28
11.2.4. Connect the Cable to the Indoor Unit
1. The inside and outside connection cable can be
connected without removing the front grille.
2.
Connection cable
between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 4 x 1.5 mm
2
flexible cord, type designation 245 IEC 57 or heavier
cord.
3. Bind all the indoor and outdoor connection cable with
tape and route the connection cable via the escapement.
4. Remove the tapes and connect the connection cable
between indoor unit and outdoor unit according to the
diagram below.
5. Secure the connecting cable onto the control board with the holder (clamper).
• Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
• Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
Summary of Contents for CS-E24MKES
Page 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control ...
Page 11: ...11 5 2 Outdoor Unit ...
Page 12: ...12 6 Refrigeration Cycle Diagram ...
Page 13: ...13 7 Block Diagram ...
Page 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 15: ...15 8 2 Outdoor Unit 8 2 1 CU E24MKE ...
Page 16: ...16 8 2 2 CU E28MKE ...
Page 17: ...17 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 18: ...18 9 2 Outdoor Unit 9 2 1 CU E24MKE ...
Page 19: ...19 9 2 2 CU E28MKE ...
Page 20: ...20 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 22: ...22 10 1 6 Comparator Printed Circuit Board 10 1 7 Human Activity Sensor Printed Circuit Board ...
Page 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 24: ...24 10 2 2 Power Printed Circuit Board ...
Page 92: ...92 16 1 3 To remove power electronic controller ...
Page 93: ...93 16 1 4 To remove discharge grille 16 1 5 To remove control board ...
Page 94: ...94 16 1 6 To remove cross flow fan and indoor fan motor ...
Page 95: ...95 ...