Operation and Maintenance Documentation

ACR 1000-1500-2000 E Air curtains with electric heater

• 

Lack of voltage on surface of electric coil

•  Significantly lower coil temperature in comparison to old type of electric heaters (e.g. heat

-

ing wires, spirals)

• 

Large heat exchange surface (surface of contact of the heat exchanger with heated air)

•  Fully automatic heat control depending on air flow

• 

Complete elimination of the risk of system overheating due to self regulating heating mod-

ules (heat capacity automatically reduces when air flow goes down)

• 

Low energy consumption

ACR E

 series (with electric heater) are based on a new type of PTC electric coils J It is a modern and safe solution, additional advan-

tages of PTC heaters

ACR 1500W

Inlet/outlet water temperature

50/30

60/40

70/50

80/60

90/70

Inlet air temperature

0

5

10 15 20

0

5

10 15 20

0

5

10 15 20

0

5

10 15 20

0

5

10 15 20

III. max. air flow – 3600 m

3

/h

Heat output [kW]

13,5 11,7 10,0 8,2 6,4 17,4 15,6 13,8 12,1 10,3 21,3 19,5 17,7 15,9 14,1 25,1 23,3 21,6 19,7 18,0 29,0 27,2 25,4 23,6 21,8

Outlet air temperature [°C]

11,9 15,4 18,9 22,5 26,0 15,1 18,6 22,1 25,7 29,2 18,3 21,8 25,3 28,9 32,4 21,5 25,0 28,6 32,0 35,6 24,7 28,2 31,7 35,2 38,7

Water flow [m

3

/h]

0,5 0,4 0,3 0,2 0,2 0,6 0,6 0,5 0,4 0,3 0,8 0,7 0,7 0,6 0,5 1,0 0,9 0,8 0,7 0,7 1,2 1,1 1,0 0,9 0,8

Pressure drop [kPa]

4,0 3,0 2,0 1,0 1,0 8,0 6,0 4,0 3,0 2,0 12,0 10,0 8,0 6,0 5,0 17,0 14,0 12,0 10,0 8,0 22,0 19,0 17,0 14,0 12,0

II. max. air flow – 3000 m

3

/h

Heat output [kW]

12,5 10,9 9,3 7,8 6,1 16,1 14,4 12,8 11,2 9,6 19,6 17,9 16,3 14,7 13,1 23,1 21,4 19,8 18,2 16,6 26,5 24,9 23,3 21,6 20,0

Outlet air temperature [°C]

12,7 16,1 19,5 22,9 26,3 16,2 19,6 23,0 26,4 29,8 19,7 23,1 26,5 29,9 33,2 23,2 26,5 29,9 33,3 36,7 26,6 30,0 33,4 36,7 40,1

Water flow [m

3

/h]

0,4 0,4 0,3 0,2 0,2 0,6 0,5 0,4 0,4 0,3 0,7 0,7 0,6 0,5 0,5 0,9 0,8 0,8 0,7 0,7 1,1 1,0 0,9 0,8 0,8

Pressure drop [kPa]

4,0 3,0 2,0 1,0 0,6 6,0 5,0 4,0 3,0 2,0 10,0 8,0 6,0 5,0 4,0 14,0 12,0 10,0 8,0 7,0 18,0 16,0 14,0 12,0 10,0

I. max. air flow – 2200 m

3

/h

Heat output [kW]

11,0 9,7 8,4 7,0 5,7 14,0 12,6 11,3 9,9 8,6 16,9 15,5 14,2 12,9 11,5 19,8 18,4 17,1 15,7 14,4 22,7 21,3 20,0 18,6 17,3

Outlet air temperature [°C]

14,2 17,4 20,6 23,7 26,9 18,2 21,3 24,5 27,7 30,9 22,1 25,3 28,5 31,6 34,8 26,1 29,2 32,4 35,6 38,7 30,0 33,1 36,3 39,5 42,6

Water flow [m

3

/h]

0,4 0,3 0,2 0,2 0,1 0,5 0,4 0,4 0,3 0,3 0,6 0,6 0,5 0,4 0,4 0,8 0,7 0,6 0,6 0,5 0,9 0,8 0,8 0,7 0,6

Pressure drop [kPa]

3,0 2,0 1,0 1,0 0,6 5,0 4,0 3,0 2,0 1,0 7,0 6,0 5,0 4,0 3,0 10,0 8,0 7,0 6,0 5,0 12,0 11,0 10,0 8,0 7,0

ACR 2000W

Inlet/outlet water temperature

50/30

60/40

70/50

80/60

90/70

Inlet air temperature

0

5

10 15 20

0

5

10 15 20

0

5

10 15 20

0

5

10 15 20

0

5

10 15 20

III. max. air flow – 4800 m

3

/h

Heat output [kW]

19,5 17,2 14,8 12,4 9,9 24,7 22,3 19,9 17,5 15,1 29,8 27,4 25,0 22,6 20,2 34,9 32,5 30,1 27,7 25,3 40,0 37,6 35,2 32,8 30,4

Outlet air temperature [°C]

12,5 16,0 19,5 23,0 26,5 15,7 19,2 22,7 26,2 29,7 18,9 22,4 25,9 29,4 32,9 22,1 25,6 29,1 32,6 36,1 25,2 28,7 32,2 35,7 39,2

Water flow [m

3

/h]

0,7 0,6 0,5 0,4 0,2 0,9 0,8 0,7 0,6 0,5 1,1 1,0 0,9 0,8 0,7 1,4 1,2 1,1 1,0 0,9 1,6 1,5 1,4 1,3 1,2

Pressure drop [kPa]

9,0 6,0 4,0 3,0 1,0 15,0 12,0 9,0 7,0 5,0 22,0 19,0 15,0 12,0 9,0 32,0 27,0 23,0 19,0 15,0 42,0 37,0 32,0 27,0 23,0

II. max. air flow – 4000 m

3

/h

Heat output [kW]

18,2 16,0 13,8 11,7 9,4 22,8 20,7 18,5 16,3 14,1 27,5 25,3 23,1 20,9 18,8 32,1 29,9 27,7 25,5 23,4 36,6 34,5 32,3 30,1 27,9

Outlet air temperature [°C]

13,3 16,7 20,1 23,5 26,8 16,8 20,2 23,6 27,0 30,3 20,3 23,7 27,0 30,4 33,8 23,7 27,1 30,5 33,8 37,2 27,1 30,5 33,9 37,3 40,6

Water flow [m

3

/h]

0,6 0,5 0,4 0,3 0,2 0,8 0,7 0,6 0,5 0,4 1,0 0,9 0,8 0,7 0,6 1,2 1,1 1,0 0,9 0,8 1,4 1,3 1,2 1,1 1,0

Pressure drop [kPa]

7,0 5,0 4,0 2,0 1,0 12,0 10,0 7,0 5,0 4,0 19,0 16,0 13,0 10,0 8,0 26,0 22,0 19,0 16,0 13,0 35,0 30,0 26,0 22,0 19,0

I. max. air flow – 2900 m

3

/h

Heat output [kW]

15,9 14,1 12,3 10,5 8,7 18,8 18,0 16,2 14,4 12,6 23,6 21,8 20,0 18,2 16,4 27,4 25,6 23,8 22,0 20,2 31,2 29,4 27,6 25,8 24,0

Outlet air temperature [°C]

15,0 18,1 21,3 24,4 27,5 18,9 22,1 25,2 28,4 31,5 22,9 26,0 29,2 32,3 35,5 26,8 29,9 33,1 36,2 39,4 30,7 33,8 37,0 40,1 43,3

Water flow [m

3

/h]

0,5 0,4 0,4 0,3 0,2 0,7 0,6 0,5 0,4 0,4 0,8 0,8 0,7 0,6 0,5 1,0 0,9 0,9 0,8 0,7 1,2 1,1 1,0 1,0 0,9

Pressure drop [kPa]

5,0 4,0 3,0 2,0 1,0 9,0 7,0 5,0 4,0 3,0 13,0 11,0 9,0 7,0 5,0 18,0 16,0 13,0 11,0 9,0 24,0 21,0 18,0 16,0 13,0

ACR 1000E

ACR 1500E

ACR 2000E

Inlet air temperature [°C]

0

5

10 15 20

0

5

10 15 20

0

5

10 15 20

Heat output [kW]

7,0 7,0 7,0 7,0 7,0 11,0 11,0 11,0 11,0 11,0 14,0 14,0 14,0 14,0 14,0

Outlet air temperature [°C]

12 18 22 27 32 13 18 23 28 33 14 19 24 29 34

Summary of Contents for ACR 1000W

Page 1: ...EN Operation and Maintenance Documentation www pakole com ACR_008_039_011_221021_V004_en Type ACR 1000W ACR 1000E ACR 1000C ACR 1500W ACR 1500E ACR 1500C ACR 2000W ACR 2000E ACR 2000C AIR CURTAINS...

Page 2: ...CE 3 3 BASIC TECHNICAL PARAMETERS 4 4 HEAT OUTPUT RANGES 4 5 Installation 6 6 CONTROL PANEL 10 7 ACR DOOR SWITCH 10 8 DIAGRAMS OF ELECTRICAL CONNECTIONS 11 9 DIMENSIONS OF THE ACR 1000 1500 2000 W E C...

Page 3: ...reduce the airflow in order to ensure the fire safety and if sparks or a damaged supply cable noticed discontinue the operation immediately Electricity network to which the curtain is connected shoul...

Page 4: ...r W 37 80 160 51 106 220 75 162 320 Electric heater consumption V Hz A Weight with water without water kg 15 18 5 25 Sound level dB A 45 50 60 46 50 61 47 50 61 Protection Class IP IP21 IP21 IP21 ACR...

Page 5: ...3 24 5 27 7 30 9 22 1 25 3 28 5 31 6 34 8 26 1 29 2 32 4 35 6 38 7 30 0 33 1 36 3 39 5 42 6 Water flow m3 h 0 4 0 3 0 2 0 2 0 1 0 5 0 4 0 4 0 3 0 3 0 6 0 6 0 5 0 4 0 4 0 8 0 7 0 6 0 6 0 5 0 9 0 8 0 8...

Page 6: ...ol panel With larger door openings it is possible to mount more curtains of the same type one by one to create an uninterrupted air flow The curtain is permanently mounted in either a horizontal or ve...

Page 7: ...the wall in a horizontal position using 2 mounting brackets to the horizontal system In the brackets there are 9mm holes for M8 screws In the EPP housing drill holes 12 13mm in front of existing hole...

Page 8: ...g drill holes 12 13mm in front of existing holes in the steel in take grille The exact location is indicated by special tags on the EPP housing and the figure below Then insert the spacer sleeves into...

Page 9: ...er use a vent which is located on the exchanger collector on the engine side ATTENTION It is necessary to ensure that the unit is properly leveled When it is mounted in a position other than vertical...

Page 10: ...L not supported function in this settings the device does not work To install the control panel unscrew the screw remove the front cover and panel board fix the panel to the wall and replace the panel...

Page 11: ...g The set does not include power cord or main switch Diagram of connecting one ACR 1000 1500 2000 W water heater and C without heater to the COMFORT panel Power supply 230V 50Hz Security system B4 Cro...

Page 12: ...B25 Control Panel COMFORT 3 speed fan control with thermostat OMY 5x 1 0mm In the MASTER curtain between the L1 NC terminal replace the factory made fuse C 3 15 with C 6 3 400V 50Hz power supply wire...

Page 13: ...control circuit between terminal 3 on Comfort Panel and Terminal 2 in the ACR curtain The on off switch itself should be installed in a place suitable for the curtain user Warning The Comfort Panel t...

Page 14: ...vated PP OPERATION Digital signal 1 potential free contact closed information about the operation of the curtain reed relay on door opened Digital signal 0 potential free contact opened Reed relay off...

Page 15: ...n the COMFORT panel in ON position READY FOR OPERATION 1 signal activated PP OPERATION Digital signal 1 potential free contact closed information about the operation of the curtain reed relay on door...

Page 16: ...16 ACR air curtains Operation and Maintenance Documentation 9 DIMENSIONS OF THE ACR 1000 1500 2000 W E C CURTAINS...

Page 17: ...f and the heat input disconnected Only suitably qualified staff well acquainted with the safety regulations concerning handling with an electrical device must be employed when the device is being inst...

Page 18: ...n suitable part and mending which is done by not authorized retailer or service station The regular maintenance is the owner s responsibility The manufacturer does not assume the responsibility in cas...

Page 19: ......

Page 20: ...PAKOLE TRADE Kft H 8000 Sz kesfeh rv r B rg ndi t 8 10 www pakole com mail pakole hu Tel 36 22 316 484 www pakole com...

Reviews: