47
12.5 Outdoor Fan Speed Control
Outdoor fan speed can be changes to Hi or Lo according to outdoor temperature. (For PC24TKF)
There is only one speed for outdoor fan motor. (For PC12/18TKF)
When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.
12.6 Vertical Airflow Direction Control
12.6.1 Auto
Control
When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as
shown in the diagram.
When stops operation using the remote control, the discharge vent is reset and stops at the closing position.
During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that
condition, the louver will stop swinging.
(For PC12TKF)
Inner Vane
Stopper
Closed
Position
Reference Point
Upper Limit for
Cooling Mode
(10°)
Cooling/Dry Mode (Airflow
direction auto or manual)
Lower Limit (45°)
0°
110.01°
45°
10°
Outer Vane
Stopper
Closed
Position
Reference Point
Upper Limit for
Cooling Mode
(20°)
Cooling/Dry Mode (Airflow
direction auto or manual)
Lower Limit (56°)
0°
43.85°
134.59°
20°
56°