4. OUTLETS

5. TROUBLESHOOTING

AC Appliances

Check the total rating of the appliance to be connected and ensure 

the rating of the appliance(s) does not exceed the rating of the 

generator.

1.  Start the generator and ensure 

the AC power indicator lights up. 

Allow the engine to stabilise before 

connecting appliances.

2.  Check that the appliance 

and the AC power switch are 

switched off.

3.  Plug the appliance into 

either of the AC sockets.

4.  Flip the AC power switch 

to the on position and then 

you can start using the 

equipment.

Note:

 If the connected appliance does not operate, refer to the 

Overload Indicator (RED)

’ and ‘

Inrush Current Overload

’ 

sections for troubleshooting.

USB Output

The generator has 2 USB outlets that supply 1.0A and 2.1A 

respectively. These are always on once the generator is started. 

Connect the device to be 

charged/powered via a USB 

cable (not supplied) to the USB 

port.

Note: 

The USB outlets provides 

power only, it does not 

provide any communication 

capabilities. A suitable USB 

cable must be used (not included).

Maintenance

Refer to the Maintenance Manual for maintenance instructions. 

The instructions should be followed to ensure optimum operation. 

2000W

PETROL INVERTER GENERATOR

4 STROKE 119CC ENGINE

2000W

INVERTER

TECHNOLOGY

2x

AC SOCKET 1

USB PORTS

AC SOCKET 2

OVERLOAD

AC OUTPUT

AC

IF OVERLOADED

RESTART ENGINE TO RESET

AC POWER

I

0

I

0

I

0

240V

1

240V

2

FUEL ECONOMY

ENGINE POWER

AUTOMATIC ENGINE SHUT OFF

REFILL MOTOR OIL

LOW OIL

OFF

ON

OFF

ON

OFF

ON

LOW OIL

2000W

PETROL INVERTER GENERATOR

4 STROKE 119CC ENGINE

2000W

INVERTER

TECHNOLOGY

2x

AC SOCKET 1

USB PORTS

AC SOCKET 2

OVERLOAD

AC OUTPUT

AC

IF OVERLOADED

RESTART ENGINE TO RESET

AC POWER

0

I

0

I

0

I

240V

1

240V

2

FUEL ECONOMY

ENGINE POWER

AUTOMATIC ENGINE SHUT OFF

REFILL MOTOR OIL

LOW OIL

OFF

ON

OFF

ON

OFF

ON

LOW OIL

2000W

PETROL INVERTER GENERATOR

4 STROKE 119CC ENGINE

2000W

INVERTER

TECHNOLOGY

AC SOCKET 1

AC SOCKET 2

OVERLOAD

AC OUTPUT

AC

IF OVERLOADED

RESTART ENGINE TO RESET

AC POWER

I

0

0

I

0

I

240V

1

240V

2

FUEL ECONOMY

ENGINE POWER

AUTOMATIC ENGINE SHUT OFF

REFILL MOTOR OIL

LOW OIL

OFF

ON

OFF

ON

OFF

ON

LOW OIL

1.0A

USB PORTS

2.1A

2000W

PETROL INVERTER GENERATOR

4 STROKE 119CC ENGINE

2000W

INVERTER

TECHNOLOGY

2x

AC SOCKET 1

USB PORTS

AC SOCKET 2

OVERLOAD

AC OUTPUT

AC

IF OVERLOADED

RESTART ENGINE TO RESET

AC POWER

I

0

0

I

I

0

240V

1

240V

2

FUEL ECONOMY

ENGINE POWER

AUTOMATIC ENGINE SHUT OFF

REFILL MOTOR OIL

LOW OIL

OFF

ON

OFF

ON

OFF

ON

LOW OIL

WARNING! 

BEFORE CONNECTING, INSPECT THE 

APPLIANCE CABLES. DO NOT USE THE APPLIANCE IF 

THERE ARE SIGNS OF FRAYING AND/OR DAMAGE.

WARNING! 

NEVER ADD MORE LOAD THAN THE 

GENERATOR CAPACITY. TAKE CARE TO CONSIDER 

SURGE LOADS IN GENERATOR CAPACITY.

WARNING! 

DO NOT USE THE OUTLET IF THE COVERS 

ARE BROKEN.

Problem

Possible Cause Solution

Engine  

•  will not start,

•  shuts down 

after starting 

or

•  starts but 

runs rough 

Choke is in off 

position.

Move choke to on position.

No fuel.

Add unleaded 91 RON petrol 

to fuel tank.

Engine switch is 

in the off position. Set engine switch to on.

Oil is low.

Check oil level and fill if 

necessary.

Spark plug 

connector is 

not properly 

connected.

Check and reattach 

connector if necessary.

Spark plug is 

faulty.

Replace spark plug.

Fuel is stale/old, 

or there is water 

in the fuel.

Drain system of all fuel and 

refill with fresh unleaded 91 

RON petrol.

Engine is flooded. Wait 5 minutes before 

restarting engine.

Engine stored 

without treating 

or draining fuel. 

Bad fuel is used.

Drain system of all fuel and 

refill with fresh unleaded 91 

RON petrol.

Air filter is dirty.

Check air filter. Clean if 

necessary.

Fuel filter is dirty. Check fuel filter. Clean if 

necessary.

Engine lacks 

power

Engine stored 

without treating 

or draining fuel. 

Bad fuel is used.

Drain system of all fuel and 

refill with fresh unleaded 91 

RON petrol.

Air filter is dirty.

Check air filter. Clean if 

necessary.

No power

Device plugged 

in is faulty.

Check device for damage, 

try plugging in a different 

device.

Generator is 

overloaded.

Refer to overload indicator 

section.

Poor connection 

or defective 

cable.

Check for damage and 

replace if necessary.

Summary of Contents for IGP-2018

Page 1: ...LICY OR PROCEDURE OZITO Australia New Zealand Head Office 25 Fox Drive Dandenong South Victoria Australia 3175 ozito com au Inverter Generator 0321 1 YEAR REPLACEMENT WARRANTY Your product is guarante...

Page 2: ...evel before each use and top up as necessary Refer to maintenance schedule for oil replacement information 2000W PETROL INVERTER GENERATOR 4 STROKE 119CC ENGINE 2000W INVERTER TECHNOLOGY 2x AC SOCKET...

Page 3: ...Add fuel to the tank 91 RON Unleaded Petrol Do not overfill the fuel tank check the fuel gauge on the fuel tank Do not use ethanol blended fuels Fuel tank capacity is 10L 4 After refuelling make sure...

Page 4: ...engine power switch to the on position 3 Adjust the choke lever to suit the conditions COLD START If the weather is cold push the choke all the way right to the ON position WARM START If the weather...

Page 5: ...ILL MOTOR OIL LOW OIL OFF ON OFF ON OFF ON LOW OIL Starting Watts aka Surge Watts You may find that even though the appliance you wish to connect to the generator is below the rated power the generato...

Page 6: ...VERLOADED RESTART ENGINE TO RESET AC POWER I 0 0 I 0 I 240V 1 240V 2 FUEL ECONOMY ENGINE POWER AUTOMATIC ENGINE SHUT OFF REFILL MOTOR OIL LOW OIL OFF ON OFF ON OFF ON LOW OIL 1 0A USB PORTS 2 1A 2000W...

Page 7: ...l on A wrench or a key left attached to a rotating part of the power tool may result in personal injury e Do not overreach Keep proper footing and balance at all times This enables better control of t...

Page 8: ...only be passed on with these instructions Do not use in rain wet or damp environment this may lead to electrocution Always keep the generator appliances and power cords dry The electrical continuity o...

Page 9: ...GENERATOR 4 STROKE 119CC ENGINE 2000W INVERTER TECHNOLOGY 2x I 0 I 0 I 0 240V 1 240V 2 AC SOCKET 1 USB PORTS AC SOCKET 2 FUEL ECONOMY ENGINE POWER OVERLOAD AC OUTPUT AC IF OVERLOADED RESTART ENGINE T...

Page 10: ...SOCKET 2 FUEL ECONOMY ENGINE POWER OVERLOAD AC OUTPUT AC IF OVERLOADED RESTART ENGINE TO RESET AUTOMATIC ENGINE SHUT OFF REFILL MOTOR OIL LOW OIL OFF ON OFF ON OFF ON LOW OIL AC POWER 2 KNOW YOUR PROD...

Page 11: ...OR 1 Frame Carry Handles 2 Recoil Starter 3 Economy Mode Switch 4 Status Indicator Lights 5 Fuel Cap 6 AC Power Socket 7 Engine Power Switch 8 USB Ports 9 Grounding Terminal 10 Oil Drain Bolt 11 AC Po...

Page 12: ...xamine Every 2 years If necessary please change 3 WARNING SHUT OFF THE GENERATOR DISCONNECT ANY APPLIANCES CABLES BEFORE PERFORMING ANY MAINTENANCE PLACE GENERATOR ON A LEVEL SURFACE AND REMOVE SPARK...

Page 13: ...HOT ENGINE LUBRICANT CAN RESULT IS SERIOUS BURNS 1 Use a spanner not supplied to remove the oil drain screw 2 Place a suitable container underneath the oil drain hole tilt the generator to collect th...

Page 14: ...ng for a long period of time or if a lot of oil is in the engine Wipe up the excess oil after each use and after stopping the generator WARNING DO NOT USE PETROL OR LOW FLASHPOINT SOLVENTS FOR CLEANIN...

Page 15: ...k the spark arrester for damage If damaged replace with replacement parts specifically designed for this unit 4 Re install the spark arrester Tighten the bolt to secure the spark arrester WARNING DO N...

Page 16: ...d 2 Remove the spark plug using the spark plug wrench supplied by turning it anti clockwise 3 Clean the electrode with a metal brush and remove any carbon build up or replace the spark plug Set the el...

Page 17: ...e nut using an M14 spanner not supplied whilst holding on to the fuel tap 3 Unscrew filter by hand and carefully clean with carburettor cleaner 4 Ensure the filter is dry before reattaching it to the...

Page 18: ...generator in a vehicle If the generator is left in an enclosed vehicle for many hours high temperatures inside the vehicle could cause fuel to vaporize resulting in a possible explosion Do not operate...

Page 19: ...start the engine and operate it in the idle position until all remaining fuel is gone and the engine stops automatically 2 Allow the generator to cool completely 3 Discharge the oil as described in t...

Page 20: ...unqualified persons Store fuel in an approved container designed to hold fuel Store container in secure location to prevent use by others Inadequate ventilation for generator Materials placed against...

Page 21: ...ll ventilated area Make sure hands are dry before touching unit Placing generator on or against highly conductive surface such as a steel walkway or metal roof Accidental leakage of electrical current...

Page 22: ...uel fires Keep children or others away from the generator at all times Operating generator while suspended Generator will not operate properly and will cause damage to the generator and could cause se...

Page 23: ...ct against damage to vehicle from leaks Remove generator from vehicle immediately upon arrival at your destination Risks From Lifting Hazard What could happen How to prevent it Lifting a very heavy ob...

Page 24: ......

Reviews: