![oventrop OV-DMC 3 Operating Instructions Manual Download Page 25](http://html1.mh-extra.com/html/oventrop/ov-dmc-3/ov-dmc-3_operating-instructions-manual_1662719025.webp)
106927880-V02.03.2019
25
“OV-DMC 3”
Technical description
EN
(1)
WLAN / Wi-Fi
-
RED (flashing)
The appliance is
starting
- MAGENTA
(flashing)
The appliance is
ready to us as an
access point
- MAGENTA
(continuously
illuminated)
The appliance is
connected to a
client as an access
point
- BLUE (continu-
ously illumi-
nated)
This function is not
yet available for
this model
f
Check to see
whether new
firmware is
available for
installation
using the app.
(2)
WSN
This function is not
yet available for
this model
f
Check to see
whether new
firmware is
available for
installation
using the app.
(3)
On/Off
- GREEN
The appliance is
switched on
- WHITE
The appliance is
changing mode
3.3 Technical data
“OV-DMC 3”
Media temp.
-20 °C to +120 °C
Ambient temp.
0 °C to +40 °C
Storage temp.
-20 °C to +55 °C
Operating pres-
sure
max. 25 bar (2500 kPa)
Differential pres-
sure
max. 2.5 bar (250 kPa)
Measuring range
-20 °C to +120 °C
Air humidity
max. 90 % RH
Temperature
sensor type
PT 1000
Power supply
LiFe battery or using
enclosed USB power
supply unit.
Operating volt-
age
5 V DC
Power consump-
tion
500 mA
Protection class
IP64
Interface
WLAN / Wi-Fi
Radio frequency
2.4 GHz
Transmission
power
Max. 10 mW
Range inside
buildings
Dependent on materials
and sources of interfer-
ence
Media
Water and suitable
water-glycol mixtures
in accordance with
VDI 2035/ÖNORM 5195
Not suitable for steam,
media containing oil, or
aggressive media
Materials
Plastic with brass
connection couplings
and measurement
adapter
Dimensions
Measuring case
with accessories:
370 x 295 x 170 mm
(L x W x H)
Measuring sensor:
107 x 165 x 40 mm
Weight
Measuring case with
accessories: 4300 g
Measuring sensor: 650g
Power supply unit
Type
Friwo FW8002USB/05
Input
100-240 V ~/50-60 Hz/
160-80 mA
Output
5 V
/1400 mA