background image

300913-24 

SUPER-SD1 7

22"

12"

18"

30"

25"

11"

11"

20"

16"

26"

14"

15"

5"

10"

16"

18"

28"

4"

4"

8"

28"

18"

16"

8"

22"

8"

Minimum

Clearance to 

Combustibles

Procedure:

CAUTION: THE STRUCTURAL INTEGRITY OF THE 
MOBILE HOME FLOOR, WALL AND CEILING/ROOF 
MUST BE MAINTAINED.

Note: See "Combustion Air" section on page 10.
1.  Position stove and fl oor protection with hole for combus-

tion air in accordance with the clearances as stated 
on the label and in Figure #1.

2.  Mark the position for the hole in the ceiling and roof 

by using a string and plumb-bob.

3.  Check that the intended location will not interfere with 

fl oor joists, ceiling joists or rafters before proceeding 
further.

4.  Cut a hole in the ceiling and roof to suit the chimney 

system and frame in the sides. The chimney support 
is mounted to the framing.

5.  Assemble chimney sections so the fi nished length 

is resting on the support and protruding through the 
roof. Avoid having joints between ceiling and roof. 

 

Install radiation shield. Assemble fl ashing and storm 
collar and be sure to maintain the vapour barrier at 
this point. (Seal securely.) Attach rain cap and check 
fl ashing for leaks.

6.  Install connector as per manufacturer's instructions.
7.  Attach stove to fl ooring using two 1/4" x  2" or longer 

lag screws.

Mobile Home 
Installation

Warning:

 Under no circumstances is this heater to be 

installed in a makeshift or "temporary" manner. It may be 
fi red only after the following conditions have been met.

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE 

SERVING ANOTHER APPLIANCE.

DO NOT INSTALL IN A SLEEPING ROOM.

- Outside air supply must be used for Mobile Home instal-

lations see Figure #2, Page 8.

- The services of a competent or certifi ed installer, (certifi ed 
by the Wood Energy Technical Training program (WETT) 
- in Canada, Hearth Education Foundation (HEARTH) - in 
U.S.A.,) are strongly recommended.

Clearances

This heater must be installed with listed double-wall con-
nector and compatible chimney system listed on page 7.
Clearances to combustible surfaces and materials are 
shown below in Figure #1 and Figure #1.
Clearances may be reduced with various heat insulating 
materials. Consult local fi re codes and authorities for 
approval.

NOTE:

 Longer chimney lengths and different pitch 

fl ashings may be used. All other parts listed must be 
installed (see Figure #2, Page 8). Install all components 
to the connector or chimney manufacturer's installation 
requirements. Consult your chimney supplier for instal-
lation advice.

FIG. #1

Double Wall Connector - Residential

Single Wall Connector - Residential

Alcove:  Min. Height  7 1/2'
 

Max. Depth  4'

Double Wall Connector - Mobile Home

Summary of Contents for SUPER 27

Page 1: ...tioninstructions Contact local building or fire officials about restrictions and installation inspection requirements in your area TESTED and LISTED to CAN ULC S627 AND UL 1482 Meets the Environmental...

Page 2: ...ntenance 3 Maintenance Checks 4 Creosote 5 Formation and Need for Removal 5 Chimney Fires 5 In Case of a Chimney Fire 5 Avoiding a Chimney Fire 5 Assembly 6 Crate Removal 6 Optional Ash Cleanout Syste...

Page 3: ...maintained in good condition Periodically inspect seals and replace if necessary Follow instructions included in the DR31 WDGKIT kit obtainable from your nearest Pacific Energy dealer 5 DOORGLASS Dono...

Page 4: ...he Chimney System Top baffle board blanket Baffle Top heat shield and mounting bolt Baffle Gasket Brick Rails Manifold Blower The blower should be cleaned out a minimum every six months by using a vac...

Page 5: ...t be lived with Regular inspection and clean ing is the solution The use of dry seasoned wood and ample combustion air will help to minimize the buildup Chimney Fires The result of excessive creosote...

Page 6: ...to bottom pallet 4 Place stove body carefully on its back 5 Using two 3 4 wrench remove 1 x 1 2 bolts and save for later use 6 Remove pallet retaining brackets from stove bottom Optional Ash Cleanout...

Page 7: ...o flooring using two 1 4 x 2 or longer lag screws Mobile Home Installation Warning Under no circumstances is this heater to be installed in a makeshift or temporary manner It may be fired only after t...

Page 8: ...Minimum 7 2 1m Ceiling Height Attachment to floor for mobile homes Non combustible floor protector 48 1219 mm 3 914 mm Minimum Hooded vent or 90 elbow turned The chimney may incor porate an offset To...

Page 9: ...ve performance Chimney flue exit is to be 3 feet 1 m above roof and two feet 0 6 m above highest projection within 10 feet 3 m The installation must meet all local codes Do not connect this unit to a...

Page 10: ...llation requires the unit to be secured to the structure to prevent dislodging of the air duct To draw outside air from behind the stove an outside air adaptor may be required see Optional Blower sect...

Page 11: ...for the first 2 3 times it is very important that the room be well ventilated Open all windows and doors Smoke and fumes caused by the curing process may cause discomfort to some individuals Lighting...

Page 12: ...ry replace with gasket 139 5availablefromyourPacificEnergydealer Re install baffle assembly in reverse order The two side pieces of insulation must be tight against the siderails Restarting After Exte...

Page 13: ...ill al low the fan to turn on as the stove heats up to operating temperature It will also shut the blower off after the fire has gone out and the unit cooled to below a useful heat output range Manual...

Page 14: ...latch Excessive Creosote Buildup See 1 2 3 above Low Heat Output 1 Wood is wet Use dry wood 2 Fire too small Build a larger fire 3 Draft too low Chimney plugged or restricted inspect and clean Won t B...

Page 15: ...ant Nickel CAST 31RSNI 10 Door Handle Assembly WODC 4147C 11 Boost Manifold 4105 12 Firebrick Set BRIC SSERA 13a Brick Rail Left Right SSER RAILSET 14 Replacement Baffle Kit SSER DBAKIT 15 Baffle Pin...

Page 16: ...kel CAST 31NI Door Casting Radiant Nickel CAST 31RSNI 12 Door Handle Assembly WODC 4147C 13 Boost Manifold 4105 14 Firebrick Set BRIC SSERA 15a Brick Rail Left Right SSER RAILSET 16 Replacement Baffle...

Page 17: ...anding the basic functions of this design Traditionalwoodstoveshadabasiccombustion systemwhichallowedaconsiderableamountof heat energy to escape up the chimney as un burned gases and particulates smok...

Page 18: ...ts back 5 Using a 3 4 wrench remove 1 x 1 2 bolts and save for later use 6 Remove pallet retaining brackets from stove bottom Pedestal Kit 1 With the unit on its back and the removable cover facing up...

Page 19: ...either A B C as shown below if you are installing the optional ash cleanout system or 1 full brick in place of A B if you are not installing the ash cleanout system Next install the side firebricks 4...

Page 20: ...20 SUPER SD1 300913 24...

Page 21: ...300913 24 SUPER SD1 21...

Page 22: ...22 SUPER SD1 300913 24...

Page 23: ...07 INSTALLEZ ET UTILISEZ SELON LES INSTRUCTIONS D INSTALLATION ET D OP RATION FOURNI AVEC L APPAREIL CONTACTEZ LES OFFICIELS DE LA CONSTRUCTION OU DE SERVICE D INCENDIE POUR DES INFORMATIONS QUANT AUX...

Page 24: ...PACIFIC ENERGY FIREPLACE PRODUCTS LTD 2975 Allenby Rd Duncan B C V9L 6V8 Phone 250 748 1184 Web site http www pacificenergy net Printed in Canada...

Reviews: