19
9.1.
Indoor Unit
9.1.1.
HOW TO FIX INSTALLATION PLATE
The mounting wall is strong and solid enough to prevent it from
the vibration.
The centre of installation plate should be at more than 550 mm
at right and left of the wall.
The distance from installation plate edge to ceiling should more
than 67 mm.
From installation plate left edge to unit’s left side is 47 mm.
From installation plate right edge to unit’s right is 73 mm.
#
: For left side piping, piping connection for liquid should
be about 126 mm from this line.
: For left side piping, piping connection about 174 mm
from this line.
: For left side piping, piping connection about 984 mm
from this line.
1. Mount the installation plate on the wall with 5 screws or
more.
(If mounting the unit on the concrete wall, consider using
anchor bolts.)
• Always mount the installation plate horizontally by
aligning the marking-off line with the thread and using a
level gauge
2. Drill the piping plate hole with ø70 mm hole-core drill.
• Line according to the arrows marked on the lower left
and right side of the installation plate. The meeting point
of the extended line is the centre of the hole. Another
method is by putting measuring tape at position as
shown in the diagram above. The hole centre is obtained
by measuring the distance namely 150 mm and 125 mm
for left and right hole respectively.
• Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
9.1.2.
TO DRILL A HOLE IN THE WALL
AND INSTALL A SLEEVE OF
PIPING
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the
wall.
4. Finish by sealing the sleeve with putty or caulking
compound at the final stage.
9.1.3.
INDOOR UNIT INSTALLATION
1.
For the right rear piping
2.
For the right and right bottom piping
3.
For the embedded piping
Caution
When the wall is hollow, please be sure to use the sleeve
for tube ass’y to prevent dangers caused by mice biting
the connecting cable.
Summary of Contents for CS-E9EKK
Page 9: ...9 4 Dimensions 4 1 Indoor Unit ...
Page 10: ...10 4 2 Outdoor Unit ...
Page 11: ...11 5 Refrigeration Cycle Diagram ...
Page 12: ...12 6 Block Diagram ...
Page 13: ...13 7 Wiring Connection Diagram ...
Page 14: ...14 ...
Page 15: ...15 8 Printed Circuit Board 8 1 Indoor Unit Main Printed Circuit Board ...
Page 16: ...16 8 2 Outdoor Unit Main Printed Circuit Board ...
Page 17: ...17 8 3 Indicator panel ...
Page 20: ...20 This can be used for left rear piping and left bottom piping also ...
Page 37: ...37 14 Technical Data 14 1 Thermostat Characteristics ...
Page 38: ...38 14 2 Operation Characteristics Cooling Characteristic at Different Outdoor Air Temperature ...
Page 39: ...39 ...
Page 40: ...40 ...
Page 41: ...41 ...
Page 42: ...42 ...
Page 43: ...43 ...
Page 44: ...44 ...
Page 45: ...45 ...