Table 12 R22 flaring dimensions
Nominal
diameter
Outside
diameter
(mm)
Wall thickness
(mm)
A(mm)
R410A flaring
tool, clutch type
Conventional flaring tool
Clutch type
Wing-nut type
1/4
6.35
0.8
0 - 0.5
0.5 - 1.0
1.0 - 1.5
3/8
9.52
0.8
0 - 0.5
0.5 - 1.0
1.0 - 1.5
1/2
12.70
0.8
0 - 0.5
0.5 - 1.0
1.5 - 2.0
Table 13 R410A flare and flare nut dimensions Unit:mm
Nominal
diameter
Outside
diameter
(mm)
Wall thickness
(mm)
A +0, -0.4
B
dimension
C
dimension
D
dimension
Flare nut
width
1/4
6.35
0.8
9.1
9.2
6.5
13
17
3/8
9.52
0.8
13.2
13.5
9.7
20
22
1/2
12.70
0.8
16.6
16.0
12.9
23
26
Table 14 R22 flare and flare nut dimensions Unit:mm
Nominal
diameter
Outside
diameter
(mm)
Wall thickness
(mm)
A +0, -0.4
B
dimension
C
dimension
D
dimension
Flare nut
width
1/4
6.35
0.8
9.0
9.2
6.5
13
17
3/8
9.52
0.8
13.0
13.5
9.7
20
22
1/2
12.70
0.8
16.2
16.0
12.9
20
24
2. Procedure and precautions for flare connection
a. Check to make sure there are no scratches, dust, etc., on the flare and union.
b. Align the flared surface with the axial center of the union.
c.
Use a torque wrench, and tighten to the specified torque. The tightening torque for R410A is the same as the conventional
torque value for R22. Be careful, because if the torque is too weak, it may lead to a gas leak. If it is too strong, it may split
the flare nut or make it impossible to remove the flare nut.
Table 15 R410A tightening torque
Nominal
diameter
Outside
diameter (mm)
Tightening torque
N m (kgf cm)
Torque wrench tightening torque
N m (kgf cm)
1/4
6.35
14 - 18 (140 - 180)
18 (180)
3/8
9.52
33 - 42 (330 - 420)
42 (420)
1/2
12.70
55 (550)
55 (550)
10.3.3. Storing and Managing Piping Materials
1. Types of piping and their storage
The following is a general classification of the refrigerant pipe materials used for ACs.
Because the gas pressure of R410A is approximately 1.6 times as high as that of R22, copper pipes with the thickness shown
in Table 10, and with minimal impurities must be used. Care must also be taken during storage to ensure that pipes are not
crushed, deformed, or scratched, and that no dust, moisture or other substance enters the pipe interior. When storing sheathed
copper pipes or plain copper pipes, seal the openings by pinching or taping them securely.
2. Markings and management
a. Sheathed copper pipes and copper-element pipes
When using these pipes, check to make sure that they are the stipulated thickness. For flare nuts, be sure to use the same
nut that is used on the AC unit.
b. Copper pipes
Use only copper pipes with the thickness given in table 10, and with minimal impurities. Because the surface of the pipe is
exposed, you should take special care, and also take measures such as marking the pipes to make sure they are easily
distinguished from other piping materials, to prevent mistaken use.
3. Precautions during refrigerant piping work
Take the following precautions on-site when connecting pipes.(Keep in mind that the need to control the entry of moisture and
dust is even more important than in conventional piping.)
a. Keep the open ends of all pipes sealed until connection with the AC equipment is complete.
47
CS-MVG103KE / CU-MVG153KE
Summary of Contents for CS-MVG103KE
Page 3: ...2 Functions 2 1 REMOTE CONTROL 3 CS MVG103KE CU MVG153KE ...
Page 4: ...2 2 INDOOR UNIT 4 CS MVG103KE CU MVG153KE ...
Page 5: ...5 CS MVG103KE CU MVG153KE ...
Page 6: ...2 3 OUTDOOR UNIT 6 CS MVG103KE CU MVG153KE ...
Page 9: ...4 Dimensions 4 1 CS MVG103KE INDOOR UNIT 9 CS MVG103KE CU MVG153KE ...
Page 10: ...4 2 CU MVG153KE OUTDOOR UNIT 10 CS MVG103KE CU MVG153KE ...
Page 15: ...8 Operation Details FUNCTIONS 8 1 SIMULTANEOUS OPERATION CONTROL 15 CS MVG103KE CU MVG153KE ...
Page 53: ...11 2 3 PIPING LENGTH 53 CS MVG103KE CU MVG153KE ...
Page 54: ...11 3 INDOOR OUTDOOR UNIT INSTALLATION DIAGRAM 54 CS MVG103KE CU MVG153KE ...
Page 69: ...13 Technical Data 13 1 OPERATION CHARACTERISTICS 69 CS MVG103KE CU MVG153KE ...
Page 70: ...70 CS MVG103KE CU MVG153KE ...
Page 78: ...CS MVG103KE Main PCB Back Side Receiver PCB 78 CS MVG103KE CU MVG153KE ...
Page 79: ...15 2 OUTDOOR UNIT MAIN PCB CU MVG153KE Main PCB Front Side CS MVG103KE CU MVG153KE 79 ...
Page 80: ...CU MVG153KE Main PCB Back Side CS MVG103KE CU MVG153KE 80 ...
Page 84: ...16 2 CU MVG153KE 16 2 1 Exploded View 84 CS MVG103KE CU MVG153KE ...