12.2 Soft Dry Operation
Soft Dry operation can be set using remote control.
Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
This operation starts when the intake air temperature sensor reaches -1.5°C from the setting temperature on the
remote control.
When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operation will be
turned “OFF” for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the
setting temperature as shown in figure below.
However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restart control), the
indoor unit will start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON”
point.
Compressor
ON
Cooling ON point
1.5ºC
Cooling OFF,
Soft Dry ON point
Soft Dry OFF point
1.0ºC
Soft Dry ON point
Cooling
Dry
Dry OFF
Intake air
temperature
Compressor
OFF
12.2.1 Soft Dry Operation Time Diagram (For PC12TKF)
Intake
Temp
ON
Dry OFF, ON
Basic Time
1’
1’
1’
4’
Compressor
Indoor Fan
Outdoor Fan
Operation LED
OFF
Set Temp
Cooling
Cooling
1.0°C
1.5°C
<Description of operation>
Pipe
Temp
10ºC
2ºC
10’
6’
6’
6’
min 6’
a
b
c
d
e
f
g
h
i
j
k
l
m
n
o
p
q
r
s
t
u
v
w
x
y
z
Operation
Stop
: Minimum 60 seconds force operation.
: Minimum 3 minutes restart control (Time Delay Safety Control) -
: Minimum 6 minutes restart control (Time Delay Safety Control) -
: 10 minutes dry operation.
Cooling operation.
Soft Dry operation.
: Freeze Prevention control.
a - c
c - e
t - x
e - g, i - k, m - o, v - x
g - h, l - m, o - p