background image

© Panasonic HA Air-Conditioning (M) Sdn. Bhd. 2008.
Unauthorized copying and distribution is a violation of law.

Order No. PHAAM0810055C2

Air Conditioner

Indoor Unit      Outdoor Unit
CS-RE18JKE  CU-RE18JKE
CS-RE24JKE  CU-RE24JKE

TABLE OF CONTENTS

PAGE

PAGE

1 Safety Precautions

-----------------------------------------------

3

2 Specifications

-----------------------------------------------------

5

3 Features

-------------------------------------------------------------

8

4 Location of Controls and Components

-------------------

9

4.1. Indoor Unit--------------------------------------------------- 9
4.2. Outdoor Unit ------------------------------------------------ 9
4.3. Remote Control -------------------------------------------- 9

5 Dimensions

-------------------------------------------------------

10

5.1. Indoor Unit & Remote Control ------------------------ 10
5.2. Outdoor Unit----------------------------------------------- 11

6 Refrigeration Cycle Diagram

--------------------------------

13

7 Block Diagram

---------------------------------------------------

14

7.1. CS-RE18JKE  CU-RE18JKE-------------------------- 14
7.2. CS-RE24JKE  CU-RE24JKE-------------------------- 15

Summary of Contents for CS-E18JKEW

Page 1: ...18JKE CS RE24JKE CU RE24JKE TABLE OF CONTENTS PAGE PAGE 1 Safety Precautions 3 2 Specifications 5 3 Features 8 4 Location of Controls and Components 9 4 1 Indoor Unit 9 4 2 Outdoor Unit 9 4 3 Remote Control 9 5 Dimensions 10 5 1 Indoor Unit Remote Control 10 5 2 Outdoor Unit 11 6 Refrigeration Cycle Diagram 13 7 Block Diagram 14 7 1 CS RE18JKE CU RE18JKE 14 7 2 CS RE24JKE CU RE24JKE 15 ...

Page 2: ...Operation 42 13 3 Protection Control For Heating Operation 44 14 Servicing Mode 45 14 1 Auto OFF ON Button 45 14 2 Remote Control Button 46 15 Troubleshooting Guide 47 15 1 Refrigeration Cycle System 47 15 2 Relationship Between The Condition Of The Air Conditioner And Pressure And Electric Current 48 15 3 Breakdown Self Diagnosis Function 49 15 4 Error Codes Table 50 15 5 Self diagnosis Method 51...

Page 3: ...tion An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause electrical shock or fire 9 This equipment is strongly recommended to install with Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire in case equipment breakdown or insulation breakdow...

Page 4: ...ntenance 6 Pb free solder has a higher melting point than standard solder typically the melting point is 50qF 70qF 30qC 40qC higher Please use a high temperature solder iron In case of the soldering iron with temperature control please set it to 700 20qF 370 10qC Pb free solder will tend to splash when heated too high about 1100qF 600qC 7 Power supply connection to the conditioner Connect the powe...

Page 5: ...Outdoor Noise H L dB A 47 52 Power Level dB 61 66 H e a t i n g Capacity kW 0 90 5 80 8 00 0 90 8 60 9 90 BTU h 3070 19800 27300 3070 29300 33800 Kcal h 770 4990 6880 770 7400 8510 Running Current A 7 0 12 1 Input Power W 245 1 54k 2 60k 360 2 66k 3 20k COP W W 3 67 3 77 3 08 2 50 3 23 3 09 Kcal hW 3 14 3 24 2 65 2 14 2 78 2 66 Power Factor 96 96 Indoor Noise H L QLo dB A 44 37 47 38 Power Level d...

Page 6: ...in 16 00 565 17 30 611 Hi Cool m3 min ft3 min 16 30 575 18 4 650 Heat m3 min ft3 min 17 90 630 19 5 690 SHi Cool m3 min ft3 min 18 10 639 19 30 682 Heat m3 min ft3 min 18 50 653 20 0 709 Outdoor Airflow Hi Cool m3 min ft3 min 40 0 1410 50 2 1770 Heat m3 min ft3 min 38 6 1360 50 2 1770 Refrigeration Cycle Control Device Expansion Valve Capillary Tube Refrigerant Oil cm3 RB68A or Freol Alpha 68M 400...

Page 7: ...18JKE CU RE24JKE Indoor Heat Exchanger Fin Material Aluminium Pre Coat Aluminium Pre Coat Fin Type Slit Fin Slit Fin Row u Stage u FPI 2 u 15 u 19 2 u 15 u 21 Size W u H u L mm 810 u 315 u 25 4 810 u 315 u 25 4 Outdoor Heat Exchanger Fin Material Aluminium Pre Coat Aluminium Pre Coat Fin Type Corrugated Fin Corrugated Fin Row u Stage u FPI 2 u 34 u 17 2 u 30 u 19 Size W u H u L mm 36 4 u 714 u 794...

Page 8: ... Piping CS CU RE18JKE long piping up to 20 meter CS CU RE24JKE long piping up to 30 meter Easy to use remote control Quality Improvement Random auto restart after power failure for safety restart operation Gas leakage protection Prevent compressor reverse cycle Inner protector to protect compressor Noise prevention during soft dry operation Serviceability Improvement Breakdown Self Diagnosis funct...

Page 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...

Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control ...

Page 11: ...11 5 2 Outdoor Unit 5 2 1 CU RE18JKE ...

Page 12: ...12 5 2 2 CU RE24JKE ...

Page 13: ...13 6 Refrigeration Cycle Diagram ...

Page 14: ...14 7 Block Diagram 7 1 CS RE18JKE CU RE18JKE ...

Page 15: ...15 7 2 CS RE24JKE CU RE24JKE ...

Page 16: ...16 8 Wiring Connection Diagram 8 1 Indoor Unit ...

Page 17: ...17 8 2 Outdoor Unit 8 2 1 CU RE18JKE ...

Page 18: ...18 8 2 2 CU RE24JKE ...

Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...

Page 20: ...20 9 2 Outdoor Unit 9 2 1 CU RE18JKE ...

Page 21: ...21 9 2 2 CU RE24JKE ...

Page 22: ...22 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...

Page 23: ...23 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...

Page 24: ...24 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU RE18JKE ...

Page 25: ...25 10 2 2 Main Printed Circuit Board 10 2 2 1 CU RE24JKE ...

Page 26: ...26 10 2 3 Power Printed Circuit Board 10 2 3 1 CU RE24JKE ...

Page 27: ...irect sunlight or rain be careful that heat radiation from the condenser is not obstructed There should not be any animal or plant which could be affected by hot air discharged Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not place any obstacles which may cause a short circuit of the discharged air If piping length is over the piping length for additional gas a...

Page 28: ...he extended line is the centre of the hole Another method is by putting measuring tape at position as shown in the diagram above The hole centre is obtained by measuring the distance namely 128 mm for left and right hole respectively Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor side 11 2 2 To Drill a Hole in the Wall and Install a Sl...

Page 29: ...29 1 For the right rear piping 2 For the right and right bottom piping 3 For the embedded piping ...

Page 30: ...d outdoor unit shall be approved polychloroprene sheathed 4 u 1 5 mm2 flexible cord type designation 245 IEC 57 or heavier cord Secure the connecting cable onto the control board with the holder clamper This equipment must be properly earthed Ensure the colour of wires of outdoor unit and the terminal Nos are the same to the indoor s respectively Earth wire shall be Yellow Green Y G in colour and ...

Page 31: ... cutter and then remove the burrs 2 Remove the burrs by using reamer If burrs is not removed gas leakage may be caused Turn the piping end down to avoid the metal powder entering the pipe 3 Please make flare after inserting the flare nut onto the copper pipes ...

Page 32: ... Align the center of piping and sufficiently tighten the flare nut with fingers Further tighten the flare nut with torque wrench in specified torque as stated in the table Connecting the Piping to Outdoor Decide piping length and then cut by using pipe cutter Remove burrs from cut edge Make flare after inserting the flare nut located at valve onto the copper pipe Align center of piping to valves a...

Page 33: ...e valves to OPEN using a hexagonal wrench 4 mm 8 Mount valve caps onto the 2 way valve and the 3 way valve Be sure to check for gas leakage 11 3 4 Connect the Cable to the Outdoor Unit 1 Remove the control board cover from the unit by loosening the screw 2 Cable connection to the power supply through Isolating Devices Disconnecting means Connect the approved polychloroprene sheathed power supply c...

Page 34: ...onnecting means should have minimum 3 0 mm contact gap Earth wire shall be Yellow Green Y G in colour and longer than other AC wires for safety reason 11 3 5 Pipe Insulation 1 Please carry out insulation at pipe connection portion as mentioned in Indoor Outdoor Unit Installation Diagram Please wrap the insulated piping end to prevent water from going inside the piping 2 If drain hose or connecting...

Page 35: ... are depending on the air conditioner settings and the operation environment The final shifted value will be used as internal setting temperature and it is updated continuously whenever the electrical power is supplied to the unit 12 1 2 Cooling Operation 12 1 2 1 Thermostat control Compressor is OFF when Intake Air Temperature Internal Setting Temperate 1 5qC Compressor is ON after waiting for 3 ...

Page 36: ...lue of T1 will increase up to 10qC T2 will decreased by 3qC and T3 will decreased up to 8qC The Auto Operation Mode shifting will take place whenever operation mode changed from Cooling Soft Dry to Heating or vice versa 12 1 6 Indoor Fan Motor Operation A Basic Rotation Speed rpm i Manual Fan Speed Cooling Dry Fan motor s number of rotation is determined according to remote control setting Heating...

Page 37: ...h one fan speed only It starts when compressor starts operation and it stops 30 seconds after compressor stops operation 12 2 Airflow Direction 1 There are two types of airflow vertical airflow directed by horizontal vane and horizontal airflow directed by vertical vanes 2 Control of airflow direction can be automatic angles of direction is determined by operation mode heat exchanger temperature a...

Page 38: ...nditioner is stopped using remote control the vane will shift to close position 12 2 2 Horizontal Airflow 1 Automatic horizontal airflow direction can be set using remote control the vane swings left and right within the angles as stated below For heating mode operation the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below 2 Manual horizontal airflow direction ca...

Page 39: ...dge the operation starting time From the above judgment the decided operation will start operate earlier than the set time as shown below 12 4 OFF Timer Control OFF timer can be set using remote control the unit with timer set will stop operate at set time 12 5 Auto Restart Control 1 When the power supply is cut off during the operation of air conditioner the compressor will re operate within thre...

Page 40: ...ling operation A will be applied 13 1 4 IPM Power transistor Prevention Control A Overheating Prevention Control 1 When the IPM temperature rises to 110qC compressor operation will stop immediately 2 Compressor operation restarts after three minutes the temperature decreases to 95qC 3 If this condition repeats continuously 4 times within 20 minutes timer LED will be blinking F96 is indicated B DC ...

Page 41: ...mes within 20 minutes the unit will Stop operation Timer LED blinks and F91 indicated 13 1 7 Compressor Tank Temperature Rise Protection Control a Control start conditions For 5 minutes the compressor continuously operates and outdoor total current is between 0 65A and 1 65A During Cooling and Soft Dry operations Indoor suction temperature indoor piping temperature is below 4qC Indoor temperature ...

Page 42: ...erature and Indoor pipe temperature judgment by microcontroller if fulfilled When Cooling or Dry mode is operated more than 20 minutes or more 3 This control stopped if Compressor stopped Remote control setting changed fan speed temperature Outdoor air temperature and indoor intake temperature changed 4 Fan speed angle of louver vertical airflow angle will be adjusted accordingly in this control F...

Page 43: ...during its normal operation 4 If indoor heat exchanger temperature is higher than 13qC for five minutes the fan speed will return to its normal operation 13 2 6 Freeze Prevention Control 2 1 Control start conditions During Cooling operation and soft dry operation During thermo OFF condition indoor intake temperature is less than 10 C or Compressor stops for freeze prevention control Either one of ...

Page 44: ...ve 14qC in order to avoid compressor overloading 13 3 3 Overload Protection Control The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures 13 3 4 Cold Draught Prevention Control When indoor pipe temperature is low cold draught operation starts where indoor fan speed will be reduced 13 3 5 Deice Operation When outdoor pipe temper...

Page 45: ...ontrol to set change the advance setting of air conditioner operation 3 REMOTE CONTROL NUMBER SWITCH MODE The Remote Control Number Switch Mode will be activated if the Auto OFF ON button is pressed continuously for more than 11 seconds 3 beep sounds will occur at 11th seconds to identify the Remote Control Number Switch Mode is in standby condition and press AC RESET button and then press any but...

Page 46: ...conds by using pointer Press TIMER SET button until a beep sound is heard as confirmation of transmission code change To change the air quality sensor sensitivity Press and release by using pointer Press the Timer Decrement button to select sensitivity 1 Low Sensitivity 2 Standard Default 3 Hi Sensitivity Confirm setting by pressing Timer Set button a Beep sound will be heard LCD returns to origin...

Page 47: ... problems before inspecting the refrigeration cycle Such problems include insufficient insulation problem with the power source malfunction of a compressor and a fan The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions the standard values for them are shown in the table on the right ...

Page 48: ...es after an operation is started Cooling Mode Heating Mode Condition of the air conditoner Low Pressure High Pressure Electric current during operation Low Pressure High Pressure Electric current during operation Insufficient refrigerant gas leakage Clogged capillary tube or Strainer Short circuit in the indoor unit Heat radiation deficiency of the outdoor unit Inefficient compression ...

Page 49: ... on 2 Press the CHECK button on the remote controller continuously for 5 seconds 3 will be displayed on the remote controller display Note Display only for No transmitting signal no receiving sound and no Power LED blinking 4 Press the TIMER or button on the remote controller The code H00 no abnormality will be displayed and signal will be transmitted to the main unit The power LED lights up If no...

Page 50: ...utdoor air temperature sensor abnormality Continue for 5 sec O Outdoor temperature sensor defective or disconnected H28 Outdoor heat exchanger temperature sensor abnormality Continue for 5 sec O Outdoor heat exchanger temperature sensor defective or disconnected H30 Discharge temperature sensor abnormality Continue for 5 sec Discharge temperature sensor H33 Indoor Outdoor wrong connection Indoor O...

Page 51: ...transmission is checked whether it is normal Malfunction Caused Faulty indoor unit PCB Faulty outdoor unit PCB Indoor unit outdoor unit signal transmission error due to wrong wiring Indoor unit outdoor unit signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor units Indoor unit outdoor unit signal transmission error due to disturbed power supply w...

Page 52: ...are interconnected Malfunction Caused Wrong models interconnected Wrong indoor unit or outdoor unit PCBs mounted Indoor unit or outdoor unit PCBs defective Indoor outdoor unit signal transmission error due to wrong wiring Indoor outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor and outdoor units Troubleshooting ...

Page 53: ...ction Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Page 54: ...n Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Page 55: ...ions A current transformer CT is detected by checking the compressor running frequency rated frequency and CT detected input current less than 0 65A for continuously 20 seconds Malfunction Caused CT defective Outdoor PCB defective Compressor defective low compression Troubleshooting ...

Page 56: ...etermine abnormal fan motor feedback of rotation 2550rpm or 50rpm Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the fan motor Operation stops due to breaking of fan motor lead wires Operation stops due to Hall IC malfunction Operation error due to faulty indoor unit PCB Troubleshooting ...

Page 57: ... Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Page 58: ...ction Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Page 59: ...ction Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Page 60: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Page 61: ...alfunction Decision Conditions The supply power is detected for its requirement by the indoor outdoor transmission Malfunction Caused Wrong models interconnected Wrong indoor unit and outdoor unit PCBs used Indoor unit or outdoor unit PCB defective Troubleshooting ...

Page 62: ...lity Malfunction Decision Conditions If Patrol sensor feedback is 0V or 5V continuous for 6 hours Error will display only when the Patrol operation is ON Malfunction Caused Faulty connector connection Faulty Patrol sensor Troubleshooting ...

Page 63: ...eration is used to determine abnormal fan motor Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the fan motor Operation stops due to breaking of fan motor lead wires Operation stops due to Hall IC malfunction Operation error due to faulty outdoor unit PCB Troubleshooting ...

Page 64: ...During heating operation the temperature detected by the indoor pipe temperature sensor is above 60qC Malfunction Caused Clogged air filter of the indoor unit Dust accumulation on the indoor unit heat exchanger Air short circuit Detection error due to faulty indoor pipe temperature sensor Detection error due to faulty indoor unit PCB Troubleshooting ...

Page 65: ...Decision Conditions Freeze prevention control takes place when indoor pipe temperature is lower than 2qC Malfunction Caused Clogged air filter of the indoor unit Dust accumulation on the indoor unit heat exchanger Air short circuit Detection error due to faulty indoor pipe temperature sensor Detection error due to faulty indoor unit PCB Troubleshooting ...

Page 66: ...onditions When heating operation when indoor pipe temperature is below 10qC When cooling operation when indoor pipe temperature is above 45qC Malfunction Caused Connector in poor contact Faulty sensor Faulty outdoor unit PCB 4 way valve defective Troubleshooting ...

Page 67: ...peration of cooling and heating when Power Factor Correction PFC protection circuitry at the outdoor unit main PCB senses abnormal high DC voltage level Malfunction Caused DC voltage peak due to power supply surge DC voltage peak due to compressor windings not uniform Faulty outdoor PCB Troubleshooting ...

Page 68: ...y checking the CT detected input current value and the compressor running frequency During startup and operating of cooling and heating input current 8 78 256 A Hz u compressor running frequency 0 25 Gas shortage detection 2 A gas shortage is detected by checking the difference between indoor pipe temperature and indoor intake air temperature during cooling and heating Malfunction Caused Refrigera...

Page 69: ...alfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit Malfunction Caused Compressor terminal disconnect Outdoor PCB malfunction Troubleshooting ...

Page 70: ...s detected by the outdoor pipe temperature sensor Malfunction Caused Outdoor pipe temperature rise due to short circuit of hot discharge air flow Outdoor pipe temperature rise due to defective of outdoor fan motor Outdoor pipe temperature rise due to defective outdoor pipe temperature sensor Outdoor pipe temperature rise due to defective outdoor unit PCB Troubleshooting ...

Page 71: ...vated Heat Sink Overheating During operation of cooling and heating when heat sink temperature data 90 C is detected by the heat sink temperature sensor Malfunction Caused IPM overheats due to short circuit of hot discharge air flow IPM overheats due to defective of outdoor fan motor IPM overheats due to defective of internal circuitry of IPM IPM overheats due to defective IPM temperature sensor M...

Page 72: ...on of cooling and heating when compressor tank temperature data 112 C is detected by the compressor tank temperature sensor Malfunction Caused Refrigerant shortage refrigerant leakage 2 3 way valve closed Detection error due to faulty compressor tank temperature sensor Troubleshooting ...

Page 73: ... detected by checking the input current value being detected by current transformer CT with the compressor running Malfunction Caused Over current due to compressor failure Over current due to defective outdoor unit PCB Over current due to defective inverter main circuit electrolytic capacitor Over current due to excessive refrigerant Troubleshooting ...

Page 74: ...peak due to compressor failure DC peak due to defective power transistor s DC peak due to defective outdoor unit PCB Troubleshooting Checking the power transistor Never touch any live parts for at least 10 minutes after turning off the circuit breaker If unavoidable necessary to touch a live part make sure the power transistor s supply voltage is below 50V using the tester For the UVW make measure...

Page 75: ...or Removal Procedures 16 1 1 To remove front grille 16 1 2 To remove horizontal vane WARNING High Voltage are generated in the electrical parts area by the capacitor Ensure that the capacitor has discharged sufficiently before proceeding with repair work Failure to heed this caution may result in electric shocks ...

Page 76: ...76 16 1 3 To remove power electronic controller ...

Page 77: ...77 16 1 4 To remove discharge grille 16 1 5 To remove control board ...

Page 78: ...78 16 1 6 To remove cross flow fan and indoor fan motor ...

Page 79: ...79 ...

Page 80: ...Top Panel Fig 1 2 Remove the 10 screws of the Front Panel Fig 2 3 Remove the Top Cover of the Electronic Controller Fig 3 4 Remove the Control Board Fig 4 5 Remove the 8 screws of the Electronic Controller Fig 5 Caution When handling electronic controller be careful of electrostatic discharge ...

Page 81: ...ration Characteristics 17 1 1 CS RE18JKE CU RE18JKE Cooling Characteristic at Different Outdoor Air Temperature Condition Indoor room temperature 27 19qC Remote control setting HI FAN COOL 16qC Compressor frequency Fc Voltage 230 V ...

Page 82: ...82 Cooling Characteristic at Different Piping Length Condition Indoor room temperature 27 19qC 35 qC Remote control setting HI FAN COOL 16qC Compressor frequency Fc Voltage 230 V ...

Page 83: ...83 Heating Characteristic at Different Outdoor Air Temperature Condition Indoor room temperature 20 qC Remote control setting HI FAN HEAT 30qC Compressor frequency Fh Voltage 230 V ...

Page 84: ...84 Heating Characteristic at Different Piping Length Condition Indoor room temperature 20 qC 7 6qC Remote control setting HI FAN HEAT 30qC Compressor frequency Fh Voltage 230 V ...

Page 85: ... 1 2 CS RE24JKE CU RE24JKE Cooling Characteristic at Different Outdoor Air Temperature Condition Indoor room temperature 27 19qC Remote control setting HI FAN COOL 16qC Compressor frequency Fc Voltage 230 V ...

Page 86: ...86 Cooling Characteristic at Different Piping Length Condition Indoor room temperature 27 19qC 35 qC Remote control setting HI FAN COOL 16qC Compressor frequency Fc Voltage 230 V ...

Page 87: ...87 Heating Characteristic at Different Outdoor Air Temperature Condition Indoor room temperature 20 qC Remote control setting HI FAN HEAT 30qC Compressor frequency Fh Voltage 230 V ...

Page 88: ...88 Heating Characteristic at Different Piping Length Condition Indoor room temperature 20 qC 7 6qC Remote control setting HI FAN HEAT 30qC Compressor frequency Fh Voltage 230 V ...

Page 89: ... 4 31 3 47 1 70 22 0qC 5 94 4 08 1 40 5 55 3 93 1 50 5 16 3 79 1 61 4 69 3 61 1 73 Outdoor Temp qC Indoor wet bulb temp 30 35 40 46 TC SHC IP TC SHC IP TC SHC IP TC SHC IP 17 0qC 6 75 5 11 1 94 6 30 4 90 2 09 5 86 4 71 2 23 5 33 4 48 2 41 19 0qC 6 80 2 12 19 5qC 7 41 5 35 1 98 6 92 5 14 2 13 6 44 4 95 2 28 5 85 4 71 2 45 22 0qC 8 07 5 55 2 01 7 54 5 34 2 17 7 02 5 15 2 32 6 38 4 91 2 50 TC SHC IP ...

Page 90: ...90 18 Exploded View and Replacement Parts List 18 1 Indoor Unit ...

Page 91: ...WH131350 m 21 INDICATOR HOLDER 1 CWD933021 m 22 CONTROL BOARD FRONT COVER 1 CWH13C1183 m 23 DISCHARGE GRILLE COMPLETE 1 CWE20C3007 m 24 FULCRUM 2 CWH621103 m 25 VERTICAL VANE 15 CWE241289 m 26 CONNECTING BAR 1 CWE261156 m 27 CONNECTING BAR 1 CWE261158 m 28 CONNECTING BAR 1 CWE261157 m 29 CONNECTING BAR 1 CWE261159 m 30 CONNECTING BAR 1 CWE261160 m 31 AIR SWING MOTOR 1 CWA98K1014 m O 32 AIR SWING M...

Page 92: ...18JKE CS RE24JKE REMARKS 49 INSTALLATION INSTRUCTION 1 CWF613910 m 50 INSTALLATION INSTRUCTION 1 CWF613911 m 51 INSTALLATION INSTRUCTION 1 CWF613912 m 52 INSTALLATION INSTRUCTION 1 CWF613913 m 53 INSTALLATION INSTRUCTION 1 CWF613914 m 54 INSTALLATION INSTRUCTION 1 CWF613915 m 55 INSTALLATION INSTRUCTION 1 CWF613916 m 56 SUPER ALLERU BUSTER FILTER 1 CWD00C1263 m ...

Page 93: ...93 18 2 CU RE18JKE Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 94: ...VER 1 CWH171039A 24 NUT TERMINAL COVER 1 CWH7080300J 25 SENSOR COMPLETE COMP TOP 1 CWA50C2185 26 HOLDER SENSOR 1 CWH32074 27 V COIL COMPLETE 4 WAYS VALVE 1 CWA43C2168J 28 V COIL COMPLETE EXPAND VALVE 1 CWA43C2058J 29 SENSOR COMPLETE COMP DISC 1 CWA50C2180 30 SENSOR COMPLETE AIR TEMP AND HEAT EXCHANGE 1 CWA50C2181 31 REACTOR 1 G0C203J00003 33 TERMINAL BOARD ASSY 1 CWA28K1110J 35 FUSE CAP TERMINAL 1...

Page 95: ...95 18 3 CU RE24JKE Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 96: ...51057 25 3 WAYS VALVE GAS 1 CWB011363 O 26 2 WAYS VALVE LIQUID 1 CWB021434 O 27 SOUND PROOF BOARD 1 CWH151197 28 TERMINAL COVER 1 CWH171039A 29 NUT TERMINAL COVER 1 CWH7080300J 30 SENSOR COMPLETE COMP TOP 1 CWA50C2185 31 HOLDER SENSOR 1 CWH711010 32 V COIL COMPLETE 1 CWA43C2169J 33 V COIL COMPLETE FOR EXP VALVE 1 34 SENSOR CO COMP DISCHARGE 1 CWA50C2515 35 SENSOR COMPLETE 1 CWA50C2517 36 REACTOR 1...

Reviews: