All technical features and data are subject to changes without notice, resulting from continuous development and improvement. 

Product Leaflet 

Date of issue 

Revision / Date of revision  

MEW00277 2003-04-15 

2008-08-18 

 

Type numbers 

1826 

External Fire Brigade Panel.  

1826SE / 1826CC

:  Designation texts on the front in 

Swedish / see below.  

NOTE!

  In Swedish convention (SBF):  No "General fault" 

presentation. 

1835 

Printer for External Fire Brigade Panel 1826 

1582 

External FBP interface board.  (Required in EBL

512

 / 500 when SW mode 

1826/28 – 

1582 2nd Cab

 shall be used.) 

1587 

External FBP / DU interface board.  (Required in EBL

512

 when SW mode 

1826/28 – 

1587

 

2nd Cab

 shall be used.  EBL512 software V>2.3.2

 1

 required.) 

2431 

Connection board. (Required in EBL

1000

. SW mode 

1826/28 – 1582 2nd Cab

 only.) 

4552 

RS485 Transceiver component / comm. module.  (Required in EBL

128

.  SW mode 

1826/28 – 1587

 

2nd Cab

 only.  EBL128 software V>1.0.5

 1

 required.) 

1

  Only required if the new function ("General fault" presentation) shall be used.

 

NOTE!

  The number of ext. FBPs that can be power supplied via the c.i.e. / board / external power 

supply, is depending on if each 1826 unit has a printer or not, as well as all other units connected to the 
same c.i.e. / board / external power supply.

2

  Up to 1200 m cable can be used. 

1826

CC

 is a unit with a neutral front where the designation texts by production are made separately and 

put into a transparent "text slot" for the LED and push button respectively.  

CC

=Country Code. 

The ext. FBP 1826 can run in one of two different SW modes:   

a)

  

1826 in SW mode 1826/28 – 1587 

2nd Cab

 has the highest performance with regard to 

functionality, response time, ability to store fire alarms, etc. and is intended to succeed the ext. FBP 2426 
(1826+printer 1835 will succeed the ext. FBP 2425) but not as a spare part, since 1826, in this SW mode, 
requires an Ext. FBP / DU interface board 1587 in the EBL512 c.i.e. and the look, dimensions, etc. are 
not the same.  This mode is always to be used when the ext. FBP is connected to EBL128. 

b)

  

1826 in SW mode

 

1826/28 – 1582 

2nd Cab

 has the same functionality as the ext. FBP 2426 and can 

be used as a spare part (1826+printer 1835 is a spare part for the ext. FBP 2425), i.e. the performance is 
the same but the look, dimensions, etc. are not the same.  1826, in this SW mode, requires an Ext. FBP 
interface board 1582 in the EBL512 / EBL500 c.i.e.   

Technical data 

Voltage (V DC) 

  rated 
  allowed 

 

24 
12-30 

  normal (in the system) 
  normal (in the system by battery back-up) 

24 
21-27 

Current consumption at norm. volt. (mA) 

  Ext. FBP 1826 
    quiescent / active 
  Printer 1835 
    quiescent / active 

 

 

26

 (at 24 V), 48 (at 12 V) / 

49

 (at 24 V), 88 (at 12 V) 

 

4

 (at 24 V), 7 (at 12 V) / 

161

 (at 24 V), 345 (at 12 V) 

Ambient temperature (

°

C) 

  operating 
  storage 

 

0 to +40 
-40 to +70 

Ambient humidity (% RH) 

max. 90, non condensing 

Ingress Protection rating (estimated) 

IP52 

Size W x H x D (mm) 

415 x 290 x 128 

Weight (g) 

  Ext. FBP 1826 (excl. printer) 
  Printer 1835 (incl. paper roll) / paper roll 

 

5000 
345  /  110 

Colour (metal cabinet / door) 

Light grey (NCS S 1500-N, PMS Cool grey 2) & aluminium sides. 

Approvals 

CE;  Conforms with EN54-2 and –4 whenever applicable. 
Conforms with SS3654 edition 1. 

2

  On each 1582 board are up to eight addresses available and on each 1587 board up to sixteen addresses. In EBL128 

are up to four addresses available.

 