background image

 

 

 

3.

 

SAFETY REQUIREMENTS 

 

Carefully read and follow safety requirements provided below before installing and while operating 
the Unit: 

 

Do not discard the Installation and operation manual, keep it for future reference. 

 

The Unit should be installed and operated in compliance with this Installation and operation 
manual, following the requirements of effective legislation and standards. 

 

When connecting the Unit to mains supply, grounding must be installed in compliance with 
requirements of effective legislation and standards. 

 

To  prevent  accidents  and  potential  damage  to  the  Unit  it  should  be  installed,  connected, 
maintained and repaired only by qualified technician. Never attempt to do this by yourself! 

 

Turn off the Unit by using Control panel and  wait for fans to stop completely before replacing 
air filters. 

 

Turn off the Unit by using Control panel, wait for fans to stop completely and disconnect the 
Unit from mains supply before performing any maintenance. 

 

Disconnect  the  Unit  from  mains  supply  before  disconnecting  or  reconnecting  the  control 
panel. 

 

Before  connecting  the  Unit  make  sure  that  no  items  will  get  sucked  into  the  its  air  intake 
openings! 

 

The Unit is  not intended to  be  used  by  persons (including children) with reduced physical, 
sensory or mental capabilities, unless they have been instructed to use the Unit and under 
constant supervision of person held responsible for their safety. 

 

Children may only use the Unit under adult supervision. 

 

Only  original  supplementary  parts  and  consumables,  certified  by  manufacturer  should  be 
used. 

 

The Unit package (cardboard, plastic, foam polystyrene) can pose hazard to children. Dispose 
or recycle the package elements! 

 

Disused Unit should be disposed in accordance with requirements of legislation on handling 
of waste electrical and electronic equipment. 

 

IT IS PROHIBITED

 to operate the Unit with damaged mains supply cable! Switch off the power 

circuit-breaker to disconnect mains supply and contact a qualified technician or manufacturer 
service centre immediately upon noticing such damage. 

 

IT  IS  PROHIBITED

  to  attempt  the  repair  of  the  damaged  Unit  or  its  part,  to  open  its 

maintenance and service hatch! Contact a qualified technician or manufacturer service centre. 

 

IT IS PROHIBITED

 to operate the Unit while construction works are still in progress to remove 

dust or excess moisture. Fine dust of building materials, used in construction, can irreversibly 
change  characteristics  of  the  heat  exchanger  or  cause  damage  to  sensitive  electronic 
components. Failure of the Unit caused by such operation will void the warranty. 

 

 

 

Summary of Contents for X-Air C200

Page 1: ...Rev 2 3 2021 04 INSTALLATION AND OPERATION MANUAL Heat Recovery Unit OXYGEN X Air C200...

Page 2: ...1...

Page 3: ...t functions 19 8 4 Control board electrical wiring diagram 20 8 5 Description of control board contacts 21 9 OPERATION OF THE UNIT 22 9 1 WiFi controller 22 9 1 1 Downloading the app 22 9 1 2 WiFi con...

Page 4: ...of packages matches with the consignment documentation Upon noticing any non conformity or damage of the package tears dents or compressed box detached or reattached packaging tape inform the courier...

Page 5: ...l panel 10m connection cable included or WiFi adapter 1 pc Fastening elements L shaped horizontal installation bracket 4 pcs Bolt type M5 8 mm 8 pcs Spring washer type M5 8 pcs Condensate drain nozzle...

Page 6: ...used by persons including children with reduced physical sensory or mental capabilities unless they have been instructed to use the Unit and under constant supervision of person held responsible for t...

Page 7: ...014 ES 1254 2014 ES 2017 1369 EN 13141 7 2010 2010 30 EU labelling and standard product information of the consumption of energy and other resources by energy related products ES 1254 2014 2011 65 EU...

Page 8: ...f heat recovery 81 h Maximum flow rate m3 h 191 i Electric power input of the fan drive including W 106 j Sound power level LWA 49 k Reference flow rate m3 s 0 039 l Reference pressure difference Pa 5...

Page 9: ...El consumption W 100 100 191 96 150 177 94 200 154 93 250 130 90 300 106 88 350 81 84 400 54 80 450 16 79 70 50 136 44 75 122 44 100 108 43 125 92 42 150 77 40 175 60 39 200 46 38 225 16 38 50 25 100...

Page 10: ...38 5 Exhaust 28 9 39 7 42 40 7 38 5 28 6 16 46 6 70 Suppply 39 51 1 51 8 51 2 49 9 43 8 30 4 57 3 Extract 21 5 45 2 44 5 36 6 33 2 22 5 14 2 48 4 Outside 22 44 6 42 8 36 1 33 1 21 7 13 7 47 3 Exhaust...

Page 11: ...ions and weight Figure 1 Unit dimensions Body dimensions and weight Length mm Width mm Height mm Weight kg OXYGEN X Air C200 1015 537 272 25 OXYGEN X Air C200 left side version OXYGEN X Air C200 right...

Page 12: ...to humidity level indoors Disabling of supply or exhaust air stream Filtration G4 EN 779 2012 COARSE 65 ISO 16890 exhaust air filtering only G4 Carbon EN 779 2012 EPM2 5 60 ISO 16890 retains average s...

Page 13: ...maintenance and service hatch looking downwards L shape fastening brackets provided should be used to fasten Unit to the ceiling Use ceiling pins or locking sleeves not included depending on installa...

Page 14: ...d exhaust ducts Make sure that openings in the outside wall are installed lower than corresponding ducts of the Unit The air intake opening in the outside wall should be protected against precipitatio...

Page 15: ...installing the Unit ensure enough space for its maintenance Suspended ceiling in the room should be installed at least 30 mm from the lowest point of the Unit housing refer to section 7 2 Installation...

Page 16: ...the Unit Mechanical damage will void the warranty The necessary incline of the condensate drain pipe should be ensured during the installation at least 2 incline should be ensured in the horizontal p...

Page 17: ...y balanced System has to be balanced according to ventilation system installation project Balance the supply and exhaust air flows by adjusting values for Fan1 and Fan2 in the operating parameters set...

Page 18: ...ilure of the control panel or the Unit due to improper connection will void the warranty 8 1 Connecting electric circuit WARNING To prevent accidents and potential damage to the Unit it can only be co...

Page 19: ...ght from the floor for convenient access Lay the control panel connection cable supplied from the Unit location to the control panel location before finishing decoration works The maximum permissible...

Page 20: ...ital contacts of RJ45 function connector Figure 9 Contacts of functions connector IMPORTANT Only passive jumpers or electric relays should be used to activate the function IMPORTANT If the Unit is bei...

Page 21: ...ntrol board electrical wiring diagram Figure 11 Control board electrical wiring diagram IMPORTANT Make sure that the Unit is disconnected from mains supply before connecting or disconnecting system co...

Page 22: ...tract air temperature humidity sensor AI1 DI2 function Away GND AI0 DI3 function CO2 sensor 24V Not used DI1 DI1 function Boost GND DI0 DI0 function Fire alarm GND Tach1 Exhaust fan tacho signal GND T...

Page 23: ...t is powered Failure of the Unit or WiFi controller caused by improper connection will void the warranty 9 1 1 Downloading the app Download the OXYGEN WiFi app for your smartphone or tablet from the A...

Page 24: ...r 2 minutes If You fail to connect while it is active broadcasting will stop Slightly press and release immediately the hidden button through the small hole on WiFi controller body with thin screwdriv...

Page 25: ...using browser Safari Chrome or similar by entering 192 168 4 1 in the address field Make sure that your device smartphone or tablet is connected to OXYGEN_xxxxxx WiFi network you may be asked to conf...

Page 26: ...een of control app 9 1 4 Setting up weekly operation program Up to 4 different ventilation modes can be set for each day of week Set the desired operation program for the selected day or days of the w...

Page 27: ...Ventilation boost activation After the selected time previously set or scheduled ventilation intensity will be activated 9 1 6 Away Activate selected decreased ventilation intensity until the selected...

Page 28: ...clicking RESET button order replacement filter set by clicking troley icon Figure 19 Filter menu 9 1 8 Resetting WiFi controller to factory defaults If it is necessary to reset WiFi controller to fact...

Page 29: ...touchscreen display 9 2 1 Standby mode Touchscreen display of control panel will only display the time of day in standby mode if the Unit is switched off If the Unit is in operation settings of desire...

Page 30: ...valve state depends on device configuration Preheater state This menu enables to Activate the boost mode by single touch of button Access the settings menu Set the desired room air temperature Set the...

Page 31: ...cold season air supplied to the room can be additionally heated by a separately purchased duct heater installed in the ventilation system IMPORTANT Availability of feature depends on device configurat...

Page 32: ...ode settings menu Weekly operation program will be saved by clicking back arrow button IMPORTANT Click on the round button next to schedule button in main menu to activate a weekly operation program G...

Page 33: ...rer of the Unit or its local representative You may control the Unit by app installed on smartphone or tablet by purchasing the WiFi controller 9 3 Control panel with a knob Control panel with a knob...

Page 34: ...r filters IMPORTANT Higher than usually power consumption is to be expected when the Unit is operating in this mode 9 3 3 Failure indicator The flashing red led indicates that failure of the Unit comp...

Page 35: ...ter the Unit reset procedure has been performed contact manufacturer of the Unit or its local representative 9 3 5 Resetting the filter lifetime meter Filter lifetime meter has to be reset after air f...

Page 36: ...setting P2 boost mode power setting P3 supply fan power adjustment P4 exhaust fan power adjustment S1 reset button S2 switches for disabling OFF or activating ON boost 1 and away 2 functions Figure 2...

Page 37: ...air filters Shut down the Unit by control panel make sure that fans have completely stopped Open the lid of the filter that you intend to change marked by OXYGEN by firmly gripping it and pulling out...

Page 38: ...rs can result in ventilation power decrease and higher than usually power consumption IMPORTANT Only original manufacturer recommended filters should be used The use of low quality third party filters...

Page 39: ...is connected to mains supply Power circuit breaker is ON If RESET button is being displayed on touchscreen control panel refer to section 9 2 5 Failure indication or flashing red led of control panel...

Page 40: ...as JSC Company code 304288834 VAT code LT100010366918 Bank account LT42 7044 0600 0810 3886 SWIFT CBVILT2X AB SEB bank Address Birzelio 23 osios g 23G 50220 Kaunas Lithuania Phone No 370 627 26666 oxy...

Reviews: