Display of the next valve
(2) which can be measu -
red in the regulating
group. Other valves
may also be chosen
be means of the
keys and .
The numbering of valves
once determined must
be observed.
Go to next menu win-
dow by using the key
“OK”.
23
---------------------
---------------------
in object
OV-BALANCE
!! Attention !!
3.0
reset valve
OV-Balance
Measurement
Enter nominal flow rate
for valve no. 1 (e.g. 500
l/h).
Go to next menu win-
dow by using the key
“OK”.
---------------------
---------------------
in object
OV-BALANCE
Cellar G.: 1 / 1
Hydrocon R DN 20
3.0 preset’g 0.0
mbar
500 l/h
>STORE<
The command for
storing appears.
Go to next menu win-
dow by using the key
“OK”.
---------------------
---------------------
in object
OV-BALANCE
Cellar G.: 1 / 1
Hydrocon R DN 20
3.0 preset’g. 0.0
mbar
500 l/h
>STORE<
User information.
Set back valve to previ-
ous presetting (e.g. 3.0).
Go to next menu win-
dow by using the key
“OK”.
---------------------
---------------------
in object
OV-BALANCE
Cellar G.: 1 /
2
----------- DN 00
3.0 preset’g. 0.0
mbar
l/h
>STORE<