• Dirtiness level sensitivity adjustment
It is possible to change the gas sensor sensitivity, where the Threshold value (G1 ~ G4) will be shifted accordingly:
1. Press and release “SET” buttton.
2. Press “Timer increment” / “Timer decrement” button to select sensitivity. (Low
Standard
(Default)
High)
3. Confirm setting by pressing “Timer Set” button. LCD returned to original display after 2 seconds.
4. LCD returned to original display if remote control does not operate for 30 seconds.
b. e-ion Control
• When dirtiness level is 1 or 2, e-ion operation starts.
• If dirtiness level improves from level 2 to level 1, the unit carries out level change after 60 seconds.
• When dirtiness level returns to level 0 continuously for 10 minutes or more, e-ion operation stops.
Dirtiness Level Shift
• For Auto Fan Speed, the fan speed increased based on dirtiness level:
c. Indoor Fan Control
• During any operation mode combines with Patrol operation, fan speed follows respective operation mode.
• During Patrol individual operation if e-ion starts, only Auto Fan Speed and no Powerful operation is allowed. Even if “Fan
Speed” button is pressed, no signal is sent to air conditioner, and no change on LCD display.
• During Patrol individual operation if e-ion stops, Indoor Fan stop operation.
d. Airflow direction (Horizontal, Vertical) Control
• During any operation mode combines with Patrol operation, airflow direction follows respective operation mode.
• During Patrol individual operation if e-ion starts, only Auto Air Swing is allowed. Even if “Air Swing” button is pressed, no signal
is sent to air conditioner, and no change on LCD display.
• During Patrol individual operation if e-ion stops, Airflow direction louver closed.
e. Indicator
• When Patrol operation starts, Patrol Sensor indicator ON.
• When e-ion operation starts based on dirtiness level, e-ion indicator ON.
g. Timer Control
• When ON timer activates when unit stops, previous operation resumes and restored last saved patrol operation status.
• When ON timer activates during any operation, no change and carry on current operation.
• When OFF timer activates during any operation, all operation stops and the latest patrol operation status is saved.
f. Remote Control Receiving Sound
• Normal Operation
• Patrol Mode
• Patrol Mode
• Stop
→
→
→
→
Patrol Mode
Stop
Normal Operation
Patrol
:
:
:
:
Beep
Long Beep
Beep
Beep
Summary of Contents for CS-NE9LKE
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit...
Page 14: ...14 5 2 Outdoor Unit...
Page 15: ...15 6 Refrigeration Cycle Diagram...
Page 16: ...16 7 Block Diagram...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit...
Page 18: ...18 8 2 Outdoor Unit...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Page 20: ...20 9 2 Outdoor Unit...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Page 22: ...22 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board...
Page 24: ...24 10 2 Outdoor Unit...
Page 80: ...80 16 1 3 To remove discharge grille...
Page 81: ...81 16 1 4 To remove control board 16 1 5 To remove cross flow fan and indoor fan motor...
Page 82: ...82...
Page 84: ...84 17 Technical Data 17 1 Operation Characteristics 17 1 1 CU NE9LKE...
Page 85: ...85...
Page 86: ...86...
Page 87: ...87...
Page 88: ...88 17 1 2 CU NE12LKE...
Page 89: ...89...
Page 90: ...90...
Page 91: ...91...