background image

Venting Through Closed Spaces

If the vent piping passes through a closed space, a minimum clearance of
8” (20 cm) when installed horizontally or 6” (15 cm) when installed
vertically should be maintained between the vent pipe and combustibles
and noncombustibles. Be sure to follow local codes and vent
manufacturer’s installation instructions.

For maintenance and inspection purposes, the following access panels
are required.

l

Two (2) inspection access panels large enough to allow access for
venting inspection. One (1) of these access panels should be close
to where the vent pipe enters the ceiling. The other access panel
should be near the vent termination.

l

A ventilation access panel with a 16 in

2

(103 cm

2

) opening should

be provided every 10 ft (3 m).

downward slope 

1/4" per foot 

Ceiling 

Vent Pipe 

Wall Thimble 

Board 

Inspection 

Fire 
Stop

Access Panel #1 

Inspection 

Access 

Panel #2  

Appliance Vent Adapter

The water heater must be installed
with a UL 1738 approved Category III
Stainless Steel appliance vent adapter.

Read the following instructions before
installation.

l

Test fit the adapter over the water heater
collar before proceeding. Adjust clamp as
needed.

l

With an alcohol wipe, clean inside surface
“A” of adapter and outside surface “B” of
heater collar.

l

Apply 1/4” (6 mm) wide bead of high
temperature silicone (500°F [260°C])
around outside of heater collar “B”.

l

Slide adapter end “A” down over heater
collar “B” as far as it will go.

l

Tighten the clamp around the collar.

l

Inspect the inside of the adapter to verify
that the collar and adapter are sealed. If
more sealant is required, apply sealant to a
flat tool, then spread around the collar edge
on inside of adapter.

l

Ensure that the clamp does not interfere
with the damper shaft.

NOTICE: 

Follow the appliance vent adapter

manufacturer’s instructions.

Appliance 
Vent Adapter

Water Heater

Exhaust

Flow

A

B

High Temp.
Sealant

Collar

Clamp

Draining the Condensate

Provision should be made to collect and
dispose of condensate from venting systems.

When a water heater is 

vented horizontally,

the vent pipe can have a DOWNWARD or
UPWARD slope towards the termination. If 
an UPWARD slope is used, a condensate trap
must be installed as close as practical to the
water heater in order to prevent condensate
from draining back into the water heater. See
Examples A and B on page 14 for
DOWNWARD and UPWARD slope for
horizontally vented water heaters. 

When a water heater is 

vented vertically,

an

UPWARD slope must always be used. A
condensate trap must be installed in the
horizontal section of the vent and as close 
as practical to the water heater in order to
prevent condensate from draining back into 
the water heater. See the diagram on page 15
showing UPWARD slope for vertically 
vented water heaters.

Always attach a drain hose to the drain fitting
and plumb the hose to a sanitary sewer drain.

A high temperature silicon tubing suitable for
use with acidic condensate and appropriate for
the temperature range should be used.

The drain tube is fashioned into a “pigtail” trap
and must be filled with water to prevent flue
gases from emitting into the building prior to
operating the appliance.

CAUTION: Condensate

must drain away from the
water heater and should
not be allowed to drain
back into any part of the
vent system.

WARNING: Failure to

provide a vent condensate
drain close to the appliance
could allow acidic flue gas
condensate to enter into
appliance flueways, causing
premature failure of the
appliance.

CAUTION: Condensate

is known to be acidic; refer
to local, state (provincial)
or federal codes for proper
handling and discharge
methods.

11

CAUTION: Ensure that the
appliance vent adapter is
securely attached to the
water heater collar. 

Summary of Contents for PH-16 FISN

Page 1: ...ater and two to the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater This manual also includes a parts list It is very important...

Page 2: ...THIS MANUAL FOR YOUR RECORDS Write the model and serial numbers here You can find them on a label on the appliance Staple sales slip or cancelled check here Proof of the original purchase date is nee...

Page 3: ...well as other flammable materials and liquids adhesives solvents paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combus...

Page 4: ...emote control and a dip switch adjustment Only qualified service personnel should perform this adjustment Only factory authorized remote control s should be used Notice When this water heater is suppl...

Page 5: ...P gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level l Before attempting to light the water heater make sure to loo...

Page 6: ...ATION READ ALL INSTRUCTIONS BEFORE USING WARNING For your safety the information in this manual must be followed to minimize the risk of fire or explosion electric shock or to prevent property damage...

Page 7: ...y result in severe burns death or property damage The water heater must be located so it is not subject to physical damage for example by moving vehicles area flooding etc l The water heater should be...

Page 8: ...dentally spilled l The water heater should be installed as close as practical to the vent termination to minimize vent length and the number of elbows required for venting l The water heater should be...

Page 9: ...ter heater warranty is voided when failure of the heater is due to operation in a corrosive atmosphere NOTICE The water heater should not be installed near an air supply containing halogenated hydroca...

Page 10: ...service Additional installation information for the Commonwealth of Massachusetts is located on the page 36 of this manual DANGER Failure to install the appliance vent adapter and properly vent the wa...

Page 11: ...he appliance vent adapter manufacturer s instructions Appliance Vent Adapter Water Heater Exhaust Flow A B High Temp Sealant Collar Clamp Draining the Condensate Provision should be made to collect an...

Page 12: ...1 foot 300 mm above opening 6 inches 15 cm for appliances 10 000 Btuh 3 kW 9 inches 23 cm for appliances 10 000 Btuh 3kW and 50 000 Btuh 15kW 12 inches 30 cm for appliances 50 000 Btuh 15kW K Clearanc...

Page 13: ...posed vent pipe of indoor water heaters outside of building Guard vent against accidental contact with people and pets Install outdoor water heater such that air inlet and flue outlet is above anticip...

Page 14: ...s Reinstall the decorative sheathing around the Wall Thimble This assembly may be painted to match the exterior decor l Attach a Paloma approved 3 7 6 cm screened 90 elbow termination to the female en...

Page 15: ...vent purchased from the manufacturer Chase Requires 6 15 cm Clearance to Combustibles Firestop Firestop Roof Jack Adjustable Roof Flashing Vent Adapter 3 8 cm Clearance Support Hanger Condensate Trap...

Page 16: ...th cold and hot water supply lines DO NOT cover the drain or pressure relief valve To ensure proper operation of the water heater the following water pressure guidelines should be followed l Operation...

Page 17: ...Installation of unions or flexible copper connections are recommended on the HOT and COLD water lines so that the water heater may disconnect easily for servicing if necessary Install a Check Valve be...

Page 18: ...codes govern the installation of relief valves If local codes require that a temperature and pressure relief valve should be installed the manufacturer recommends a type 40XL Watts T P relief valve or...

Page 19: ...use excessive force over 31 5 ft lbs 42 7 Nm in tightening the pipe particularly if teflon pipe compound is used as the unit may be damaged The inlet gas pressure to the water heater must not exceed 1...

Page 20: ...te controls can connect to the water heater Therefore a maximum of three controls can connect to the water heater No other manufacturer s controls are suitable for use with this water heater DO NOT at...

Page 21: ...e remote control over the base plate Ensure the projections in the base plate fit into the housings in the remote control l l Fix the control to the base plate at the bottom of the remote control usin...

Page 22: ...nnection when servicing controls Wiring errors can cause improper and dangerous operation Verify correct operation after servicing BK 8 R GR Y B O W BR WATER FLOW SENSOR OVER HEAT LIMITER BK GND GND T...

Page 23: ...codes or plumbing authority requirements may vary from the instructions or diagrams provided and take precedent over these instructions Vacuum Relief Valve Not Supplied If required install per local c...

Page 24: ...ket is to reduce the standby heat loss encountered with storage tank heaters This water heater does not store water making an insulation blanket unnecessary The manufacturer s warranty does not cover...

Page 25: ...pply q Gas type matches rating plate q Gas supply pressure is sufficient for the water heater q Gas line equipped with shut off valve union and sediment trap q Approved pipe joint compound used q Soap...

Page 26: ...s label 2 Turn off all electric power to the appliance 3 Do not attempt to light the burner by hand 4 Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the OFF position 5 Wait...

Page 27: ...alves are available for reducing point of use water temperature by mixing hot and cold water in branch water lines Contact a licensed plumber or the local plumbing authority for further information Se...

Page 28: ...otter water increases the risk of scald injury Always supervise young children or others who are incapacitated The water heater is equipped with a device that will shut off the gas supply to the burne...

Page 29: ...nd or cleaning ensure proper operation by turning on a hot water faucet Housekeeping Before performing Housekeeping tasks to this water heater turn the unit off and disconnect the power supply Vacuum...

Page 30: ...burner flame Blue flames should be seen when the main burner is firing See figure on page 34 for location of sight glass If any unusual burner operation is noted the water heater should be shut off u...

Page 31: ...eezing conditions even for a short period of time be sure to drain all water from the unit as instructed above Exposure to freezing conditions can occur from down draft of venting system or from insta...

Page 32: ...lfunctions if applicable l Check and replace if necessary Error code displayed on remote control l See instructions for Error Code and if required contact a dealer for service Not enough water demand...

Page 33: ...erial or vent configuration l Open the Gas shutoff valve fully l Contact gas utility company l Fill up LP Gas container or replace with a new cylinder of LP Gas l Bleed all air from gas lines l Ensure...

Page 34: ...t connectors or other safety devices Refer repairs to qualified service personnel WARNING For your safety DO NOT attempt to disassemble this unit for any reason Indoor Water Heater Gas Supply Unit Cov...

Page 35: ...bove then continue as listed below l Press the SW1 button on the left hand side of the PCB for more than 1 second The LED on the PCB starts illuminating continuously At the same time the display of th...

Page 36: ...time of completion of installation the owner shall have a period of thirty 30 days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbo...

Page 37: ...d to one 1 year from the Effective Date WARRANTY EXCLUSIONS This Limited Warranty will not cover a Service trips to your home to teach you how to install use or maintain this water heater or to bring...

Page 38: ...rts Paloma determines that a defect exists Paloma shall furnish replacement part s in full settlement of its warranty obligations Purchasers shall be required to return at purchasers expense the defec...

Page 39: ...This page was intentionally left blank...

Page 40: ...Paloma Industries Inc 2151 Eastman Avenue Oxnard CA 93030 PRINTED IN JAPAN 31 80171 00...

Reviews: