
This appliance must be installed with a listed 6"(150mm) chimney system approved under the following stan-
dards:
CAN-ULC S629(IN CANADA) OR UL 103HT(IN U.S.).
MAINTAIN CLEARANCES TO COMBUSTIBLES AS SPECIFIED IN THE CHIMNEY MANUFACTURERS
INSTALLATION INSTRUCTIONS. YOU MUST FOLLOW THE CHIMNEY MANUFACTURER'S
INSTALLATION INSTRUCTIONS FOR INSTALLATION OF ALL CHIMNEY COMPONENTS.
USE APPROPRIATE SUPPORTS, CAPS, FLASHING AND SHIELDS IN ACCORDANCE WITH THE
CHIMNEY MANUFACTURERS INSTALLATION INSTRUCTIONS.
CAUTION: THE STRUCTURAL INTEGRITY OF THE FLOOR, WALL AND CEILING/ROOF MUST BE
MAINTAINED.
NOTE: FOR ALL CHIMNEYS, YOU MUST USE THE MANUFACTURER'S FIREPLACE ANCHOR PLATE. -
Some brands of Anchor Plate including ICC, do not sit flush with the top of the Fireplace and will require the
installation of an Anchor Plate spacer. Part #FP30.7757. Ensure the Chimney Achor plate is fully engaged
with the Fireplace's Flue Collar when using the Anchor Plate
Spacer.
NOTE: The FP25 must be installed so the outlet of the
chimney system is a minimum 15ft (4.6m) in height as
measured from the base of the unit, up to a maximum
height of 35' (10.7m). The chimney must be supported on
lengths over 20' (6.1m).
NOTE:
Install all components to the chimney manufacturer's
installation requirements. Consult your chimney supplier for
installation advice.
1. After locating the desired location and framing in the
fireplace, use a plumb bob to line up the holes with the
Flue Collar. Cut and frame square holes in all floors,
ceilings, and roof that the chimney will pass through.
Mount the firestops and radiation shields to the framing
as per instructions.
WARNING: A radiation shield/firestop must be used for
each floor/wall the chimney passes through.
2. Maintain a minimum 2"(51mm) clearance between the
chimney and any combustible materials. Do not fill the
space with insulation or any other combustible material.
Install the insulation shields as required by code and all
pieces necessary to prevent contact with combustible
materials whenever passing through floors, ceilings or
attic spaces.
3. Install the pipe manufacturer's fireplace anchor/base
plate by inserting it into the flue collar on the fireplace.
We recommend sealing the joint with stove cement.
Secure the anchor plate with stainless steel screws.
Chimney Installation
Anchor
Plate
Listed
Chimney and
Accesories
Maintain
38 3/4” [985mm]
Minimum distance
from the top of the
unit to the ceiling.
Non-Combustible
Ember Protection
Minimum distance
from the base of the
unit to the ceiling is
7’ [2.13m]
Insulation Shield
Firestop
Figure 10: FP25LE Basic installation.
18
FP25 LE 040523-36
100003890