5500 power cable does not

reach the wall outlet. Can I use an

extension cord to make it reach?

Yes, but you must use only Panamax extension

cords to keep your warranty valid. Ask for

Part

# GEC1410 

(10 feet long) or #P12X10NEMA5-

10 (premium grade).

____

The provided coax or telephone jumper

cables are not long enough to reach my

equipment. Can I use other cables?

Yes, any length cable of the same type meets the

warranty requirements.

____

The 4 Amp, Isolation Transformer circuit

breaker continually trips.  What is the

problem?

The four Isolation Transformer Outlets share the

500 VA Isolation Transformer for their power

source.  The connected equipment plugged into

the four outlets is drawing more than 4 Amps

collectively, causing the circuit breaker to trip.

These four outlets are designed specifically for

low-current, digital source components.  Check

to see if you have connected a high current

amplifier or subwoofer to the Isolation

Transformer Outlets.  If so, unplug the high cur-

rent components and plug them into the High

Current Outlet Bank.

____

The Isolation Transformer Outlets are not

switching ON or OFF with the MAX

®

5500.

How can I fix this?

These outlets may be set as either switched or

always-on outlets.  The 3-position, Isolated

Outlet Turn-Off Delay switch on the back panel

controls this.  Change the setting of this switch

from Always-On to a delayed setting.  This will

allow the Isolation Transformer Outlets to

become Switched Outlets.

____

The MAX

®

5500 is ON but the Voltmeter

and Ammeter are not lit up. What is the

problem?

Check the Meter Light Dimmer control to see if

the lighting is turned ON or OFF.  If the control

knob is turned OFF, turn it ON and continue

turning until you have reached the desired light

level.  If the control knob is turned ON and there

is no light, turn the knob to maximum.  If you

still have no light, call Panamax Customer

Service for help.

____

I connected the 5W Convenience Lamp

and the lamp will not work. What is the

problem?

1.

Check to see if  the  bulb is burned-out.

2.

Check to see if the MAX

®

5500 is in an unsafe

voltage condition by looking to see if the Unsafe

Voltage LED is lit.  If the LED is lit, then wait until

voltage is back to normal and the light will turn

back on.  If the LED is not lit, check to see if the

Lamp Dimmer control knob is turned ON and

turned up. 

3.

If the bulb is good, if the unsafe voltage LED

is OFF and the light control knob is turned on

and the light is still not on, call Panamax

Customer Service for help

.

____

The halogen light on the Convenience

Lamp is dead. What type of light do I

replace it with?

The halogen light must be replaced with a

12VDC, 5-Watt bulb or damage to lamp power

supply may occur. Use USHIO JC12V-5W/BA9S

or equivalent.

____

There is an audible buzz/hum coming

from my MAX

®

5500. What is the cause

of this and how do I make it go away?

This is the result of a DC Bias that is usually

introduced in your circuit by certain appliances-

most commonly lamps with High-Low dimmer

switches and some room heaters, which use

only half of the AC sine wave. These appliances

introduce a small DC bias placed on the AC sup-

ply. Some audio equipment- especially ampli-

fiers with toroidal power transformers- may react

unfavorably to this DC voltage, and buzz. The

MAX

®

5500 isolation transformer will remove

this waveform distortion and protect the loads

plugged into the isolated outlets. If the distortion

is bad, you may actually hear the MAX

®

5500

buzzing slightly as it works to correct the AC

power. The best way to stop the buzz is to find

the source of the disturbance (most likely a

quartz lamp) and plug it into a different branch

circuit. Panamax Technical Support will be glad

to help you if you have any questions about this.

FAQs

12

1690 Corporate Circle, Petaluma, CA 94954  •  www.panamax.com

Summary of Contents for M5500

Page 1: ...MAX 5500 ACRegenerator Owner s Manual 1690 Corporate Circle Petaluma CA 94954 www panamax com...

Page 2: ...at meets the power quality needs for each piece of equipment in your entertainment system This is truly a Firewall for Noise With power this clean you ll wonder how you ever used your system without i...

Page 3: ...n 9 AC Power Cord 9 AC Surge Protection 10 SurgeGate Plus Protection 10 Technical Specifications 11 Contacting Panamax 11 Frequently Asked Questions 12 TABLE OF CONTENTS 1 MAX 5500 ACRegenerator 1 RJ...

Page 4: ...the system specifically addresses the unique power requirements of current hungry components such as amplifiers and powered subwoofers These components can rapidly draw large amounts of current to rep...

Page 5: ...3 CONNECTION DIAGRAM Tri Power Filtration System USA Canada 800 472 5555 707 283 5900 www panamax com...

Page 6: ...ways On 10 and 30 seconds Satellite Coax Jacks Two pairs of gold plated F Connectors optimized for Satellite TV signal line protection Cable TV Coax Jacks Two pairs of gold plated F Connectors optimiz...

Page 7: ...to the receptacle When the knob is turned completely to the left the lamp is in its OFF state Turning the knob to the right will turn the light ON and increase the brightness In the event of an unsaf...

Page 8: ...ating that the wall outlet has a reversed line and neutral wire or there is no ground present This light will remain OFF if the wall outlet is properly wired Unsafe Voltage Red LED Under normal voltag...

Page 9: ...ed by using the isolation transformer to regenerate the AC current The power from a typical wall outlet is contaminated with electromagnetic EMI and radio frequency RFI interference noise picked up by...

Page 10: ...s jack has an electrically isolated switch built in If nothing is inserted into the input jack the voltage sense is bypassed and the MAX 5500 Switched Outlets button on the front panel has sole contro...

Page 11: ...olts to operate and utilize the frequency range of 950Mhz to 2 2Ghz The clamping level of the MAX 5500 s satellite protection circuitry is 27 volts just 3 volts above the maximum operating voltage The...

Page 12: ...owing tasks until line voltage returns to a safe level 1 Disconnects power to all connected equipment 2 Unsafe Voltage LED is activated and will blink once per second during the unsafe voltage conditi...

Page 13: ...Circuit YES AC Line Voltage 120VAC Max Current Rating 15A 1800 Watts Thermal Fuse YES Over Under Voltage Protection YES Over voltage shutoff threshold Response time 137 4 VAC 10 milliseconds Under vol...

Page 14: ...ht turn the knob to maximum If you still have no light call Panamax Customer Service for help ____ I connected the 5W Convenience Lamp and the lamp will not work What is the problem 1 Check to see if...

Reviews: