210513-24 VISTA
INSERT-D
9
Blower
The Insert comes equipped with a variable speed circulating
air blower. The blower system is thermostatically controlled
for automatic operation, as well manually with a convenient
bypass switch.
Blower Operation
Automatic:
To operate the blower automatically, push the
rocker switch to the “0” or OFF position and set the fan speed
control to a desired setting.
This will allow the blower to turn on automatically once the
Insert has come up to operating temperature. It will also shut
the blower off after the fi re has gone out and the appliance
cooled to below a useful heat output range. On and Off times
will vary with installation and location of appliance.
Manual:
To manually operate the blower, push the rocker
switch to the “1” or ON position and set the fan speed control
to a desired setting. This will bypass the temperature switch
and allow full control of the blower.
Suggested settings:
- Combustion air control setting of "L" (low), operate blower
speed control on “Low”.
- Combustion air control greater than "L" (low), operate
blower speed control at desired setting.
Electrical Supply
Circulating air blower electrical rating: 115V, 60 Hz, 80 Watts.
For your protection against shock hazard, use only a properly
grounded outlet that will accept a three-pronged plug. Do not
cut or remove the grounding prong.
Consult local codes or in the absence of local codes, with the
current CSA C22.1 Canadian Electrical Code and in the USA
with the National Electrical Code, ANSI/NFPA 70 (latest edition).
Combustion Air
Consult local building codes regarding combustion air supply.
Intake or combustion air can be supplied to the Insert in one
of two ways:
1) Outside air supply: Remove cover from ash clean out in
existing fi replace. Place a rodent screen in place of the
cover. Install the Insert as described in the "Installation"
section, making sure not to cover the opening of the air
inlet. When installation is complete, seal surround to fi re-
place and anywhere else air may enter. This will ensure
combustion air is drawn from outside the house and into
the 7" x 2" intake at the lower rear of the appliance.
2) Room air supply: Remove the circular knockouts from
both sides of the unit casing prior to installation (Fig. #12).
Install the Insert as described in the "Installation" section.
The Insert will now draw its air from the room through the
front.
Fig. # 12
Fig. # 13
L2 (black)
G (green)
L1 (white)
Speed
Control
Blower
Thermo
Switch
By-pass
Rocker Switch
Remove knockouts on
both sides
Summary of Contents for PACIFIC VISTA INSERT
Page 18: ...18 VISTA INSERT D 210513 24 ...