Electrode-specific configuration – combined chlorine (CTE 1)
For configuration of total chlorine electrodes, press the buttons
Set value
[13] +
Select function
. This is indicated via the text
“
SEt CCL
” and flashing of the “
Off
” and “
Auto
” LEDs.
To exit configuration, press the
Cal.
button [0] or scroll past the last line.
The following can be modified in the channel-specific configuration – Combined chlorine:
Line
Text
Setting
Explanation
-01
doS
Selection of dosing outlet and function.
oFF
No dosing.
ono*
On/Off dosing.
Pdo
Pulse width dosing.
FrE
Frequency dosing.
Cur
Dosing via current output.
-02
P
0.10–2.00 (0.20*) ppm
P-band. (Pdo, FrE, Cur)
-03
I
000–100 (000*)
minutes
I-time, 000 = no I-regulation. (Pdo, FrE, Cur)
-04
d
000–100 (000*)
seconds
D-time, 000 = no D-regulation. (Pdo, FrE, Cur)
-05
dF
010–180 (100*)
strokes/minute
Max. frequency dosing. (FrE)
-06
Pdo
005–015 (010*)
minutes
Pulse width during pulse width dosing. (Pdo)
-07
Ldt
000–060 (000*)
minutes
Long dosing time alarm, 0 = no function.
-08
oFt
000–600 (000*)
seconds
Min. time OFF for relay, 0 = no function. (ono)
-09
ont
000–600 (000*)
seconds
Min. time ON for relay, 0 = no function. (ono)
-10
Cur
- - 0 / - - 4 (- - 4*)
Current output, selection of range 0–20mA / 4–20mA.
-11
C-L
0.00–9.99 (0.00*) ppm
Current output, value for 0/4mA.
-12
C-H
0.00–9.99 (5.00*) ppm
Current output, value for 20mA.
-13
AHd
005–600 (005*) seconds
Delay time for high alarm.
-14
ALd
005–600 (005*) seconds
Delay time for low alarm.
* Factory default