background image

Lutron Electronics Co., Inc.   

7200 Suter Road, Coopersburg, PA 18036-1299 U.S.A.

)

Lutron, Lutron, myRoom, and Palladiom are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US  

and/or other countries.

©2016–2019 Lutron Electronics Co., Inc.

Troubleshooting

If the thermostat displays “E” and a number, there is an issue with its functionality or configuration. Follow the table below for a possible solution.

Category

ID

Name

Description

Value

Default

Increment

Range

Primary 

Configuration

01

Function Type

0 = Operate with thermostat; 1 = Operate without the thermostat *; 2 = Not Configured

0 = Operate with 

thermostat

0–2

02

Temperature Sensor Type

0 = Remote return air sensor; 1 = Thermostat sensor. Set to 0 when Function Type = 1 

(operate without thermostat). 

1 = Thermostat 

sensor

0–1

03

Deadband

Inactive range above and below the Setpoint.

1 °F (0.55 °C)

0.1 °F (0.055 °C)

0.1 °F–10.0 °F  

(0.055 °C–5.5 °C)

04

ChangeOver Differential

Changeover temperature = Se Changeover diff Deadband. Used for 

switching from Heating to Cooling.

3 °F (1.70 °C)

0.1 °F (0.055 °C)

0.1 °F–10.0 °F  

(0.055 °C–5.5 °C)

Fan Control

05

Fan High Differential

Auto fan mode temperature difference in degrees to switch from medium to high fan speed.

1.5 °F (0.80 °C)

0.1 °F (0.055 °C)

0.1 °F–10.0 °F  

(0.055 °C–5.5 °C)

06

Minimum Fan On-Time

Minimum fan on-time for auto mode (minutes).

2 minutes

1 minute

0–99 minutes

07

Overrun Cool Fan Time

Minutes the fan runs after cooling stops in Auto Mode.

0 minutes

0.1 minutes

0–99.9 minutes

08

Overrun Heat Fan Time

Minutes the fan runs after heating stops in Auto mode.

0.1 minutes

0.1 minutes

0–99.9 minutes

09

Kick-Start Fan

0 = OFF; 1 = Set fan to high speed for 1 second when turning on.

0 = OFF

0–1

10

Fan Circulation Mode

Defines when fan circulation will run. 0 = Disabled; 1 = Enabled, fan will run periodically to circulate 

air; 2 = Use with return air sensor, fan will circulate air only when using a return air sensor.

2

0–2

13

Fan Circulation Off-Time

Maximum time for fan to stay off. If set to 0 and circulation is enabled, the fan will always run.

15 minutes

1 minute

0–99 minutes

14

Fan Circulation On-Time

Fan will turn on for fan on-time if the fan has stayed off for fan off-time.

5 minutes

1 minute

1–99 minutes

15

Fan Circulation Speed

Fan speed during fan circulation on-time. 1 = Low; 2 = Medium; 3 = High

1 = low

1–3

Operating Without the 

Thermostat 

Configuration

16

Temperature Setpoint when 

operating without the thermostat Standalone setpoint (°F)

72 °F (22 °C)

1 °F (0.55 °C)

50 °F–90 °F

(10 °C–32 °C)

17

Deadband when operating 

without the thermostat

Standalone deadband (°F)

2 °F (1.1 °C)

0.1 °F (0.055 °C)

0.1 °F–10.0 °F  

(0.055 °C–5.5 °C)

18

Temperature Operation Mode 

when operating without the 

thermostat

0 = OFF; 1 = Heat only; 2 = Cool only; 3 = Auto

3 = Auto

0–3

19

Fan Mode when operating 

without the thermostat

0 = OFF; 1 = Low; 2 = Medium; 3 = High; 4 = Auto

4 = Auto

0–4

20

Return Air Sensor Offset

Temperature offset for return air temperature sensor. This allows for compensation based on 

the installation location of the probe.

0 °F (0 °C)

0.1 °F (0.055 °C)

–5.0 °F–5.0 °F  

(–2.7 °C–2.7 °C)

Alarm Configuration

25

Freeze Protection (°F)

Freeze protection temperature for emergency heat

45 °F (7.2 °C)

1 °F (0.55 °C)

32 °F–50 °F 

(0 °C–10 °C)

26

Setpoint Alarm Timeout

Cannot reach setpoint alarm time threshold

0.5 hours

0.5 hours

0.5–99.5 hours

27

Setpoint Alarm Action

0 = Alarm and keep trying; 1 = Alarm and enter failsafe

0 = Keep trying

0–1

28

Humidity Setpoint Alarm Timeout Length of continuous dehumidification before raising an alarm that the humidity setpoint has 

not been achieved.

8 hours

0.5 hours

0.5–99.5 hours

Dehumidification 

Configuration

33

Enable Dehumidification

0 = Disabled; 1 = Enabled

0 = Disabled

0–1

34

Dehumidification Mode

1 = Over-cool only; 2 = Over-cool with heating (for 4-pipe). Dehumidification must be enabled 

to run.

1 = Over-cool only

1–2

35

Humidity Deadband

Inactive range around the humidity setpoint.

10% RH

1% RH

5–20%

36

Overcool Offset Temperature

Degrees below the setpoint deadband to continue cooling for dehumidification if humidity 

setpoint has not been reached.

2 °F (1.1 °C)

0.1 °F (0.055 °C)

0.1 °F–5.0 °F 

(0.055 °C–2.7 °C)

37

Dehumidification Setpoint

Relative humidity (RH) setpoint by dehumidification only.

50% RH

1% RH

0–100%

2-pipe Configuration 

(only applies for a 2-pipe 

system)

40

ChangeOver to Heat for Pipe 

Temperature

Pipe temperature that designates heating mode when using a 2-pipe system with a 

changeover sensor on the pipe.

82 °F (27.8 °C)

1 °F (0.55 °C)

75 °F–99 °F 

(23.8 °C–37.2 °C)

41

ChangeOver to Cool for Pipe 

Temperature

Pipe temperature that designates cooling mode when using a 2-pipe system with a 

changeover sensor on the pipe.

60 °F (15.5 °C)

1 °F (0.55 °C)

32 °F–70 °F 

(0 °C–21.1 °C)

42

Enable Purge Function

Turns the valve on periodically if left dormant to refresh pipe temperature;  

0 = Disabled; 1 = Enabled

1 = Enabled

0–1

43

Purge Valve On-Time

Number of minutes to leave the valve on during a purge; 0 = Disabled

2 minutes

1 minute

0–60 minutes

44

Purge Valve Off-Time

Number of hours to leave the valve off between purges; 0 = Disabled

2 hours

0.5 hours

0.5–99.5 hours

0–10 V

-

 Configuration 

(only available in 

SMC55x)

50

Proportional Fan Minimum 

The lowest percent output to apply for fan speed. This determines the low end-point of the 

fan being on. If at any time the fan output is 0% (off), the valves will also close at 0%. 

10%

1%

0–100%

51

Proportional Fan Low Speed

The output to apply when the manual fan-speed is set to Low.

20%

1%

0–100%

52

Proportional Fan Medium Speed The % output to apply when the manual fan-speed is set to medium.

60%

1%

0–100%

53

Proportional Fan High Speed 

The % output to apply when the manual fan-speed is set to high. This is also the fan 

maximum in auto mode.

100%

1%

0–100%

54

Minimum Valve Percent Open

The lowest % output to apply for the valve opening. This determines the low end-point of the 

straight-line curve for the valve opening.

10%

1%

0–100%

55

Valve Fully Open Differential

The temperature offset from deadband at which the valve is fully open (100% opening).

1 °F (0.55 °C)

0.1 °F (0.055 °C)

0.1 °F–10.0 °F 

(0.055 °C–5.5 °C)

Floating Point 3-Position 

Valve Control*

60

Enable Floating Point

0 = Disabled; 1 = Enabled (overrides basic valve configuration).

0 = Disabled 

0–1

61

Actuator Running Time

Actuator running time for floating point control.

150 seconds

1 second

1–999 seconds

Contact Closure Input 

(CCI) Support

64

CCI Type

0 = Disabled; 1 = Normally Open; 2 = Normally Closed

0 = Disabled

0–2

65

CCI Open Delay

Seconds the window contact sensor needs to be open before HVAC is disabled.

10 seconds

1 second

1–999 seconds

66

CCI Closed Delay

Seconds the window contact sensor needs to be closed before HVAC is enabled.

1 second

1 second

1–999 seconds

67

Open CCI Fan Mode

Fan mode setting when CCI is open. 0 = Off; 1 = Low; 2 = Medium; 3 = High; 4 = Auto;  

5 = Unaffected

0 = Off

0–5

Advanced Configuration Parameter Table

*

 

For floating point control, see Application Note #630 (P/N 048630) at www.lutron.com. Basic Configuration set for the valve type is overridden when selecting Floating Point.

† 

 Dehumidification supported in future versions.

‡ 

Available only in myRoom Prime systems with thermostat version 4.12 or later. Contact Lutron Customer Assistance before using this feature.

C. Advanced Configuration Parameters (optional)

 

Review the Advanced Configuration Parameters Table below. If any values need to be changed, enter Advanced Configuration Mode 
using the steps below.

 1.

 

Enter Advanced Configuration Mode:

  1a.

  If the thermostat has been powered for over 15 minutes, cycle power to the thermostat. Your previously saved settings are 

stored during power cycles.

  1b.

  Hold the °C | °F and   buttons for 3 seconds. Once the display begins to flash, release both buttons and hold only the   button 

for 3 seconds.

  1c.

  The thermostat will enter the Advanced Configuration Mode’s Parameter Menu (

1 2 3

), with “P”, “Set”, and 2 circles filled on 

the display.

 

2.

 

Select a Parameter to Modify:

  2a.

 Tap the 

}

 or 

{

 buttons to change parameter identification number.

  2b.

 Tap the 

u

 button to select the parameter.

  2c.

  The thermostat will enter the Parameter Value Selection Menu (

1 2 3

), with 3 circles filled on the display. 

 

3.

 

Set or View a Parameter Value:

  3a.

  While in the Parameter Value Selection Menu (

1 2 3

), tap the 

}

 or 

{

 buttons to change the desired value for the parameter.

  3b.

  Once the correct value is displayed, tap the 

u

 button to set this value. The 

Set

 segment will show and the display will return to 

the Parameter Menu 

1 2 3

.

  3c.

  If you do not want to set a new value, tap the   button to return to the Parameter Menu.

  3d.

 Follow the steps above to set all the parameters required for your system. 

  3e.

  When finished, hold the 

u

 button for 3 seconds. The display will flash and return to normal operation.

Tap 

to view 

parameter value.

 

Hold 3 seconds

 to 

save and exit 

configuration mode

Diagram 1:  Parameter Menu

Increase

Decrease

Hold °C | °F and    for 3 seconds,  

then   for 3 seconds to enter mode. 

Advanced Configuration Mode 

 

Parameter Menu 

 

 

 

 

 

Set

 

 

 

 

T p 

to view 

parameter value 

Hold 3 seconds

 

to save and exit  

C  F 

 

 

 

 

 

 

 

LUTRON

 

 

 

Hold °C | °F and  for 3 seconds, then  for 2 seconds to enter mode. 

1 2 3

Return to Parameter Menu 

without setting

Tap 

to set and return 

to Parameter Menu,

 

Hold 3 seconds

 to 

save and exit 

configuration mode

Diagram 2:  Parameter Value Selection

Increase

Decrease

Advanced Configuration Mode 

 

Parameter Value Selection 

 

 

 

 

 

 

Tap 

to set and 

return to 

Parameter Menu, 

Hold 3 seconds 

to 

save and exit 

mode  

Increment 

C  F 

 

Decrement 

 

 

Return to 

Parameter Menu 

without setting 

 

 

 

 

LUTRON

 

1 2 3

Symptom

Possible Cause

Solution

Display is blank

The thermostat does not have power.

Check the wiring to confirm that Common (Black) and V+ (Red) wires are connected to a 24–36 V

-

 power supply.

E0 shown on the display

The thermostat temperature sensor is not functioning properly.

Contact Customer Assistance.

E1 shown on the display

Wiring issue between the thermostat and the FCU controller or controller not powered.

Ensure that the FCU controller communication link is wired correctly and isolated from all other connections and 
that the controller is powered. If using a 3

rd

 party controller verify that it is wired correctly to the HVAC unit. 

The incorrect HVAC controller or modbus address was selected.

Enter into HVAC controller selection mode and select the correct HVAC controller and modbus address.

E2 shown on the display

Remote temperature sensor is malfunctioning or misconfigured.

Check the wiring between the sensor and the FCU controller and confirm configuration.

E3 shown on the display

Changeover sensor malfunctioning or misconfigured (applicable only for 2-pipe systems). Check the wiring between the sensor and the FCU controller and confirm configuration.

E4 shown on the display

QS link wiring issue or no temperature has been provided by the processor.

Contact Customer Assistance.

E5 shown on the display

Incorrect FCU controller or thermostat model.

Ensure that a myRoom thermostat is connected to a myRoom FCU controller.

System is not heating / cooling as expected The FCU controller or HVAC equipment may not have power.

Ensure that the FCU controller and HVAC equipment are powered and properly wired. Consult an HVAC 
professional if the issue persists.

Summary of Contents for QS Room Thermostat

Page 1: ...in the table to the below Only the supported options are displayed 3 Save parameter values and exit basic configuration mode Hold the ubutton for 3 seconds to save this configuration The display will flash then normal operation will begin 4 Adjust advanced configuration parameters optional See the Advanced SMC Controller Configuration Instructions on next page Re enter Configuration Mode optional ...

Page 2: ... to apply when the manual fan speed is set to medium 60 1 0 100 53 Proportional Fan High Speed The output to apply when the manual fan speed is set to high This is also the fan maximum in auto mode 100 1 0 100 54 Minimum Valve Percent Open The lowest output to apply for the valve opening This determines the low end point of the straight line curve for the valve opening 10 1 0 100 55 Valve Fully Op...

Page 3: ...tat 2 Après 15 minutes de cycle d alimentation de l unité maintenez les boutons C F et pendant 3 secondes 3 Relâchez les boutons et maintenez immédiatement 3a pour le Mode de sélection du contrôleur 3b C F pour le Mode de configuration de base 3c pour le Mode de configuration avancée Déterminer la version du micrologiciel facultatif seulement disponible avec thermostat de version 4 12 ou plus réce...

Page 4: ... bas 20 1 0 100 52 Vitesse moyenne proportionnelle du ventilateur La puissance en pourcentage à appliquer lorsque la vitesse du ventilateur manuelle est réglée sur moyen 60 1 0 100 53 Vitesse haute du ventilateur proportionnelle La puissance en pourcentage à appliquer lorsque la vitesse du ventilateur manuelle est réglée sur haut Il s agit aussi de la vitesse maximale du ventilateur en mode Auto 1...

Page 5: ...iguración básica Mantenga pulsado el botón u durante 3 segundos para guardar esta configuración La pantalla destellará y luego comenzará la operación normal 4 Ajuste los parámetros de configuración avanzada opcional Consulte las Instrucciones de configuración avanzadas del controlador SMC en la página siguiente Vuelva a ingresar al Modo de configuración opcional Si se necesitara algún cambio luego...

Page 6: ...onal del ventilador El de la salida a aplicar cuando la velocidad del ventilador manual esté configurada a Media 60 1 0 100 53 Velocidad alta proporcional del ventilador El de la salida a aplicar cuando la velocidad del ventilador manual esté configurada a Alta Este es también el máximo del ventilador en el modo Automático 100 1 0 100 54 Mínimo porcentaje de apertura de la válvula El menor de la s...

Page 7: ... Nur die unterstützten Optionen werden angezeigt 3 Parameterwerte speichern und Grundlegenden Konfigurationsmodus beenden Halten Sie u Taste 3 Sekunden lang gedrückt um diese Konfiguration zu speichern Die Anzeige blinkt und der Normalbetrieb wird wiederaufgenommen 4 Erweiterte Konfigurationsparameter anpassen optional Siehe erweiterte SMC Steuerungskonfigurationsanleitung auf der nächsten Seite A...

Page 8: ...ttlerer zu hoher Ventilatorgeschwindigkeit 1 5 F 0 80 C 0 1 F 0 055 C 0 1 F 10 0 F 0 055 C 5 5 C 06 Ventilator Mindest Einschaltzeit Ventilator Mindest Einschaltzeit für Auto Modus Minuten 2 Minuten 1 Minute 0 99 Minuten 07 Kühlungsventilator Überlaufzeit Laufzeit des Ventilators in Minuten nachdem die Kühlung im Automatikmodus stoppt 0 Minuten 0 1 Minuten 0 99 9 Minuten 08 Heizungsventilator Über...

Page 9: ...下表所示 仅显示支持的选项 3 保存参数值 然后退出基本配置模式 按住u按钮3秒钟以保存此配置 显示屏将闪烁 然后开始正常操作 4 调整高级配置参数 可选 有关高级SMC控制器配置说明 见在下一页 再次进入 配置模式 可选 如果配置完成后需要进行任何更改 则进行以下步骤 1 反复通断温控器电源 2 在单元重启15分钟内 按住 C F 和 按钮3秒钟 3 释放这两个按钮 然后立即按住 3a 进入 控制器选择模式 3b C F进入 基本配置模式 3c 进入 高级配置模式 确定固件版本 可选 仅4 12或更高版本温控器提供 1 要确定温控器的固件版本 请按住 和 按钮3秒钟 将显示温控器的固件版本 2 如果该温控器与SMC53 SMC55结合使用 则在完成第1步后10秒钟内 2a 按下向 按钮以获取FCU控制器固件版本 2b 按下 C F按钮 以获取FCU控制器的基本配置号 参数值 Set 按下...

Page 10: ...0 禁用 2分钟 1分钟 0 60分钟 44 清洗阀关闭时间 清洗之间保持阀关闭的小时数 0 禁用 2小时 0 5小时 0 5 99 5小时 0 10 V 配置 仅用于SMC55x 50 比例风机最小值 适用于风机速度的最低百分比输出 这决定了开启风机的低端点 如果在任何时间风机输出为0 关闭 这些阀也将在0 时关闭 10 1 0 100 51 比例风机低速 当手动风机速度设置为低时适用的输出 20 1 0 100 52 比例风机中速 当手动风机速度设置为中时适用的 输出 60 1 0 100 53 比例风机高速 当手动风机速度设置为高时适用的 输出 这也是自动模式下的风扇最大速度 100 1 0 100 54 阀百分比打开最小值 适用于阀打开的最低 输出 这确定了阀打开的直线曲线的低端点 10 1 0 100 55 阀完全打开差分 阀完全打开 100 打开 时距死区的温度偏差 1 F 0...

Page 11: ...i dei parametri e uscire dalla modalità di configurazione base Tenere premuto per 3 secondi il pulsante uper memorizzare questa configurazione Il display lampeggia e poi inizia il normale funzionamento 4 Regolazione dei parametri di configurazione avanzata facoltativo Vedere le istruzioni per la configurazione avanzata del controllore SMC nella pagina successiva Ritornare alla modalità di configur...

Page 12: ... Sovrafunzionamento tempo di raffrescamento ventilatore Per quanti minuti il ventilatore continua a funzionare dopo che il raffrescamento si arresta in modalità automatica 0 minuti 0 1 minuti 0 99 9 minuti 08 Sovrafunzionamento tempo di riscaldamento ventilatore Per quanti minuti il ventilatore continua a funzionare dopo che il riscaldamento si arresta in modalità automatica 0 1 minuti 0 1 minuti ...

Page 13: ...salvar esta configuração O mostrador piscará e a operação normal terá início 4 Ajuste os parâmetros de configuração avançados opcional Veja as instruções de configuração avançada do controlador SMC na próxima página Entre novamente no Modo de configuração opcional Se for necessário fazer alguma alteração após a conclusão da configuração siga as etapas abaixo 1 Conclua um ciclo de energia do termos...

Page 14: ...uando a circulação do ventilador funcionará 0 desabilitado 1 habilitado o ventilador funcionará periodicamente para circular o ar 2 use com sensor de ar de retorno o ventilador circulará o ar somente quando o sensor estiver presente 2 0 2 13 Tempo em que a circulação do ventilador está desligada Tempo máximo para o ventilador permanecer desligado Se estiver configurado para 0 e a circulação estive...

Page 15: ... parameterwaarden op en sluit de basisconfiguratiemodus af Houd de knop ugedurende 3 seconden ingedrukt om de configuratie op te slaan Het display knippert en de normale bedrijfsmodus wordt actief 4 Geavanceerde configuratieparameters aanpassen optioneel Raadpleeg de instructies voor geavanceerde configuratie van de SMC regelaar op de volgende pagina Configuratiemodus opnieuw inschakelen optioneel...

Page 16: ...1 F 10 0 F 0 055 C 5 5 C 06 Minimale aan tijd ventilator Minimale tijdsduur dat de ventilator aan staat voor automatische modus minuten 2 minuten 1 minuut 0 99 minuten 07 Overlooptijd koelventilator Aantal minuten dat de ventilator draait nadat het koelen is gestopt in auto modus 0 minuten 0 1 minuten 0 99 9 minuten 08 Overlooptijd verwarmingsventilator Aantal minuten dat de ventilator draait nada...

Reviews: