Switching on the “OV-DMC 3”
“OV-DMC 3”
7. Switching on the
“OV-DMC 3”
f
Press the “On/Off” button (see (3) in
) for around 5 seconds.
Z
The LED next to the “On/Off” button will
illuminate green.
Z
All LEDs flash simultaneously while the
appliance is starting.
Z
The LED next to the “WLAN” (Wi-Fi) button
will flash red while the “OV-DMC 3” carries
out adjustments.
Z
The LED next to the “WLAN” (Wi-Fi) button
will flash magenta after a few seconds.
Z
The appliance is ready for operation.
8. Operation
The measurement process is de-
scribed in the app relevant to your
operating system.
WARNING
Risk of scalding due to hot
fluids!
There is a risk of scalding caused by
unintentional discharge of hot water or
steam.
f
Allow the system to cool down.
f
Observe the permissible operating
pressures.
f
Wear suitable protective clothing.
f
Keep children and untrained per-
sonnel away.
WARNING
Risk of burns due to hot compo-
nents and surfaces
f
Wear protective clothing to avoid
unprotected contact with hot sys-
tem components and fittings.
NOTICE
Measurement errors caused
by dirty measuring hoses
f
Check the measuring hoses for
unobstructed water flow.
f
Clean or replace the dirt strainers
if they are dirty.
The “OV-DMC 3” software enables valves to
be adjusted using a range of measurement
methods. During this process measurement
values (differential pressure and flow rate) are
given and displayed graphically. The supply
flow and return flow temperatures can addition
-
ally be determined if temperature sensors are
connected. The measured values are used to
determine, display, and log the presets for the
valves.