Maximum exhaust gas temperature hysteresis [Fh20]

– this parameter describes

how much exhaust gas temperature should drop in relation to maximum temperature

for the controller to stop [Hot ] alarm and resume normal work.

6.7. Fuel shortage testing.

If central heating installation is equipped with exhaust gas temperature sensor

(

[Fc 1]

), then fuel shortage testing starts when exhaust gas temperature falls below

temperature set with additional thermostat knob. If there is no exhaust gas

temperature sensor (

[Fc 0]

), then fuel shortage testing starts when boiler water

temperature falls below value of

[L 65]

. If temperature tested during fuel shortage

testing stays below threshold for specified time, the controller will stop regulation

process and will show

[FUEL]

message on the display. This alarm can be erased with

STOP button.

Fuel shortage testing time during boiler start [Fd60]

– time set with this parameter

is used when testing fuel shortage during boiler start. Boiler is considered starting from

the time when the controller is switched from STOP mode to WORK mode and ends

when boiler temperature reaches minimum temperature (set with

[L 65]

parameter).

Setting

[Fd60]

parameter to „--” disables fuel shortage checking during boiler start.

Fuel shortage testing time in work mode [Fb30]

– time set with this parameter is

used when testing fuel shortage after boiler has started. Setting this parameter to „--”

disables fuel shortage checking in WORK mode.

6.8. Additional output.

Additional output work mode [Ar 0]

- the controller is equipped with a multipurpose

output that can work in one of following modes:

-

[Ar 0] mode

- output may control oil or gas boiler if such boiler exists in the

heating circuit. After switching the controller on with the main power switch, the

additional boiler is turned off and it turnes on again when there is no fuel in the solid

fuel boiler. This function is useful in heating systems where the solid fuel boiler is used

to cut heating costs. After erasing no fuel alarm by pressing STOP button, the

additional boiler is again turned off and the controller works again.

-

[Ar 1] mode

- output may control additional alarm signaling system. Boiler

temperature sensor malfunction, overheating or no fuel alarm will turn on the

additional alarm.

-

[Ar 2] mode

- output may control boiler emergency cooling system (e.g. pump).

In this mode the additional output is turned on in case of boiler overheating or boiler

temperature sensor error alarm.

-

[Ar 3] mode

- output may control devices working together with blow-in fan.

CAUTION.

Equipment should be connected to additional output using UM-1module.

Connection schemes are shown on picture 3.

Summary of Contents for RK-2001AT2

Page 1: ...OPERATION MANUAL SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER RK 2001AT2 Version AC22...

Page 2: ...r starts in HEATING UP mode This mode turns off influence of exhaust gas thermostat on the fan and central heating pump HEATING UP is active until exhaust gas temperature achieves temperature set with...

Page 3: ...shows diagram of electrical connection of the device WARNING Before plugging the device to the power source check if it is proprerly grounded and if the screws of the connector are properly screwed CA...

Page 4: ...on stops the fan for example allowing to add fuel to the boiler If the controller isn t in service mode the display shows water temperature of the boiler and the last sign on the display defines mode...

Page 5: ...splays current measured room or exhaust gas temperature 6 Setting up the parameters service mode Holding OK button for more than 3 seconds causes change to service mode where you can view and change p...

Page 6: ...ng pump turn off delay 1 99 1min 2 L 65 Minimum boiler temperature 60 65 1 C 65 H 90 Maximum boiler temperature 80 95 1 C 90 h 5 Boiler temperature hysteresis 1 10 1 C 5 A105 Boiler overheating temper...

Page 7: ...meter value in range from 0 to 10 means time in minutes of the smooth fan speed increase from 40 to value of for smooth boiler start Fan work time n 5 time of turning the fan on for a while to remove...

Page 8: ...ion Central heating pump turn off delay Pd 2 central heating pump stopping too early can cause temperature rise in the boiler and cause its overheating This parameter allows setting central heating pu...

Page 9: ...described above When contacts are open the controller will keep minimum boiler temperature Attention When external thermostat is connected in place of room temperature sensor the temperature set with...

Page 10: ...ing boiler start Fuel shortage testing time in work mode Fb30 time set with this parameter is used when testing fuel shortage after boiler has started Setting this parameter to disables fuel shortage...

Page 11: ...are working correctly After detection of fault it stops the pressure fan turns on the circulating pump and shows proper error message on the display In case of failure please turn off the controller p...

Page 12: ...urement range 9 109 C 1 C Boiler temperature adjustment range 30 90 C 1 C Programmable boiler overheating protection 90 99 C 1 C Hardware boiler overheating protection 95 C 1 C Circulating pump launch...

Page 13: ...13 Picture 2 RK 2001AT2 connection scheme Picture 3 UM 1 module connection scheme...

Page 14: ...controller work mode Pc Central heating pump pause time Pd 2 Central heating pump turn off delay L 65 Minimum boiler temperature H 90 Maximum boiler temperature h 5 Boiler temperature hysteresis A105...

Page 15: ......

Page 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Reviews: