46
12.11.7. Setting Position Judgment
• According to installation position when there is only one activity area detected, the horizontal airflow direction louver position is
fixed according to chart below:
• When 2 activity areas have been detected, according to Human Activity Level, the timing of horizontal airflow direction louver
steps at the targeted activity areas is judged.
• When 3 activity areas have been detected, according to Human Activity Level the timing of horizontal airflow louver steps at the
targeted activity areas is judged.
• When 3 activity areas have same activity level, the horizontal airflow direction louver will swing left and right.
12.11.8. Setting Temperature and Fan Speed Shift
• Cooling Dual Sensor
Target area
Horizontal airflow direction louver position
Left installation
Center installation
Right installation
A
2
1
1
B
5
5
4
C
3
3
3
Operation mode
Activity level difference
Louver stop time
Cooling
1 level
Higher Activity level 60 seconds
Lower Activity level 30 seconds
2 levels
Higher Activity level 60 seconds
Lower Activity level 8 seconds
Heating
1 level
Higher Activity level 8 seconds
Lower Activity level 30 seconds
2 levels
Higher Activity level 8 seconds
Lower Activity level 60 seconds
Operation mode
Activity level
Louver stop time
Cooling
Hi
Me
Lo
45 seconds
30 seconds
20 seconds
Heating
Hi
Me
Lo
20 seconds
30 seconds
45 seconds
Summary of Contents for CS-E24MKES
Page 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control ...
Page 11: ...11 5 2 Outdoor Unit ...
Page 12: ...12 6 Refrigeration Cycle Diagram ...
Page 13: ...13 7 Block Diagram ...
Page 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 15: ...15 8 2 Outdoor Unit 8 2 1 CU E24MKE ...
Page 16: ...16 8 2 2 CU E28MKE ...
Page 17: ...17 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 18: ...18 9 2 Outdoor Unit 9 2 1 CU E24MKE ...
Page 19: ...19 9 2 2 CU E28MKE ...
Page 20: ...20 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 22: ...22 10 1 6 Comparator Printed Circuit Board 10 1 7 Human Activity Sensor Printed Circuit Board ...
Page 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 24: ...24 10 2 2 Power Printed Circuit Board ...
Page 92: ...92 16 1 3 To remove power electronic controller ...
Page 93: ...93 16 1 4 To remove discharge grille 16 1 5 To remove control board ...
Page 94: ...94 16 1 6 To remove cross flow fan and indoor fan motor ...
Page 95: ...95 ...