background image

7

English

• To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end or 

cover it with tape.

Do not allow air, etc., to become mixed with the specified refrigerant inside the refrigeration cycle.

The outdoor unit is charged with refrigerant.

To prevent flare nut cracking and gas leaks, be sure to use both a spanner and torque wrench together, as 
shown in the drawing, when connecting or disconnecting pipes to / from the unit.

Refer to the table below for flare measurements.

When connecting the flare nut, coat the flare both inside and outside with ester oil or ether oil and initially 
tighten by hand 3 or 4 turns before tightening firmly.

Refer to the table for tightening torque. Overtightening may damage the flare.

Use the attached pipe, with the “CS-

∗∗

PM1HPK”.

Wrap only the gas line side with the sealing pad (5). Bend the pad over the insulation for fitting (union) from 
above.

After inspecting pipe joints for gas leakage, be sure to insulate with the accessory joint insulation for fitting 
(3) (4) while referring to the figure on the next page. (Fasten both ends with clamps (6)).

CAUTION

Overtightening may damage the flare and cause leaks.

Use “ Tabel 2 ” as a reference if a torque wrench is not available. Once work is complete, make sure there is 
no gas leaking. As the flare nut is tightened with the wrench, the torque will suddenly increase. From that posi-
tion, tighten the nut to the angle shown on “ Tabel 2 ”.

Make absolutely sure to execute heat insulation works on the pipe-connecting section after checking gas 
leakage by thoroughly studying the following figure and using the attached heat insulating materials for 
fitting (3) and (4). (Fasten both ends with the clamps (6) (attached).) 

(Refer to Fig. 1)

Wrap the sealing pad (5) (attached) only around the insulation for the joints on the gas piping side. 

CAUTION

Be sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping 
may cause condensation or burns if touched.

When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution 
(NOTE 1) or while inserting nitrogen into the refrigerant piping (NOTE 2). Once this is done, connect the 
indoor unit with a flared or a flanged connection.

NOTES

1.

Refer to the “Manual for Multi Installation for Buildings” for directions on how to carry out nitrogen substi-
tution. (Inquire with your dealer.)

2.

Nitrogen should be set to 0.02 Mpa (0.2 kg/cm

2

) with a pressure-reducing valve if brazing while inserting 

nitrogen into the piping.

Torque wrench

Flare nut

Piping union

Spanner

Coated with ester 
oil or ether oil.

Insulation for fitting 
(accessory) (4)

(For liquid pipes)

Clamp (6)
(4 accessory)

Insulation for fitting 
(accessory) (3)

(For gas pipes)

Sealing pad (accessory) (5)

(Wrapped over union)

Gas pipe

Liquid pipe

Fig. 1

Refrigerant piping

Part to be brazed

Taping

Pressure-reducing valve

hands valve

Nitrogen

Nitrogen

Summary of Contents for CS-20PM1HPK

Page 1: ...NSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI ÄÉÁÂÁÓÔÅ ÐÑÏÓÅÊÔÉÊÁ ÁÕÔÅÓ ÔÉÓ ÏÄÇÃÉÅÓ ÐÑÉÍ ...

Page 2: ... result in water leakage electric shocks or fire Be sure to use only the specified accessories and parts for installation work Failure to use the specified parts may result in water leakage electric shocks fire or the unit falling Install the air conditioner on a foundation strong enough to withstand the weight of the unit A foundation of insufficient strength may result in the equipment falling a...

Page 3: ...ng copper pipes or soldered parts may result in refrigerant leakage c near machinery emitting electromagnetic waves Electromagnetic waves may disturb the operation of the control system and result in a malfunction of the equipment d where flammable gases may leak where there are carbon fiber or ignitable dust suspensions in the air or where volatile flammables such as thinner or gasoline are handl...

Page 4: ... object in fan heater stove cooking appliance etc may result in production of toxic gases This unit both indoor and outdoor is suitable for installation in a commercial and light industrial environ ment If installed as a household appliance it could cause electromagnetic interference 2 2 ACCESSORIES Check the following accessories are included with your unit 2 3 OPTIONAL ACCESSORIES These are two ...

Page 5: ...or units is possible within the allowable limit Refer to the instal lation manual of the outdoor unit Keep the indoor and outdoor units power cable and transmission wiring at least 1 m from TVs and radios to prevent distorted pictures and static Depending on the type and source of the electrical waves static may be heard even when more than 1 m away Items to be checked If not properly done what is...

Page 6: ...ite order Pull towards the front unit the knob snaps in place Maintenance area 80 or more A or more B or more 625 CS 20 25RM1HPK CS 32 40RM1HPK CS 50 63RM1HPK CS 20 25PM1HPK CS 32 40PM1HPK CS 50 63PM1HPK A mm 570 710 990 B mm 1030 1170 1450 IMPORTANT Leave sufficient clearance for air inlet and maintenance Model CS RM1HPK Base CS PM1HPK Window 100 or more PM1HPK 150 or more RM1HPK 100 or more PM1H...

Page 7: ...y Open the left side lid of control panel and mount the lower case on the remote controller switch 6 REFRIGERANT PIPING WORK For refrigerant piping of outdoor units see the installation manual attached to the outdoor unit Be sure to thermally insulate both the gas pipes and fluid pipes Water leakage may result if the pipes are not insulated Only use insulation resistant to at least 120 C Furthermo...

Page 8: ...will suddenly increase From that posi tion tighten the nut to the angle shown on Tabel 2 Make absolutely sure to execute heat insulation works on the pipe connecting section after checking gas leakage by thoroughly studying the following figure and using the attached heat insulating materials for fitting 3 and 4 Fasten both ends with the clamps 6 attached Refer to Fig 1 Wrap the sealing pad 5 atta...

Page 9: ... the right drawing 2 After piping work is finished check drainage flows smoothly 3 Be sure to insulate all indoor pipes CAUTION Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sew age might enter the indoor unit through the drain pipes and corrode the heat exchanger Pipe gauge Tightening torque Flare dimension A mm Flare sh...

Page 10: ...to the entire system must be installed 8 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A 8 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE NOTES 1 Allowable length of transmission wiring between indoor outdoor units and between the indoor unit and the remote controller is as follows 1 Outdoor unit Indoor unit Max 1000 m T...

Page 11: ...unit wire as shown in the figure on the right If wiring from the piping side wire as shown in the figure on the right CAUTION When cramping wiring use the included cramping material to do an appropriate cramp to prevent undue pressure on the wiring connections When carrying out the wiring bundle the wires to prevent the switch box lid from lifting and attach the lid firmly When attaching the switc...

Page 12: ...deteriorate protection 4 Keep transmission wiring at least 50 mm away from power supply wiring The equipment may malfunction if subjected to electrical external noise 5 For remote controller wiring refer to the INSTALLATION MANUAL OF REMOTE CONTROLLER 6 Never connect power supply wiring to the terminal board for transmission wiring A mistake of the sort could damage the entire system 7 Use only sp...

Page 13: ... 220 240V 50Hz or 220V 60Hz Power supply 220 240V 50Hz or 220V 60Hz IN D OUT D F1 F2 F1 F2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 L N Control box Outdoor unit No 2 System Indoor unit A Indoor unit B Indoor unit C Most downstream indoor unit For use with 2 remote controllers Power supply 220 240V 50Hz or 220V 60Hz Note It is not necessa...

Page 14: ...e the switch of the other remote controller set to M 9 4 COMPUTERISED CONTROL FORCED OFF AND ON OFF OPERATION 1 Wire specifications and how to perform wiring Connect the input from outside to terminals T1 and T2 of the terminal board remote controller to trans mission wiring 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to input A Wire specification Sheathed...

Page 15: ...TION FORCED OFF at factory set 9 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional controllers for centralized control 10 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the remote controller will flash when an error occurs Check the error code on the liq uid crystal dis...

Page 16: ... 0110 HT 3VA11734 2A EM01A161 ...

Reviews: