[5] Size F of 400 V System
Name
Terminal
symbol
Terminal no.
(upper to bottom)
Description
24V 1
Termin
al
block
Control
power
supply
input
0V 2
24 V dc +/- 15%
L1 1
L2 2
Main power
supply input
L3 3
3 phase 380–480 V
+ 10%
- 15%
50/60 Hz input
B1 4
B3 5
B2 6
Regen
resistor
connection
NC 7
Normally, short out the circuit between B2 and B3.
When a trip happens due to a regenerative load protection error, open the circuit
between B2 and B3 and connect an external regenerative resistor (prepared by
customer) between B1 and B2.
Note: Keep NC terminal unconnected.
U 8
V 9
Termin
al block
Motor
connection
W 10
Connect each phase of the motor winding.
U: U phase V: V phase W: W phase
Earth
-
There are 2 grounding terminals.
Connect the one terminal to ground, and the other to the E terminal of a motor.
Do not connect more than one wire to a grounding terminal.
• Refer to section 9-3 for the tightening torque of the screw.
• Tighten the fixing screw of the terminal block cover with a torque 0.2 N•m or lower.
[6] Size G of 200 V and 400 V System
Terminal symbol
Name
200 V 400 V
Terminal no.
(upper to
bottom)
Description
L1 L1
1
200 V : 3 phase 200–230 V
+ 10%
- 15%
50/60 Hz input
L2 L2
2
Main power
supply input
L3 L3
3
400 V :
3 phase 380–480 V
+ 10%
- 15%
50/60 Hz input
B1 B1
4
B2 B2
5
Regen resistor
connection
NC NC
6
• When tripped by a regenerative load protect error, connect an external
regenerative resistor (the value set by parameter Pr0.16 and prepared by the
user) across B1 and B2.
Note: Keep NC terminal unconnected.
U U
7
V V
8
Termin
al block
(lef
t sid
e)
Motor
connection
W W
9
• Connect each phase of the motor winding.
U: U phase V: V phase W: W phase
NC
NC
1
• Leave this terminal unconnected.
L1C
24V
2
200 V : Single phase 200–230 V
+ 10%
- 15%
50/60 Hz input
Control power
supply input
L2C
0V
3
400 V : 24 V dc +/- 15%
NC NC
4
NC NC
5
• Leave this terminal unconnected.
DB1
DB1
6
Dynamic brake
resistor control
terminal
DB2
DB2
7
• Connect when it is necessary to control the MC for external dynamic brake
resistor (prepared by the user).
• Impress the voltage AC300V or less or DC100V or less between DB1 and
DB2.
NC NC
8
NC NC
9
• Leave this terminal unconnected.
DB3
DB3
10
Dynamic brake
resistor control
terminal
DB4
DB4
11
• Be short-circuited usually between DB3 and DB4.
Remove the short bar when you use the external dynamic brake resistor.
Termin
al block
(ri
ght
si
de
)
NC
NC
12
Earth
–
There are 2 grounding terminals.
Connect the one terminal to ground, and the other to the E terminal of a motor.
Do not connect more than one wire to a grounding terminal.
• Refer to section 9-3 for the tightening torque of the screw.
• Tighten M3 terminal block cover fixing screw with the 0.2 N•m torque.