52
15.3.
Error Codes Table
Abnormality /
Protection control
Abnormality
Judgement
Protection
operation
Problem
Check location
Diagnosis
display
H00
No memory of failure
—
Normal operation
—
—
H11
Indoor/outdoor
abnormal
communication
After operation for
1 minute
Indoor fan only
operation can
start by entering
into force cooling
operation
Indoor/outdoor
communication not establish
• Indoor/outdoor wire terminal
• Indoor/outdoor PCB
• Indoor/outdoor connection wire
H14
Indoor intake air
temperature sensor
abnormality
Continuous for 5s
—
Indoor intake air temperature
sensor open or short circuit
• Indoor intake air temperature
sensor lead wire and connector
H15
Compressor
temperature sensor
abnormality
Continuous for 5s
—
Compressor temperature
sensor open or short circuit
• Compressor temperature sensor
lead wire and connector
H16
Outdoor current
transformer (CT)
abnormality
—
—
Current transformer faulty or
compressor faulty
• Outdoor PCB faulty or
compressor faulty
H19
Indoor fan motor
merchanism lock
Continuous
happen for 7 times
—
Indoor fan motor lock or
feedback abnormal
• Fan motor lead wire and
connector
• Fan motor lock or block
H23
Indoor heat exchanger
temperature sensor 1
abnormality
Continuous for 5s
—
Indoor heat exchanger
temperature sensor 1 open
or short circuit
• Indoor heat exchanger
temperature sensor 1 lead wire
and connector
H24
Indoor heat exchanger
temperature sensor 2
abnormality
Continuous for 5s
—
Indoor heat exchanger
temperature sensor 2 open
or short circuit
• Indoor heat exchanger
temperature sensor 2 lead wire
and connector
H25
Indoor E-Ion
abnormality
Port is ON for 10s
during E-Ion off
—
—
• E-Ion PCB
H27
Outdoor air temperature
sensor abnormality
Continuous for 5s
—
Outdoor air temperature
sensor open or short circuit
• Outdoor air temperature sensor
lead wire and connector
H28
Outdoor heat exchanger
temperature sensor 1
abnormality
Continuous for 5s
—
Outdoor heat exchanger
temperature sensor 1 open
or short circuit
• Outdoor heat exchanger
temperature sensor 1 lead wire
and connector
H30
Outdoor discharge pipe
temperature sensor
abnormality
Continuous for 5s
—
Outdoor discharge pipe
temperature sensor open or
short circuit
• Outdoor discharge pipe
temperature sensor lead wire and
connector
H33
Indoor / outdoor
misconnection
abnormality
—
—
Indoor and outdoor rated
voltage different
• Indoor and outdoor units check
H38
Indoor/Outdoor
mismatch (brand code)
—
—
Brand code not match
• Check indoor unit and outdoor
unit.
H58
Indoor gas sensor
abnormality
Continuous for 6
hours
—
Indoor gas sensor open or
short circuit
• Indoor gas sensor
• Indoor PCB
H97
Outdoor fan motor
mechanism lock
2 times happen
within 30 minutes
—
Outdoor fan motor lock or
feedback abnormal
• Outdoor fan motor lead wire and
connector
• Fan motor lock or block
H98
Indoor high pressure
protection
—
—
Indoor high pressure
protection (Heating)
• Check indoor heat exchanger
• Air filter dirty
• Air circulation short circuit
H99
Indoor operating unit
freeze protection
—
—
Indoor freeze protection
(Cooling)
• Check indoor heat exchanger
• Air filter dirty
• Air circulation short circuit
F11
4-way valve switching
abnormality
4 times happen
within 30 minutes
—
4-way valve switching
abnormal
• 4-way valve
• Lead wire and connector.
F90
Power factor correction
(PFC) circuit protection
4 times happen
within 10 minutes
—
Power factor correction
circuit abnormal
• Outdoor PCB faulty
F91
Refrigeration cycle
abnormality
2 times happen
within 20 minutes
—
Refrigeration cycle abnormal
• Insufficient refrigerant or valve
close
Summary of Contents for CS-NE9LKE
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit...
Page 14: ...14 5 2 Outdoor Unit...
Page 15: ...15 6 Refrigeration Cycle Diagram...
Page 16: ...16 7 Block Diagram...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit...
Page 18: ...18 8 2 Outdoor Unit...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Page 20: ...20 9 2 Outdoor Unit...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Page 22: ...22 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board...
Page 24: ...24 10 2 Outdoor Unit...
Page 80: ...80 16 1 3 To remove discharge grille...
Page 81: ...81 16 1 4 To remove control board 16 1 5 To remove cross flow fan and indoor fan motor...
Page 82: ...82...
Page 84: ...84 17 Technical Data 17 1 Operation Characteristics 17 1 1 CU NE9LKE...
Page 85: ...85...
Page 86: ...86...
Page 87: ...87...
Page 88: ...88 17 1 2 CU NE12LKE...
Page 89: ...89...
Page 90: ...90...
Page 91: ...91...