KW8M Eco-POWER METER (1A/5ACT input type)
45
Chapter 8 Specifications
8.1 Main unit
Rated operating voltage
100 to 240V AC
Rated frequency
50/60Hz common
Rated power consumption
8VA
Inrush current
Max. 30A (240VAC at 25
℃
)
Allowable operating
voltage range
85 to 264V AC (85 to 110% of rated operating voltage)
Allowable momentary
power-off time
10ms
Ambient temperature
-10 to +50
℃
(-25 to +70
℃
at storage)
Ambient humidity
30 to 85%RH (at 20
℃
non-condensing)
Breakdown voltage(initial)
Between the isolated circuits:
2000V for 1min
note) Cut-off current: 10mA
Insulation
resistance(initial)
Between the isolated circuits:
100M
Ω
or more
(measured at 500V DC)
A)Outer edge (enclosure)
-
All terminals
B)Insulated circuit
・
Operating power supply terminals
-
Analog input terminals
・
Operating power supply terminals
-
Pulse input terminal
・
RS485
-
All other terminals
・
Pulse output terminals
-
All other terminals
note1)
Vibration resistance
10 to 55Hz (1cycle/min) single amplitude : 0.375mm (1h on 3 axes)
Shock resistance
Min. 294m/s
2
(5 times on 3 axes)
Display method
8-digit, 7-segment LED
Power failure
memory method
EEP-ROM (more than 100,000 overwrite)
Size
48 x 96 x 98.5 mm
Weight
approx.265g (without mounting bracket)
note1) Analog input terminals: No.11 to 20 / Pulse input terminal: No.4 and 5