KW8M Eco-POWER METER (1A/5ACT input type)
12
Chapter 4 Settings
4.1 Operation procedure
【
Basic setting to measure
】
When wiring Eco-POWER METER and CT and setting mode 1 after power on, Eco-POWER Meter can
measure the electric power. In order to use the other functions, set mode2, 3 and 4 according to your
use.
Monitor (Display when power on)
Mode 1
…
Mode for setting each parameter for power
<MODE>
measurement
Setting mode
(Mode 1)
(Mode 2)
(Mode 3)
(Mode 4)
<SET>
<SET> <SET>
<SET>
Phase/Wire system setting mode
SYST
Refer to the next page.
<SET>
CT type setting mode
CT-T
<SET>
Primary side current of CT
setting mode
CT-1
<SET>
Voltage range setting mode
VOLT
<SET>
VT setting mode
VT
<SET>
Current for time measurement
setting mode
HM-A
<SET>
Cutoff current setting mode
CUTA
<SET>
Unit for pulse output setting mode
PL-P
When select
When select “AL-P”
<SET>
When select “AL-C”
<SET>
When select “AL-S”
<SET>
When select “Cnt”
<SET>
“Values”
<SET>
Power alarm setting
mode
AL-P
Current alarm setting
mode
AL-C
Stand-by alarm setting
mode 1
AL-S 1
Preset value setting
mode
Cnt
<SET>
<SET>
<SET>
Stand-by alarm setting
mode 2
AL-S 2
<SET>
Electricity rate setting mode
RATE
<SET>
<SET>
Monitor
Press <MODE> to return Monitor.