15.1.1.
Relationship Between The Condition of The Air Conditioner and Pressure and
Electric Current
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
15.1.2.
Diagnosis Methods Of A Malfunction Of A Compressor And 4-way Valve
Cooling Mode
Heating Mode
Condition of the air
conditioner
Low Pressure
High Pressure
Electric current
during operation
Low Pressure
High Pressure
Electric current
during operation
Insufficient refrigerant
(gas leakage)
Clogged capillary tube or
Strainer
Short circuit in the indoor unit
Heat radiation deficiency of the
outdoor unit
Inefficient compression
Nature of fault
Symptom
• Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor
• The discharge tube of the compressor becomes abnormally hot (normally 70 to 90
°
C).
• The difference between high pressure and low pressure becomes almost zero.
• Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
• The compressor has a humming sound.
• Electric current during operation becomes approximately 80% lower than the normal value.
Insufficient switches of the 4-way valve
• The temperature different between from the discharge tube to the 4-way valve and from
suction
• tube to the 4-way valve becomes almost zero.
Summary of Contents for CS-A12HKD
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Outdoor Unit ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS A7HKD CS A9HKD CS A12HKD ...
Page 14: ...14 5 2 Outdoor Unit 5 2 1 CU A7HKD CU A9HKD 5 2 2 CU A12HKD ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram 7 1 CS A7HKD CU A7HKD CS A9HKD CU A9HKD ...
Page 17: ...17 7 2 CS A12HKD CU A12HKD ...
Page 20: ...20 9 Electronic Circuit Diagram ...
Page 21: ...21 10 Printed Circuit Board 10 1 Main Printed Circuit Board ...
Page 22: ...22 10 2 Power Printed Circuit Board TOP VIEW BOTTOM VIEW ...
Page 23: ...23 10 3 Indicator Printed Circuit Board 10 4 Patrol Printed Circuit Board ...
Page 51: ...51 Normal Deice Time Diagram Overload Deice Time Diagram ...
Page 57: ...57 ...
Page 58: ...58 16 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures ...
Page 59: ...59 ...
Page 60: ...60 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry Heating ...
Page 61: ...61 17 2 Operation Characteristics 17 2 1 CS A7HKD CU A7HKD ...
Page 62: ...62 ...
Page 63: ...63 ...
Page 64: ...64 ...
Page 65: ...65 17 2 2 CS A9HKD CU A9HKD ...
Page 66: ...66 ...
Page 67: ...67 ...
Page 68: ...68 ...
Page 69: ...69 17 2 3 CS A12HKD CU A12HKD ...
Page 70: ...70 ...
Page 71: ...71 ...
Page 72: ...72 ...