12.6 Quiet Operation (Heating)
Purpose
o
To provide quiet heating operation compare to normal operation.
Control
condition
o
Quiet operation start condition
When “POWERFUL/QUIET” button at remote control is pressed.
POWERFUL/QUIET LED illuminates.
o
Quiet operation stop condition
When one of the following conditions is satisfied, quiet operation stops:
POWERFUL/QUIET button is pressed again.
Stop by OFF/ON switch.
Timer “off” activates.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except
fan mode only.
During quiet operation, if timer “on” activates, quiet operation maintains.
After off, when on back, quiet operation is not memorised.
Control
contents
o
Fan speed manual
Fan speed is changed from normal setting to quiet setting of respective fan speed.
Fan speed for quiet operation is reduced from setting fan speed.
o
Fan Speed Auto
Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.
12.7 Powerful Mode Operation
When the powerful mode is selected, the internal setting temperature will shift lower up to 2°C (for Cooling/Soft
Dry) or higher up to 3.5°C (for Heating) than remote control setting temperature for 20 minutes to achieve the
setting temperature quickly.
12.8 Timer Control
There are 2 sets of ON and OFF timer available to turn the unit ON or OFF at different preset time.
If more than one timer had been set, the upcoming timer will be displayed and will activate in sequence.
12.8.1 ON
Timer
Control
ON timer 1 and ON timer 2 can be set using remote control, the unit with timer set will start operate earlier than
the setting time.
This is to provide a comfortable environment when reaching the set ON time.
60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to
determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting
time.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
12.8.2 OFF Timer Control
OFF timer 1 and OFF timer 2 can be set using remote control, the unit with timer set will stop operate at set time.
Summary of Contents for CS-E9PB4EA
Page 24: ...24 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Page 25: ...25 5 Dimensions 5 1 Indoor Unit...
Page 26: ...26 5 2 Outdoor Unit 5 2 1 CU E9PB4EA 5 2 2 CU E12PB4EA...
Page 27: ...27 6 Refrigeration Cycle Diagram 6 1 CS E9PB4EA CU E9PB4EA...
Page 28: ...28 6 2 CS E12PB4EA CU E12PB4EA...
Page 29: ...29 7 Block Diagram 7 1 CS E9PB4EA CU E9PB4EA...
Page 30: ...30 7 2 CS E12PB4EA CU E12PB4EA...
Page 31: ...31 8 Wiring Connection Diagram 8 1 Indoor Unit...
Page 34: ...34 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Page 35: ...35 9 2 Outdoor Unit 9 2 1 CU E9PB4EA...
Page 36: ...36 9 2 2 CU E12PB4EA...
Page 37: ...37 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Page 38: ...38 10 1 2 Display Printed Circuit Board...
Page 39: ...39 10 2 Outdoor Unit 10 2 1 CU E9PB4EA...
Page 40: ...40 10 2 2 CU E12PB4EA...
Page 65: ...65 14 3 2 CU E12PB4EA...
Page 106: ...106 18 Exploded View and Replacement Parts List 18 1 Indoor Unit...