- If the compressor is operating continuously for 5 minutes or longer
and the temperature difference between intake air and indoor heat
exchanger is 2.5°C or less for 2 minutes, compressor will stop and
restart automatically. / (Time Delay Safety Control is valid)
T = Intake air temperature - Indoor heat exchanger temperature /
This is to protect reverse rotation of the compressor when there is
a instantaneous power failure.
Compressor Protection Control
- After the compressor starts for 50 seconds but the outdoor fan
motor is still OFF, the compressor will stop and restart
automatically. (Time Delay Safety Control is valid).
- If the above phenomenon is repeated for 3 times, the compressor
will stops.
- The above phenomenon is reset when there is a change to heating
mode or stopped by Remote Control Switch.
Automatic Fan Speed Mode
When Automatic Fan Speed is selected at Remote Control during cooling operation.
- Fan speed rotates in the range of Hi to Me.
- Deodorizing Control.
20
Summary of Contents for CS-A123KR
Page 13: ...13 ...
Page 14: ...5 Refrigeration Cycle Diagram 14 ...
Page 15: ...6 Block Diagram 15 ...
Page 16: ...7 Wiring Diagram 16 ...
Page 17: ...REMARKS B BLUE BR BROWN BL BLACK W WHITE R RED O ORANGE P PINK Y G YELLOW GREEN 17 ...
Page 29: ...29 ...
Page 32: ...Overload Deicing Time Diagram 32 ...
Page 49: ...3 For the embedded piping 49 ...
Page 50: ... This can be used for left rear piping and left bottom piping also 50 ...
Page 75: ...75 ...
Page 78: ...78 ...
Page 79: ...79 ...
Page 80: ...15 Exploded View 80 ...
Page 89: ...How to use electronic circuit diagram 89 ...
Page 90: ...TIMER TABLE 90 ...
Page 92: ...22 2 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD TOP VIEW 92 ...
Page 93: ...22 3 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD BOTTOM VIEW 93 ...
Page 94: ... MACC Printed in Malaysia 94 ...