CKE ...
Page 17: ...Soft Dry Operation Time Diagram 17 CS PW18CKE CU PW18CKE ...
Page 21: ...a Normal Deicing Time Diagram b Overload Deicing Time Diagram 21 CS PW18CKE CU PW18CKE ...
Page 58: ...14 Technical Data 58 CS PW18CKE CU PW18CKE ...
Page 60: ...60 CS PW18CKE CU PW18CKE ...
Page 68: ...SCHEMATIC DIAGRAM 4 4 68 CS PW18CKE CU PW18CKE ...
Page 70: ...19 1 REMOTE CONTROL 70 CS PW18CKE CU PW18CKE ...
Page 71: ...19 2 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD TOP VIEW 71 CS PW18CKE CU PW18CKE ...
Page 72: ...19 3 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD BOTTOM VIEW 72 CS PW18CKE CU PW18CKE ...