14
SECTION B: COUNTDOWN PROGRAMMING
Section B of the interface is used to program the set time to close.
This is set with the SECOND buttons in 100, 10, and 1 second intervals. The countdown seconds can be set
from 1 second up to 300 seconds (5 minutes).
1. Determine the countdown and press each button until timer is set.
2. Press the SET button to lock in the desired countdown. The display will read the countdown for
approximately 10 seconds.
PROGRAMMING THE INTERFACE
SECTION A: STATUS LEDs
Section A of the Interface will show the status of various functions of the operator and timer. Used for
convenience and troubleshooting.
LED-1 = 15V. Shows presence of control voltage.
LED-2 = 5V. Shows presence of control board voltage.
LED-3 = DOOR OPENING: Activates when door is moving to the up limit.
LED-4 = DOOR CLOSING: Activates when door is moving to the down limit.
LED-5 = OPEN LIMIT: Illuminated when door is on the UP limit.
LED-6 = CLOSE LIMIT: Illuminates when door is on the DOWN limit.
LED-7 = TIMER: Flashes when countdown timer is activated and counting.
LED-8 = RESET EVENT: Flashes when a timer initiate input is activated.
SECTION C: GENERAL PROGRAMMING
Section C of the interface is used to program various parameters of the board. See Chart.
LABEL
FUNCTION
ODC-STB
Enables/Disables monitoring of the photocell input to the opener.
ETR
Enable Timer Via Radio - Countdown initiated by remote control.
ETO
Enable Timer Via Open Button - Countdown initiated by Open button.
DISP
Display OPEN message or blank display when door is open and static
T2/T3
Select between T2 or T3 type safety edge sensors.
T2
T3
ETR
ETO
DISP
ODC/
OFF
OFF
OFF
OFF
STB
SET to T3 if a monitored edge sensor is used.
SET to T2 if a non-monitored or no edge is used.
SET to ON if countdown is to be timed to close with a remote
control.
SET to ON if countdown is to be timed to close with the OPEN
button.
SET to ON if display should show OPEN when door is open.
SET to OFF if display should remain black when door is open.
SET to OFF if timer should ignore an ODC/STB safety reversal.
SET to ON if display should read
Obst
upon safety reversal.