11
|
Overview
”S-Bus interface adapter“
The ”S-Bus interface adapter“ is used for the speed con-
trol of a pump via a PWM or 0 - 10 V signal. Via the S-Bus
the adapter receives information from the controller about
speed. The speed is converted into a PWM or direct volt-
age signal and put out to the corresponding terminals.
A signal corresponding to the speed is only available if the
corresponding relay is designed for pump speed control.
Otherwise, a signal – depending on the position of the
relay – for the on or off state is transmitted.
Technical data
housing:
plastic
Protection type:
IP 20 (EN 60529)
Ambient temperature:
0 … 70 °C
Dimensions:
95 × 70 × 25 mm
Mounting:
Wall mounting is possible (but not required)
Display:
7-segment LED display
Power supply:
Mains adapter power supply: 100 … 240 V~ / 50 … 60 Hz
Interface adapter power supply: 12 V / 1 A
5.5 × 2.1 mm
Interface:
S-Bus
Included:
1 × mains adapter 12 V / 1 A / 5.5 x 2.1 mm
1 × S-Bus cable 1.5 m
1 × accessory bag containing
2 × screw and wall plug
4 × self-adhesive, skid-proof rubber pad
• Speed control of high-efficiency pumps for
controllers without integrated PWM outputs
• Easy to install
• convertible from PWM to 0-10 V signal
• With 7-segment LED display
oventrop
Artikel-Nr. 1369531
Input: DC 12 V / 1 A
IP20
Adapter S-Bus
PWM
0-10 V
Adapter S-Bus
-
+