Element 

Tag: 

  <outlet> 

Attribute: 

 

 

id = “bank” 

 

 

“bank” is the affected outlet bank number

Content   

 

 

0 | 1 

 

 

 

0 = outlet bank is OFF

        1 

outlet 

bank 

is 

ON

Example: 

 

 

<outlet id=”1”>0</outlet>   

Outlet bank 1 is OFF

EVENTS

Event messages are sent autonomously from SM3-PRO when some change occurs within the device – they are not replies to a query.

Subscribing to Event Messages

After start-up, SM3-PRO will not send any event messages.  To receive event messages a command to “subscribe” to events must be sent.  

The event subscription command is enclosed within the XML declaration and <device> element and is as follows:

 

...<commands><eventmgr><subscribe uri=”ctrlsys:

//IPADDR:PORT”/></eventmgr>

</commands>

...

IPADDR

 is the IP address and port number where the event messages should be sent.  It may be a different IP address than the control system which sent the request.   

PORT

 is the UDP port number.

Only one IP address / port event subscription is allowed.

For example, to have event messages sent from a SM3-PRO with MAC address 10-65-A3-03-FF-FF to a control system at IP address 192.168.0.127 listening 
on port 1726:

 

<?xml version=”1.0” ?><device class=”sm3” id=”1065a304ffff”><command><eventmgr><subscribe 

 uri=”ctrlsys://192.168.0.127:1726”/></eventmgr></command></device>

The unsubscribe command follows the same format

 

...<commands><eventmgr><unsubscribe uri=”ctrlsys://IPADDR:PORT”/></eventmgr></commands>

...

General Event Element Structure

All event messages are contained within an <event> element, which will contain a timestamp attribute, “time”, and an event ID attribute, “evtid”.  The time attribute is 
a UNIX timestamp, up to 10 decimal digit characters and represents the number of seconds that have passed since January 1st 1970 GMT.  The evtid attribute is the 
numeric ID value of the event message, starting from 0 after each device start-up.  

Event Messages:

Outlet State Change

An Outlet State Change event is posted when any of the outlet banks turn ON->OFF or OFF->ON. 

Element 

Tag: 

  <seq> 

Attribute:   None 
Content   

 

 

0 | 1 | 2   

 

 

0 = sequence done/finished/complete

        1 

turn 

on 

sequence 

initiated

        2 

turn 

off 

sequence 

initiated

Example:   <seq>0</seq> 

  Sequence 

has 

completed

Sequence Status

A Sequence Status event is posted when a power on or power off sequence is initiated or completed.

A subscriber ID, “subsid” is assigned to each event subscription and is included in every event message sent to the subscriber. 

A sample 

event 

message for outlet bank 2 switching ON:  

 

…<event time=”1234567890” evtid=”123” subsid=”1”><outlet id=”2”>1</outlet></event></device>

Event messages will be repeated until an acknowledgement message is sent back to SM3-PRO, or after a timeout period of approximately 20 minutes.  The acknowl-
edgement message syntax is:

 

…<command><eventmgr><ack evtid=”123” subsid=”1”></eventmgr></command></device>

Summary of Contents for SM3-PRO

Page 1: ...PDF provided by Conference Room AV Furman SM3 PRO 15A BlueBOLT Compact Power Conditioner 3 Outlet...

Page 2: ...SM3 PRO SYSTEM MANAGER ETHERNET 2 BANK 2 UNSAFE VOLTAGE WIRING FAULT BlueBOLT ACC 1 ACC 2 RESET Power Management with Remote Cloud based Control and Monitoring 15 Amp Capacity 3 Rear Panel Outlets in...

Page 3: ...ture Descriptions pg 1 Important Safety Instructions Front Panel Features Overview pg 2 Rear Panel Features Overview Bubble of Protection pg 3 BlueBOLT Setup Registration Trouble Shooting pg 4 OutletS...

Page 4: ...Protect or Disconnect Circuitry will disconnect your equipment in order to protect it The SM3 PRO will need to be repaired or replaced by Panamax if this occurs within the product s 3 year warranty S...

Page 5: ...ACC 1 ACC 2 RESET OUTLET 1 120V 60Hz GROUND BANK 1 BANK 2 OUTLET 2 OUTLET 3 12A 1 2 3 4 5 6 Color State Status OFF The wall outlet is properly wired RED The wall outlet is reversed wired or the ground...

Page 6: ...LAN HDMI AC LAN AC HDMI LAN Diagram 1 Diagram 2 Rear Panel Features Overview 3 ETHERNET 1 SM3 PRO SYSTEM MANAGER ETHERNET 2 UNSAFE VOLTAGE WIRING FAULT BlueBOLT ACC 1 ACC 2 OUTLET 1 120V 60Hz GROUND...

Page 7: ...cable and confirm the unit s breaker has not been tripped Q Is your Internet connection functioning Q Can you access a general web page Q Is your SM3 PRO connected to your internet router or modem A C...

Page 8: ...Off Delay When a Turn Off Sequence is initiated the outlet bank will turn OFF after the Turn Off Delay time The delay times are pre programmed but may be changed on the BlueBOLT web site or by issuing...

Page 9: ...______________ LAN 2 MAC ADDRESS __ __ __ __ __ __ __ __ __ __ __ __ CHALLENGE KEY __ __ __ __ __ __ __ __ __ __ __ __ Name Location of Installation ___________________________________________ _______...

Page 10: ...Snippet of the response to sendinfo query xml version 1 0 device class sm3 id 1065a30400 info time 1403729752 sernum 12345678 sernum fwver 1 0 1 fwver info device GENERAL All messages are encapsulated...

Page 11: ...t Command messages with the xid attribute expressed will return an acknowledgement enclosed in an ack element For example when the message xml version 1 0 device class sm3 id 1065a3040000 command xid...

Page 12: ...bank bank 0 outlet bank OFF 1 outlet bank ON tfilestate For Core Brands use only Query sendsettings Response settings Time stamp of the data provided in UNIX time time timestamp delay id bank Delay fo...

Page 13: ...onds 65536 seconds max Set Settings Example command set delay id 1 act 0 10 delay Set bank 1 for 10 second turn off delay delay id 1 act 1 1 delay Set bank 1 for 1 second turn on delay delay id 1 act...

Page 14: ...format commands eventmgr unsubscribe uri ctrlsys IPADDR PORT eventmgr commands General Event Element Structure All event messages are contained within an event element which will contain a timestamp...

Page 15: ...ngs Event section for details Example set delay id 1 act 2 12 delay Outlet bank 1 power cycle delay 12 sec set Settings Changed A Settings Changed event is posted when the device settings such as outl...

Page 16: ...sed in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equip...

Page 17: ...mined that you are entitled to compensation Panamax will at its election either pay you the present fair market value of the damaged equip ment or pay for the cost of the repair or send you replacemen...

Reviews: