• Patrol Sensor Control
- First 2 minutes from Patrol function activates is stabilization time, during stabilization time, no air dirtiness level is monitored.
The Air Dirtiness level is set to Clean, Patrol LED turns blue color.
- After that, Patrol sensor starts to record the resistance value at fixed interval. Higher resistance value indicates cleaner air.
- The air dirtiness level is monitored by comparing the current resistance value with maximum resistance value from time to
time to get the Air Dirtiness Value.
- There are 3 air dirtiness level, based on the Air Dirtiness Value:
• Air Dirtiness level 0: Clean
— Patrol LED = blue color
• Air Dirtiness level 1: Moderate
— Patrol LED = orange color
• Air Dirtiness level 2: Contaminated — Patrol LED = red color
• Dirtiness level sensitivity adjustment
It is possible to change the Patrol sensor sensitivity, where the Threshold value (G1 ~ G4) will be shifted accordingly:
1. Press and release “SET” button.
2. Press “Timer
” / “Timer
” button to select sensitivity.
(Air 1 “Low Sensitivity”
Air 2 “Standard” (Default)
Air 3 “High Sensitivity”)
3. Confirm setting by pressing “Timer Set” button. LCD returned to original display after 2 seconds.
4. LCD returned to original display if remote control does not operate for 30 seconds.
• e-ion Control
- e-ion operation starts condition
• When dirtiness at level 2 (Patrol LED turns red).
- e-ion operation time
• If dirtiness level improves from level 2 to level 1 (Patrol LED turns from red to orange), the unit carries out level change
after 60 seconds.
• When dirtiness level returns to level 0 (Patrol LED turns blue) continuously for 11 minutes or more, e-ion operation stops.
• Dirtiness Level and fan speed
- When e-ion operation starts, the fan speed increases based on dirtiness level:
- Indoor Fan Control
• During any operation mode combines with Patrol operation, fan speed follows respective operation mode.
• During Patrol individual operation if e-ion starts, only Auto Fan Speed and no Powerful operation is allowed. Even if “Fan
Speed” button is pressed, no signal is sent to air conditioner, and no change on LCD display.
• During Patrol individual operation if e-ion stops, Indoor Fan stop operation.
• Airflow direction (Horizontal, Vertical) Control
- During any operation mode combines with Patrol operation, air flow direction follows respective operation mode.
- During Patrol individual operation if e-ion starts, only Auto Air Swing is allowed. Even if “Air Swing” button is pressed, no
signal is sent to air conditioner, and no change on LCD display.
- During Patrol individual operation if e-ion stops, Airflow direction louver closed.
Summary of Contents for CS-A12HKD
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Outdoor Unit ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS A7HKD CS A9HKD CS A12HKD ...
Page 14: ...14 5 2 Outdoor Unit 5 2 1 CU A7HKD CU A9HKD 5 2 2 CU A12HKD ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram 7 1 CS A7HKD CU A7HKD CS A9HKD CU A9HKD ...
Page 17: ...17 7 2 CS A12HKD CU A12HKD ...
Page 20: ...20 9 Electronic Circuit Diagram ...
Page 21: ...21 10 Printed Circuit Board 10 1 Main Printed Circuit Board ...
Page 22: ...22 10 2 Power Printed Circuit Board TOP VIEW BOTTOM VIEW ...
Page 23: ...23 10 3 Indicator Printed Circuit Board 10 4 Patrol Printed Circuit Board ...
Page 51: ...51 Normal Deice Time Diagram Overload Deice Time Diagram ...
Page 57: ...57 ...
Page 58: ...58 16 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures ...
Page 59: ...59 ...
Page 60: ...60 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry Heating ...
Page 61: ...61 17 2 Operation Characteristics 17 2 1 CS A7HKD CU A7HKD ...
Page 62: ...62 ...
Page 63: ...63 ...
Page 64: ...64 ...
Page 65: ...65 17 2 2 CS A9HKD CU A9HKD ...
Page 66: ...66 ...
Page 67: ...67 ...
Page 68: ...68 ...
Page 69: ...69 17 2 3 CS A12HKD CU A12HKD ...
Page 70: ...70 ...
Page 71: ...71 ...
Page 72: ...72 ...