Using EC Max to replace Constant Torque ECM with 24vac speed taps.

• Install motor in HVAC system using a belly band mount. 

 •     Select the voltage plug that matches the voltage rating of the replaced motor. 

Install the voltage plug. Connect the harness plugs to the motor. 

White Voltage Plug

115vac Systems

Yellow Voltage Plug

230vac Systems

• HIGH VOLTAGE POWER CONNECTIONS

 

 Note: The Black and White HIGH VOLTAGE POWER wires are taped together and 

flagged for identification. 

  Connect the Black HIGH VOLTAGE POWER wire to a L1 line voltage power 

source that is continuously powered when the unit disconnect is closed.

  Connect the White HIGH VOLTAGE POWER wire to a Neutral (115vac    

systems) or L2 (230vac systems) that is continuously powered when the 

unit disconnect is closed.

  

Note: These wires can be connected to the same terminals the Constant Torque ECM 

used for line voltage inputs.

• HIGH VOLTAGE SIGNAL CONNECTION

  

Note: The Black and Red HIGH VOLTAGE SIGNAL wires are taped together and flagged 

for identification. 

  Connect the Red (HV2) HIGH VOLTAGE SIGNAL wire to a L1 line voltage 

power source that is continuously powered when the unit disconnect is 

closed. This wire can be connected to the same L1 source as the Black 

HIGH VOLTAGE POWER wire in the previous step.

 Insulate the Black (HV1) HIGH VOLTAGE SIGNAL wire with a wire nut. 

  

Note: This wire can be connected to the same terminal as the L1 HIGH VOLTAGE 

POWER connection in the previous step.

• LOW VOLTAGE SIGNAL CONNECTIONS

 

 Note: All LOW VOLTAGE SIGNAL wires are taped together and flagged for              

identification.

  Connect the Blue LOW VOLTAGE SIGNAL wire to the (C) terminal used by 

the motor that was removed or to the thermostat common terminal or to 

the common side of the 24vac transformer.

  Connect the speed desired for HEAT to the 24vac HEAT terminal and the 

speed desired for COOL (including A/C or Heat Pump systems) to the 

24vac COOL Terminal used by the motor that was removed.

  If the system has a 24vac Continuous Fan terminal connect any unused 

speed to this terminal if desired.

• NOTE: 

  After completing all connections, the technician should operate the system in all 

demand modes measuring airflow using industry best practices. To adjust the 

airflow, change the speed selection connected to the appropriate demand terminal. 

Summary of Contents for Ec Max

Page 1: ...Electronically Commutated Motor Wiring Manual R 0 G 105 B 62 00693e GREEN SPECS R 0 G 0 B 0 000000 BLACK SPECS FONT Arial Bold...

Page 2: ...packardonline com 800 334 1769 2 Table of Contents Safety Considerations 3 Application Guide 4 5 6 7 8 Operational Characteristics 9 10 11 12 Diagnostics Maintenance Warranty 13 Specifications 14...

Page 3: ...applying power to this motor Use of the wires provided in this kit is recommended Should additional wires be needed use equivalent size wire gauge and rated insulation Improper installation adjustment...

Page 4: ...In this manual there are two sets of instructions One for replacing PSC motors and one for replacing Constant Torque ECM Please make sure to use the correct instructions for the motor you are replaci...

Page 5: ...nuous Fan if applicable that were previously connected to the PSC motor Use the supplied jumper wires and terminals or wire nut all together Insulate the Red HV2 HIGH VOLTAGE SIGNAL wire with a wire n...

Page 6: ...packardonline com 800 334 1769 6 Using EC Max to replace PSC Permanent Split Capacitor induction motors...

Page 7: ...ed HV2 HIGH VOLTAGE SIGNAL wire to a L1 line voltage power source that is continuously powered when the unit disconnect is closed This wire can be connected to the same L1 source as the Black HIGH VOL...

Page 8: ...packardonline com 800 334 1769 8 Using EC Max to replace Constant Torque ECM...

Page 9: ...itself When the Red wire is energized the LOW VOLTAGE SIGNAL wires provide both the ON OFF command for the motor and determine the output level speed The LOW VOLTAGE SIGNAL wires provide the speed sel...

Page 10: ...nent Split Capacitor induction motors Example connection using the optional Y adapter when replacing PSC motors Using EC Max to replace Constant Torque ECM Example connection of one speed to multiple...

Page 11: ...s life It will never perform this function again If this is not the correct direction it can be reversed Changing the rotation of the motor after it has selected a rotation using the process above is...

Page 12: ...69 12 Wiring diagram for changing the rotation of the motor Using EC Max to replace PSC Permanent Split Capacitor induction motors Wiring diagram for changing the rotation of the motor Using EC Max to...

Page 13: ...purpose Buyer acknowledges that it alone has determined that the goods purchased will suitably meet the requirements of their intended use In no event will Packard be liable for consequential incident...

Page 14: ...ED HI HI Rotation CW or CCW automatically configured Bearing Ball Ambient Rating 40 C Enclosure Open Air Over OAO Frame size and dimensions NEMA 48 Frame 5 6 diameter see diagram below for DIM A B 1 3...

Page 15: ...packardonline com 800 334 1769 15...

Page 16: ...e Headquarters and Main Distribution Center 2700 Barrett Lakes Blvd NW Suite 100 Kennesaw GA 30144 Distribution Centers 2570 N Shadeland Ave Suite 103 Indianapolis IN 46219 6151 W Erie St Chandler AZ...

Reviews: