1. Cooling Automatic Fan Speed
The Automatic Fan Speed for cooling operation is shown as below:
a. When Automatic Fan Speed is selected
b. When Automatic Fan Speed and Powerful Mode are selected
Note:
The Fan Speed will change every 10 seconds and it will be repeated from a to h every 80 seconds.
2. Heating Automatic Fan Speed
The Automatic Fan Speed for heating operation is shown below:
·
When Automatic Fan Speed is selected, the Fan speed will change every 10 seconds from Fan Speed No. 10 to No. 22
depending on indoor heat exchanger temperature. Each time the Fan Speed will move 1 rank up or down.
·
When Automatic Fan Speed and Powerful Mode are selected, the Fan Speed will change for every 10 seconds from Fan
Speed No. 11 to No. 27 depend on heat exchanger temperature. Each time the Fan Speed will move 1 rank up or down.
3. Cooling Operation at SHi Speed
During Cooling operation, Indoor Fan speed is set at SHi when the following conditions occur:
·
Outside air temperature is 30°C or above
·
Compressor operates at One Unit operation : 47Hz and above, Two Units operation : 75Hz and above
·
Remote control setting fan speed is High
·
Indoor intake air temperature is 24°C or above
·
Remote control setting temperature is 16°C
·
Within 30 minutes after start of operation.
4. Heating Operation at SSHi Speed
During Heating operation, Indoor Fan speed is set at SSHi when the following conditions occur:
·
Heating operation for 2 hours or more
·
When remote control setting fan speed is High
·
Indoor intake air temperature is 17°C or above and less than 23°C
·
Outdoor air temperature is 4°C or below
·
Remote control setting temperature is 30°C
·
Compressor operates at One Unit operation : 75Hz and above, Two Units operation : 90Hz and above
·
Airflow Direction is set at Manual.
28
CS-MVG103KE / CU-MVG153KE
Summary of Contents for CS-MVG103KE
Page 3: ...2 Functions 2 1 REMOTE CONTROL 3 CS MVG103KE CU MVG153KE ...
Page 4: ...2 2 INDOOR UNIT 4 CS MVG103KE CU MVG153KE ...
Page 5: ...5 CS MVG103KE CU MVG153KE ...
Page 6: ...2 3 OUTDOOR UNIT 6 CS MVG103KE CU MVG153KE ...
Page 9: ...4 Dimensions 4 1 CS MVG103KE INDOOR UNIT 9 CS MVG103KE CU MVG153KE ...
Page 10: ...4 2 CU MVG153KE OUTDOOR UNIT 10 CS MVG103KE CU MVG153KE ...
Page 15: ...8 Operation Details FUNCTIONS 8 1 SIMULTANEOUS OPERATION CONTROL 15 CS MVG103KE CU MVG153KE ...
Page 53: ...11 2 3 PIPING LENGTH 53 CS MVG103KE CU MVG153KE ...
Page 54: ...11 3 INDOOR OUTDOOR UNIT INSTALLATION DIAGRAM 54 CS MVG103KE CU MVG153KE ...
Page 69: ...13 Technical Data 13 1 OPERATION CHARACTERISTICS 69 CS MVG103KE CU MVG153KE ...
Page 70: ...70 CS MVG103KE CU MVG153KE ...
Page 78: ...CS MVG103KE Main PCB Back Side Receiver PCB 78 CS MVG103KE CU MVG153KE ...
Page 79: ...15 2 OUTDOOR UNIT MAIN PCB CU MVG153KE Main PCB Front Side CS MVG103KE CU MVG153KE 79 ...
Page 80: ...CU MVG153KE Main PCB Back Side CS MVG103KE CU MVG153KE 80 ...
Page 84: ...16 2 CU MVG153KE 16 2 1 Exploded View 84 CS MVG103KE CU MVG153KE ...